DEH40212 Installation Instructions
1
DESCRIPTION
The ProSys Lighting Control System is a small network of
relay panels and occupant control switches linked by a 4-wire
dataline. Together, these devices form a reconfigurable
switching platform — one that uses “softwiring” instead of
hardwiring to link occupant switches to relays. Scheduling
capability can be readily added by simply mounting an
RCLK8PS Softwired Clock to the DIN rail in any relay panel.
The RINTERxxxxPS(P)
1
is the interior for a
ProSys
Lighting Control System
Relay Panel.
The complete relay
panel assembly will include the following:
1. Tub (RTUBxx)
2. Interior (RINTERxxxxPS or RINTERxxxxPSP)
3. Power Supply (RPWRxxx)
4. Cover (RCOVxxxx)
This instruction sheet will show you how to:
1. Install the Relay Panel(s)
2. Install and Test the Dataline
3. Document the Relay Panels
Full descriptions of the installation and operation of Softwired
Switches and the Softwired Clock and other optional
automation devices are located in other sections of this
manual and are provided with each hardware unit.
Before starting, read the following installation
instructions. If you have questions, call GE Total
Lighting Control Service at:
1-877-584-2685 (LTG-CNTL) in the USA and Canada.
RINTER2424PSP 24-Relay Interior shown with RTUB24
ProSys Lighting Control System
Catalog Number RINTERxxxPS(P)
GE Total Lighting Control
ProSys™ Lighting Control System Relay Panels
These instructions do not cover all details or variations in equipment nor do they provide for every possible contingency that may be met in connection with
installation, operation or maintenance. Should further information be desired or should particular problems arise that are not covered for the purchaser's purposes,
the matter should be referred to the GE Company.
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Was this manual helpful?
About this manual
- Brand
- GE
- Model
- General Electric Indoor Furnishings RINTERxxxPS(P)
- Document type
- User Manual
- Language(s)
- English
- Pages
- 6
- File size
- 230.1 KB
- Format
Summary
2 DEH40212 Installation Instructions J2 115VAC NEU GRD GE Lighting Controls RELAY PANEL INSTALLATION CAUTION: Make sure all power is OFF before wiring.Do not energize wiring until the unit is fully assembled.Conform to all applicable codes. ILLUSTRATION NOT TO SCALE If you have purchased the ProSys ...
DEH40212 Installation Instructions 3 TO RELAY RR7P RELAY SHOWN LED INDICATOR RELAYCONTROLBUTTON POWER UP AND TEST RELAYS 1. Apply power to the power supply only. As shown in Figure 3 , to the right, press the Relay Control Button next to each relay’s yellow plug-in termination to toggle it ON/OFF. T...
4 DEH40212 Installation Instructions The dataline connects the relay panels, switches and optionalcontrol modules. Within the 4-wire dataline are two twistedpairs: the red and black wires, carrying data; and the blue andwhite wires, providing power to the dataline switches andcontrol modules. For si...