Emerson ASCO 5310 Single-Channel Remote Annunciator- User Manual
Emerson ASCO 5310 Single-Channel Remote Annunciator– User Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – Operation; Control key switch; Alarm silence button; Transfer; NOTICE
- Page 3 – -2 Load Retransfer to Normal source; Reset button; -1 Soft reboot reset
- Page 4 – Troubleshooting
ASCO 5310
User’s Guide
381333-316 A
ASCO Power Technologies
Page 1
User’s Guide
The ASCO Catalog 5310 ATS Remote Annunciator provides
remote visual status reporting and push-button testing of one
ASCO automatic transfer switch.
This User’s Guide provides operation information after the
ATS Remote Annunciator has been installed and configured.
It also includes basic troubleshooting.
Refer to
Installation Manual 381333-317
for mounting, wiring, and configuration.
Figure 1: Status lights and Transfer button
ATS Remote Annunciator
Catalog 5310
Figure 1 shows the status lights and
Transfer
button.
The
Normal source acceptable
light (upper left) is on when
the ATS controller accepts the utility source. This light is off
when the utility has failed.
The
Emergency source acceptable
light (upper right) is on
when the ATS controller accepts the generator source. This
light is off when the generator is unacceptable (low or high
voltage, low or high frequency, or generator is off).
The
ATS connected to Normal
light (center left) is on when the
load is being fed by the utility. It is off when it is disconnected
from the utility.
The
ATS connected to Emergency
light (center right) is on
when the load is being fed by the generator. It is off when it is
disconnected from the generator.
The
ATS & common alarm
light (lower left) is on when an
ATS or common alarm is received. It is off when the alarm is
cleared. See
Alarm silence button
, page 2;
Troubleshooting
,
page 4.
The
Transfer
light (lower right) is blinking when a load
transfer time delay is active. It is off when there is not a load
transfer time delay active. See
Flashing light (time delay)
,
page 3.
381333-316 A
TABLE OF CONTENTS
page
Operation
.
2-3
Control key switch .
2
Alarm silence button
.
2
Transfer test
.
2
Flashing light
.
3
Reset button
.
3
Troubleshooting
.
4
Normal source
acceptable
ATS connected
to Normal
ATS and
common
alarm
Emergency
source
acceptable
ATS connected
to Emergency
Transfer time
delay active
Utility
Generator
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
User’s Guide ASCO 5310 Page 2 ASCO Power Technologies 381333-316 A Operation The ASCO 5310 ATS Remote Annunciator communicates with an ASCO automatic transfer switch (ATS) to report its status. The ATS Annunciator polls the ATS and obtains its status. Lights indicate if the ATS is connected to the n...
ASCO 5310 User’s Guide 381333-316 A ASCO Power Technologies Page 3 Note: If Feature 2B transfer to emergency time delay is used, the transfer may not occur for up to 61 minutes (depending upon the ATS and the setting in the controller). To bypass (cancel) this time delay, press the Transfer button a...
User’s Guide ASCO 5310 Page 4 ASCO Power Technologies 381333-316 A Troubleshooting Numbe r Symptom Probable Cause Recommended Action 1 Power ON light is off The DC or AC power source is inadequate or off. Restore the DC or AC power supply. Check the terminals, fuse, circuit breaker. Refer to Install...