Emerson iCOM - Manual

Emerson iCOM

Emerson iCOM – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
9 Page 9
10 Page 10
11 Page 11
12 Page 12
13 Page 13
14 Page 14
15 Page 15
16 Page 16
17 Page 17
18 Page 18
19 Page 19
20 Page 20
21 Page 21
22 Page 22
23 Page 23
24 Page 24
25 Page 25
26 Page 26
27 Page 27
28 Page 28
29 Page 29
30 Page 30
31 Page 31
32 Page 32
33 Page 33
34 Page 34
35 Page 35
36 Page 36
37 Page 37
38 Page 38
39 Page 39
40 Page 40
41 Page 41
42 Page 42
43 Page 43
44 Page 44
45 Page 45
46 Page 46
47 Page 47
48 Page 48
49 Page 49
50 Page 50
51 Page 51
52 Page 52
53 Page 53
54 Page 54
55 Page 55
56 Page 56
57 Page 57
58 Page 58
59 Page 59
60 Page 60
61 Page 61
62 Page 62
63 Page 63
64 Page 64
65 Page 65
66 Page 66
67 Page 67
68 Page 68
69 Page 69
70 Page 70
71 Page 71
72 Page 72
73 Page 73
74 Page 74
75 Page 75
76 Page 76
77 Page 77
78 Page 78
79 Page 79
80 Page 80
81 Page 81
82 Page 82
83 Page 83
84 Page 84
Page: / 84

Table of Contents:

