Lennox 15CHAX Series - Manual

Lennox 15CHAX Series

Lennox 15CHAX Series – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
9 Page 9
10 Page 10
11 Page 11
12 Page 12
13 Page 13
14 Page 14
Page: / 14

Table of Contents:

  • Page 3 – For use as a cooling unit.
  • Page 4 – WARNING; Product contains fiberglass wool.; Location Selection; CAUTION; NOTE − Length of forks must be a minimum of 42 inches.; Figure 1; Clearances; Figure 2
  • Page 5 – Existing Common Vent Systems; must; Condensate Drain; Figure 3; Unit
  • Page 6 – Filters; The Healthy Climate; Supply & Return Duct Connections; They; air purification system (PCO20−28) is being; Compressors; Do not loosen compressor mounting bolts.; Electrical; Use wiring with a temperature limitation of 75
  • Page 7 – Optional Electric Heat; Typical Single−Phase Unit Wiring Connections; Figure 6
  • Page 8 – Figure 7; 5CHAX Series Packaged Electric Units
  • Page 9 – ADJUST
  • Page 10 – COOL; HEAT; The; CONTINUOUS FAN
  • Page 11 – Figure 9; IMPORTANT; Voltage within the range of
  • Page 12 – Status LED Condition
  • Page 13 – Unit Start−Up and Operation
  • Page 14 – Accessories
Loading the manual

01/08

*2P0108*

Page 1

505,201M

*P505201M*

RETAIN THESE INSTRUCTIONS

FOR FUTURE REFERENCE

2006 Lennox Industries Inc.

Dallas, Texas, USA

Table of Contents

Shipping & Packing List

1

. . . . . . . . . . . . . . . . . . . . . . . . .

Unit Dimensions

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Parts Arrangement

3

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

General

3

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Requirements

3

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Location Selection

4

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Rigging & Setting Unit

4

. . . . . . . . . . . . . . . . . . . . . . . . . .

Clearances

4

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Existing Common Vent Systems

5

. . . . . . . . . . . . . . . . .

Condensate Drain

5

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Filters

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Supply & Return Connections

6

. . . . . . . . . . . . . . . . . . . .

Compressors

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Electrical

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Blower Control Board

9

. . . . . . . . . . . . . . . . . . . . . . . . . . .

System Operation Monitor

11

. . . . . . . . . . . . . . . . . . . . . .

Unit Start−Up and Operation

13

. . . . . . . . . . . . . . . . . . . .

Condenser Fan Clearances

14

. . . . . . . . . . . . . . . . . . . . .

Maintenance

14

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

INSTALLATION
INSTRUCTIONS

15CHAX SERIES UNITS

PACKAGED ELECTRIC UNIT

(2−5 TONS)

505,201M (38152A082)
01/08
Supersedes 05/06

Shipping & Packing List

1 − Assembled packaged electric unit

As soon as the unit is received, it should be inspected for
possible damage during transit. If you find any damage, im-
mediately contact the last carrier.

WARNING

Improper installation, adjustment, alteration, service
or maintenance can cause property damage, person-
al injury or loss of life. Installation and service must
be performed by a licensed professional installer (or
equivalent) or service agency.

WARNING

If this unit is to be installed in a mobile or manufac-
tured home application, the duct system must be
sized to achieve static pressures within the
manufacturer’s guidelines. All other installation
guidelines must also be followed. Failure to do so
may result in equipment damage, personal injury
and improper unit performance.

CAUTION

Danger of sharp metallic edges. Can cause injury.
Take care when servicing unit to avoid accidental
contact with sharp edges.

WARNING

Electric shock hazard. Can cause injury
or death. Before attempting to perform
any service or maintenance, turn the
electrical power to unit OFF at
disconnect switch(es). Unit may have
multiple power supplies.

Litho U.S.A.

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 3 - For use as a cooling unit.

Page 3 Parts Arrangement General These installation instructions are intended as a generalguide only, for use by an experienced, licensed contractor(or equivalent). The 15CHAX units are single−package electric unitsdesigned for outdoor installation on a rooftop or a slab. Theunits are equipped with ...

Page 4 - WARNING; Product contains fiberglass wool.; Location Selection; CAUTION; NOTE − Length of forks must be a minimum of 42 inches.; Figure 1; Clearances; Figure 2

Page 4 For installation on combustible material. WARNING Product contains fiberglass wool. Disturbing the insulation in this product duringinstallation, maintenance, or repair will expose youto fiberglass wool dust. Breathing this may causelung cancer. (Fiberglass wool is known to the Stateof Califo...

Page 5 - Existing Common Vent Systems; must; Condensate Drain; Figure 3; Unit

Page 5 Existing Common Vent Systems The 15CHAX packaged cooling units with auxiliary electricheat may replace an existing furnace which is being re-moved from a venting system commonly run with separategas appliances. In this case, the existing vent system islikely to be too large to properly vent t...