INSTALLATION INSTRUCTIONS
62- 0179
T7047C,G,H
Remote Space Sensors
APPLICATION
The T7047 Remote Space Sensors are used in Series 70
Control Systems to provide modulating space
temperature control.
SPECIFICATIONS
IMPORTANT
The specifications given in this publication do
not include normal manufacturing tolerances.
Therefore, this unit may not exactly match the
listed specifications. This product is tested and
calibrated under closely controlled conditions,
and some minor differences in performance can
be expected if those conditions are changed.
Models:
T7047C: 2-wire remote sensor with no internal
adjustment means (requires remote setpoint device
such as S963B, T7067B, and T7080B).
T7047C1009: 2-wire remote sensor for use with
control systems such as M7044 and M7045
Motors.
T7047C1025: 2-wire remote sensor for use with control
systems such as the W927, W960, and W973.
T7047C1082: 2-wire remote sensor for use with
T7080B Transmitter in W7080 Multizone Control
System.
T7047G: 2-wire remote sensor with no internal
adjustment means (requires remote setpoint device
such as S963B, T7067B or T7080B).
T7047H: Thin-film, platinum 1K (at 0°C) temperature
sensor only. For use with the Excel 80/100/500/600
Controllers.
Dimensions:
Mounting:
Mounts on wall or 2 x 4 in. vertical outlet box
with screws provided.
Temperature Sensor:
Thermistor-resistor element.
Cover Thermometer (available on most models):
Element: Bimetal.
Range: 55 to 95°F (13 to 35°C).
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
T7047C,G,H REMOTE SPACE SENSORS 3 62-0179 INSTALLATION When Installing this Product... 1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition. 2. Check the ratings given in the instructions and on the product to make sure the product is s...
T7047C,G,H REMOTE SPACE SENSORS 62-0179 4 Fig. 6. T7047G1000 Remote Sensor resistance change with change in temperature. Fig. 7. T7047H1008 Remote Sensor resistance change with change in temperature. Wiring IMPORTANT All wiring must agree with applicable codes, ordinances and regulations. Fig. 8 thr...
T7047C,G,H REMOTE SPACE SENSORS 62-0179 6 Fig. 17. T7047C1082 used as a remote sensor with T7080B Thermostat. 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. TERMINALS 3, 7 AND 8 ARE ALL EQUIVALENT COMMON TERMINALS. RESISTOR AND TIME SWITCH IN SERIES BETWEEN TERMINALS 5...