Honeywell T7984 C- Manual

Honeywell T7984 C

Honeywell T7984 C– Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
Page: / 8

Table of Contents:

  • Page 2 – SPECIFICATIONS; ORDERING INFORMATION
  • Page 3 – INSTALLATION; Location; CAUTION
  • Page 4 – WIRING; SEQUENCE
  • Page 5 – DIP SWITCH SETTINGS
  • Page 6 – DIP SWITCH SETTING
  • Page 7 – Output 1, Modulating Analog Output 2 to
  • Page 8 – Output 2, Modulating Analog Output 2 to; CHECKOUT; Service LED
Loading the manual

T7984 A,B,C Electronic Modulating Control

Thermostats

PRODUCT DATA

APPLICATION

These microprocessor-based thermostats provide

proportional - integral (PI) individual room temperature control

in zoned commercial Heating, Ventilating, and Air

Conditioning systems such as hydronic heating and/ or

cooling, pressure dependent VAV or by-pass box with or

without terminal reheat.

The T7984 family provides modulating analog 2 to 10 Vdc

control. Optional features include automatic heat/ cool

changeover, reheat control, remote night setback with local

timed override, and remote sensor on VAV models.

FEATURES

PI (proportional and integral) control action provides

accurate, stable room temperature control.

T7984 models are used with Series 70 direct-coupled

damper actuators such as ML7161 or ML7984, or with

valve actuators such as ML7285, ML7421, VC7930 or

M7410.

All models feature user-friendly set point knob.

All models feature output status LEDs for installer

check-out.

Locking cover and range stops are standard.

Night setback models feature selection of two different

offset temperatures and use central time switch

control.

Night setback models feature 2 1/2 hour local timed

override.

Heat/cool models feature automatic changeover with

3° or 5°F (1.5°C or 3°C) selectable Zero Energy Band

(Z.E.B.) to meet requirements of ASHRAE 90.1

Heat/cool models have installer-definable setpoint at

midpoint of Z.E.B, at heating setpoint, or at cooling

setpoint.

Reheat models feature fast/slow response selection to

match heating system dynamics.

DIP switch selectable 75°F (24°C) high limit heating

setpoint and low limit cooling setpoint.

Horizontal and vertical covers included.

Contents

Application ......................................................................... 1

Features ............................................................................ 1

Specifications .................................................................... 2

Ordering Information ......................................................... 2

Installation ......................................................................... 3

T7984A .............................................................................. 4

T7984B .............................................................................. 5

T7984C.............................................................................. 6

Checkout ........................................................................... 8

95C-10815-2

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Other Manuals for Honeywell T7984 C

Summary

Page 2 - SPECIFICATIONS; ORDERING INFORMATION

T7984 A,B,C ELECTRONIC MODULATING CONTROL THERMOSTATS SPECIFICATIONS IMPORTANT The specifications given in this publication do not include normal manufacturing tolerances. Therefore, this unit may not exactly match the listed specifications. Also, this product is tested and calibrated under closely ...

Page 3 - INSTALLATION; Location; CAUTION

T7984 A,B,C ELECTRONIC MODULATING CONTROL THERMOSTATS Table 2. Option Settings Parameter Selection T7984 Model A B C Reheat Time Constant Fast (7.5 min.); or Normal (15 min.) • Zero Energy Band 3°F (1.5°C); or 5°F (3°C) • • Setpoint Definition Heating; Cooling or H/C midpoint • • Night Setback 5°F (...

Page 4 - WIRING; SEQUENCE

T7984 A,B,C ELECTRONIC MODULATING CONTROL THERMOSTATS T7984A Output 1 analog 2œ10V Output 2 on/off Mode input jumper Changeover input for Out 1 Day/Night mode (NSB) Remote sensor option 75°F setpoint limit Cooling and/or heating X X WIRING To install a remote duct or room temperature sensor, adust D...