ASCO 5310

User’s Guide

381333-316 A

ASCO Power Technologies

Page 1

User’s Guide

The ASCO Catalog 5310 ATS Remote Annunciator provides
remote visual status reporting and push-button testing of one
ASCO automatic transfer switch.

This User’s Guide provides operation information after the
ATS Remote Annunciator has been installed and configured.
It also includes basic troubleshooting.

Refer to

Installation Manual 381333-317

for mounting, wiring, and configuration.

Figure 1: Status lights and Transfer button

ATS Remote Annunciator

Catalog 5310

Figure 1 shows the status lights and

Transfer

button.

The

Normal source acceptable

light (upper left) is on when

the ATS controller accepts the utility source. This light is off
when the utility has failed.

The

Emergency source acceptable

light (upper right) is on

when the ATS controller accepts the generator source. This
light is off when the generator is unacceptable (low or high
voltage, low or high frequency, or generator is off).

The

ATS connected to Normal

light (center left) is on when the

load is being fed by the utility. It is off when it is disconnected
from the utility.

The

ATS connected to Emergency

light (center right) is on

when the load is being fed by the generator. It is off when it is
disconnected from the generator.

The

ATS & common alarm

light (lower left) is on when an

ATS or common alarm is received. It is off when the alarm is
cleared. See

Alarm silence button

, page 2;

Troubleshooting

,

page 4.

The

Transfer

light (lower right) is blinking when a load

transfer time delay is active. It is off when there is not a load
transfer time delay active. See

Flashing light (time delay)

,

page 3.

381333-316 A

TABLE OF CONTENTS

page

Operation

.

2-3

Control key switch .

2

Alarm silence button

.

2

Transfer test

.

2

Flashing light

.

3

Reset button

.

3

Troubleshooting

.

4

Normal source

acceptable

ATS connected

to Normal

ATS and

common

alarm

Emergency

source

acceptable

ATS connected

to Emergency

Transfer time

delay active

Utility

Generator

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Operation; Control key switch; Alarm silence button; Transfer; NOTICE

User’s Guide ASCO 5310 Page 2 ASCO Power Technologies 381333-316 A Operation The ASCO 5310 ATS Remote Annunciator communicates with an ASCO automatic transfer switch (ATS) to report its status. The ATS Annunciator polls the ATS and obtains its status. Lights indicate if the ATS is connected to the n...

Page 3 - -2 Load Retransfer to Normal source; Reset button; -1 Soft reboot reset

ASCO 5310 User’s Guide 381333-316 A ASCO Power Technologies Page 3 Note: If Feature 2B transfer to emergency time delay is used, the transfer may not occur for up to 61 minutes (depending upon the ATS and the setting in the controller). To bypass (cancel) this time delay, press the Transfer button a...

Page 4 - Troubleshooting

User’s Guide ASCO 5310 Page 4 ASCO Power Technologies 381333-316 A Troubleshooting Numbe r Symptom Probable Cause Recommended Action 1 Power ON light is off The DC or AC power source is inadequate or off. Restore the DC or AC power supply. Check the terminals, fuse, circuit breaker. Refer to Install...