16-TON PURY-P192TSHMU-A-BS

(Consists of Two PURY-P96THMU-A-BS and One CMY-R100VBK Twinning Kit)

OutdOOr VrFZ HEAt rEcOVEry SyStEM FEAturES

• 3-phase, 208/230V systems

• Modular variable refrigerant flow zoning (VRFZ) systems;

smaller capacity units can be piped together to form a single,

large-capacity two-pipe system

• Compact size for each outdoor module; can be transported

through standard-sized doorways for installation

• Required Twinning Kit allows for easy field piping connection

• Selectable fan static, 0.12 or 0.24"WG external static

pressure; factory set to 0"WG

• Max. Total Refrigerant Piping Length: 1,804' (P72,96); 1,969'

(P120,144,168); 2,461' (P192); 2,625' (P216,240); Max.

Line Length: 541'; Max. Control Wiring Length: 1,650'

• Connects to CITY MULTI indoor units; controlled via

CITY MULTI Controls Network (CMCN)

• External finish: Pre-coated Galvanized-steel Sheets with

thermoset polyester-resin

• Operating Temperature Range

Cooling (Outdoor): 23° ~ 109°F (-5° ~ +43°C) DB

Heating (Outdoor): -4° ~ +60°F (-20° ~ +16°C) WB

** Each individual module requires a separate electrical connection. Reference electrical data for each individual module.

PURY-P96THMU-A-BS

PURY-P96THMU-A-BS

OPtIONAL PArtS

□ Twinning Kit*.…………………………………...……...CMY-R100VBK

□ Branch Joint (T-Branch: ≤ 72,000 Btu/h).………….CMY-Y102S-G2

□ Branch Joint (T-Branch: 73,000-144,000 Btu/h).……….CMY-Y102L-G2

□ Joint Adapter (Port Connector>54,000 Btu/h).………….CMY-R160J

□ Main BC Controller.…………………..CMB-P108/1010/1013/1016NU-GA

□ Sub BC Controller.…………………CMB-P104/108NU-GB/-1016NU-HB

* Twinning Kit is necessary to combine the refrigerant flows of the

modules and is included in the outdoor unit set.

Specifications

System

Module 1

Module 2

Unit Type

PURY-P192TSHMU-A-BS

PURY-P96THMU-A-BS

PURY-P96THMU-A-BS

Nominal Cooling Capacity

Btu/h

192,000

96,000

96,000

Nominal Heating Capacity

Btu/h

200,000

108,000

108,000

External Dimensions (H x W x D) In. / mm

Refer to Module Data

65 x 48-1/16 x 29-15/16 /

1,650 x 1,220 x 760

65 x 48-1/16 x 29-15/16 /

1,650 x 1,220 x 760

Net Weight

Lbs. / kg

1,170 / 530

585 / 265

585 / 265

Electrical Power Requirements

Voltage, Phase, Hertz

Refer to Module Data**

208-230V, 3-phase, 60Hz

Cooling Power Input

kW

17.04

Refer to System Data

Heating Power Input

kW

15.85

Cooling Current (208/230V)

A

52.5 / 47.5

Refer to System Data

Heating Current (208/230V)

A

48.8 / 44.2

Minimum Circuit Ampacity

(MCA)**

A

Refer to Module Data**

35 / 32**

35 / 32**

Maximum Overcurrent

Protection (MOCP)**

A

Refer to Module Data**

40 / 40**

40 / 40**

Piping Diameter

Refer to System Data

From Twinning Kit to Indoor Units

(Brazed) (In. / mm)

Liquid (High Pressure)

7/8 / 22.2

Gas (Low Pressure)

1-1/8 / 28.58

From Modules to Twinning Kit

(Brazed) (In. / mm)

Liquid (High Pressure)

Refer to Module Data

3/4 / 19.05

3/4 / 19.05

Gas (Low Pressure)

7/8 / 22.2

7/8 / 22.2

Indoor Unit

Total Capacity

50 to 150% of ODUs

Refer to System Data

Model / Quantity

P06 ~ P96 / 1 to 48

Sound Pressure Levels

dB(A)

62.0

58.0

58.0

Fan

Refer to Module Data

Type x Quantity

Propeller Fan x 1

Propeller Fan x 1

Airflow Rate

cFM

7,750

7,750

Direct-drive Inverter Motor Output

kW

0.92

0.92

Compressor Operating Range

9% to 100%

Refer to System Data

Compressor Type x Quantity

Refer to Module Data

Inverter-driven Scroll Hermetic x 1 Inverter-driven Scroll Hermetic x 1

Compressor Motor Output

kW

7.0

7.0

Compressor Crankcase Heater

kW

0.057

0.057

Refrigerant

Refer to Module Data

R410A

Lubricant

MEL32

High-pressure Protection Device

Refer to Module Data

601 psi / 4.15 MPa

601 psi / 4.15 MPa

Compressor / Fan Protection Device

Overheat Protection / Thermal Switch Overheat Protection / Thermal Switch

Inverter Protection Device

Overheat / Overcurrent Protection Overheat / Overcurrent Protection

Blue Fin Anti-corrosion Protection:

Cellulose- and polyurethane-resin coating treatment applied to condenser coil that protects it from air contaminants;

≥1μm to 1.5μm thick; Salt Spray Test Method - no unusual rust development to 960 hours.