  • Page 3 – TABLE OF CONTENTS; COM D
  • Page 4 – ii; COM U
  • Page 5 – iii; FIGURES
  • Page 6 – iv; TABLES
  • Page 7 – Introduction; NTRODUCTION; Features; Large and Small Displays; Liebert iCOM with small display; Wall Mount Large Display
  • Page 8 – Liebert iCOM Display Components and Functions; IEBERT; ISPLAY; The small and the large display have a common key layout, as shown in; Figure 2; ESC
  • Page 9 – Table 1; Icon
  • Page 10 – Figure 3
  • Page 11 – Navigating Through the Liebert iCOM Menus; Accessing Submenus on Small Displays; Figure 5; Accessing Submenus on Large Displays; Figures 6; Entering a Password on page 6; NOTE
  • Page 12 – The User menu password is 1490 the Service menu password is 5010.; Status Menu
  • Page 13 – Figure 6
  • Page 14 – Viewing Multiple Units with a Networked Large Display; Figure 7; System
  • Page 15 – Figure 8; EVENT; SET
  • Page 16 – Table 2
  • Page 17 – Figure 9; SERVICE
  • Page 18 – Operation; PERATION; - The Temperature Setpoint parameter is; Single Unit Functions; shut down
  • Page 19 – Autorestart; Shutdown; Chilled Water Units with Variable Speed Motor; liSlot 485 card), which then transmits to the unit local control.
  • Page 20 – Low-Pressure Time Delay; Pump Down; High Pressure Alarm
  • Page 21 – Digital Scroll High Temperature; and OFF time settings.
  • Page 22 – Motorized Ball Valve in Digital Scroll Units; Motorized Ball Valve Manual Mode; MBV Operation After Compressor is Turned Off; itself for initial startup.; of the digital cycle.
  • Page 23 – Temperature Control—Single Source Cooling (No Extra Cooling Coil); illustrates how the; Figure 11 Temperature proportional band; for more on using this feature.; band
  • Page 24 – compressors with or without unloaders.; Compressor Proportional Bands; One Single-Step Compressor Without Unloaders—One-Step
  • Page 25 – Two Compressors With Unloaders—Four-Step
  • Page 26 – Digital Scroll Compressors
  • Page 27 – after that the stepping starts.; Temperature Control—Second Cooling Source; Delta T (Temperature Difference) Between Room and Glycol; contact closure; Cooling
  • Page 28 – cooling valve band will take place (see; Figure 18 Second cooling source and compressorized cooling; —This feature permits the user to select the minimum
  • Page 29 – GLYCOOL; water temperature is 3; Temperature Control—Reheat; trolled by the Temperature Proportional Band, explained in; Band; through 3 are switched On, as shown in; Table 4; Type
  • Page 31 – Tight Mode; when the SCR Control Type is set to Tight mode.
  • Page 32 – Standard Mode; ing as described in
  • Page 33 – Humidity Control; setpoint and separates the two halves of the proportional band.; Figure 22 Humidity proportional band
  • Page 34 – Infrared Humidifier; ifiers cannot be driven in proportional mode.; External Humidifier Control—Optional; Parameter
  • Page 35 – Dehumidification Low Limit; the Service menu under Setpoints.; Low Limit 1; not be visible and will be inactive.; Low Limit 2; Dehumidification Compressor Quantity; outlines; WARNING on page 30; Temperature Setpoint:; Tight mode, then Low Limit 2 will be ignored, see; Table 6; Available to Set Value; Low Limit 2 only
  • Page 36 – Reheat During Dehumidification; Delayed; Control Types; Temperature and Humidity Control Types; Proportional; WARNING
  • Page 37 – Humidity Sensor Reading Control Types; occurred, the RH could be low enough to activate the humidifier.
  • Page 38 – culates the output to the actuator from the smaller deviation.; Event Types and Properties; . The threshold settings are located in both the User and Service
  • Page 39 – Screen 2 of 7. The choices for the customer inputs are shown in; along with their associated; Event; Table 7; Setting
  • Page 40 – : If this event occurs, it will only be entered into the event log.
  • Page 41 – Table 8
  • Page 42 – OSSIBLE
  • Page 43 – Next Maintenance Calculation; since the last maintenance.; Calculation of Next Maintenance and Diagnostics; with the pre-alarm maintenance time and factors in the alarm.
  • Page 44 – Parameters for Next Maintenance Calculation; —can be set as one to 12 months or to zero, which disables mainte-
  • Page 45 – Teamwork; EAMWORK; Teamwork Mode; Teamwork Modes; Standby and Cascade on
  • Page 46 – The number of available units is calculated like:; Figure 23 Teamwork Mode 1 with two cooling units
  • Page 47 – not adjust the proportional band.; Standby and Cascade; Teamwork Mode 1; deadband and related settings may differ.
  • Page 48 – Installing a Liebert iCOM Unit-to-Unit Network; status of individual units or of the entire system.; Placement of Cooling Units; addition to general good wiring practices, take into account:; Minimum Network Switch Requirements; The Liebert vNSA; Liebert vNSA on page 47
  • Page 49 – Wiring for Unit-to-Unit Communications—U2U; Liebert iCOM U2U Ethernet Network; technical issues contact:; [email protected]
  • Page 50 – Small Displays; Two cooling units, each with a small display; Large Displays; unit from the factory.
  • Page 51 – Figure 25 Wiring a small display for stand-alone operation
  • Page 52 – Figure 27 Wiring a large display for stand-alone operation
  • Page 53 – Figure 29 Liebert iCOM input-output control board; Liebert vNSA; in; Ports available for connecting Liebert iCOM control devices
  • Page 54 – Figure 30 Liebert vNSA with optional remote large display; Web system and
  • Page 55 – Mounting a Large Display on a Wall; OUNTING; Necessary Mounting Items; Elliptical Slot Mounting; OR; Keyhole Slot Mounting
  • Page 56 – Figure 31 Liebert iCOM display dimensions; Primary; FRONT VIEW
  • Page 57 – User Menu Parameters; SER; check; Spare Part List—Large Display Only; Setpoints parameters
  • Page 58 – Set alarms parameters
  • Page 59 – Active Alarms; Permits viewing all current, active alarms.; Active alarms parameters
  • Page 60 – Total run hours parameters
  • Page 61 – Service contacts parameters
  • Page 62 – Service Menu Parameters; ERVICE; ters is; Function
  • Page 63 – Unit Diary—Large Display Only; Unit diary parameters
  • Page 64 – See; Maintenance / wellness settings parameters
  • Page 67 – Diagnostics / service mode parameters
  • Page 75 – Sensor calibration / setup parameters
  • Page 76 – System / network setup parameters—large display only
  • Page 77 – Network setup parameters
  • Page 79 – Options setup parameters
  • Page 80 – Service contact info parameters
  • Page 81 – Notes
  • Page 84 – Precision Cooling
Loading the manual

Precision Cooling
For

Business-Critical Continuity™

Liebert

®

iCOM

User Manual - Intelligent Communications & Monitoring

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 3 - TABLE OF CONTENTS; COM D

i TABLE OF CONTENTS 1.0 I NTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....

Page 4 - ii; COM U

ii 3.9 Next Maintenance Calculation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 3.9.1 Calculation of Next Maintenance and Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 4.0 T EAMWORK . . . . . . . . . . . . . ....

Page 5 - iii; FIGURES

iii FIGURES Figure 1 Liebert iCOM components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Figure 2 Liebert iCOM display components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

Other Emerson Models