Page 3 - TABLE OF CONTENTS
i TABLE OF CONTENTS I MPORTANT S AFETY I NSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.0 I NTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1.1 System De...
Page 4 - ii
ii 5.0 G LYCOL /GLYCOOL-C OOLED M ODELS —S ELF -C ONTAINED C OMPRESSOR . . . . . . . . . . . . 41 5.1 Drycooler Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 5.2 Drycooler Installation . . . . . . . . . . . . . . . . ....
Page 5 - iii; FIGURES
iii FIGURES Figure 1 Removing Challenger from skid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Figure 2 Upflow (BU) cabinet dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....
Page 6 - iv; TABLES
iv TABLES Table 1 Unit net weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Table 2 Piping connection size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....
Page 7 - SAVE THESE INSTRUCTIONS; and maintenance of the Liebert Challenger 3000; NOTE; A pressure relief valve is provided with Liebert Lee-Temp; WARNING; deck for protection from rotating blower wheel(s) on upflow units.
1 I MPORTANT S AFETY I NSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important safety instructions that should be followed during the installation and maintenance of the Liebert Challenger 3000 ™ . Read this manual thoroughly before attempting to install or operate this unit.Only qualifie...
Page 8 - or near hot compressors, discharge lines, humidifiers and reheats.
2 NOTICE Risk of leaking water. Can cause equipment and building damage.This unit requires a water drain connection. It may also require an external water supply to operate.Improper installation, application and service practice can result in water leakage from the unit. Water leakage can result in ...
Page 9 - Introduction; NTRODUCTION; System Descriptions; systems do not include hot gas bypass.
Introduction 3 1.0 I NTRODUCTION 1.1 System Descriptions Challenger 3000 ™ environmental control systems are available in three main system configurations: • self-contained system with a scroll compressor in the room unit• self-contained chilled water system• split system with an evaporator section ...
Page 10 - Centrifugal Fan Air-Cooled; mounted indoors. Duct flanges are optional.
Introduction 4 1.1.3 Split Systems Each air-cooled split system consists of an evaporator section and one of the following condensing units. Prop Fan Air-Cooled Prop Fan units include scroll compressor, condenser coil, prop fan, high pressure switch, hot gas bypass and Liebert Lee-Temp head pressure...
Page 11 - Room Preparation; Table 1; Equipment Handling; addition to front service clearance.; Locate and remove shipping screw on fan motor base.
Installation (Applicable to all Models) 5 2.0 I NSTALLATION (A PPLICABLE TO ALL M ODELS ) 2.1 Room Preparation The room should be well insulated and must have a sealed vapor barrier. The vapor barrier in the ceiling can be a polyethylene film type. Use a rubber or plastic base paint on concrete wall...
Page 12 - NOTICE; will cause damage to the unit.; Liebert recommends using a fork lift (see Figure 1); • Once the unit is raised, the skid can be removed.; Figure 1; Model
Installation (Applicable to all Models) 6 2.4.1 Handling With Skid • Always keep the unit upright, indoors and protected from damage.• If possible, transport the unit using a fork lift; otherwise, use a crane with belts or cables, avoid- ing pressing on the top edges of the packaging. • If using a f...
Page 13 - Figure 2; Hi Static 3T
Installation (Applicable to all Models) 7 Figure 2 Upflow (BU) cabinet dimensions A Shaded area indicates a recommendedclearance of 34" (864mm) for componentaccess. Right side access suggested forG LYCOO L units. DPN000350Rev. 01 FRONT VIEW(front return configuration) 32-1/2" (826mm) Overall...
Page 14 - Figure 3; FLOOR CUTOUT DIMENSIONS
Installation (Applicable to all Models) 8 Figure 3 Downflow (BF) cabinet dimensions Shaded area indicatesa recommended clearance of34” (864mm) for componentaccess. Right side accesssuggested for G LYCOOL units DPN000351Rev. 01 32-1/2" (826mm) Overall Dimension 32-1/2" (826mm) Overall Dimensi...
Page 15 - Piping Considerations; comply with all applicable codes.; Table 2; Split System Fan Coil Unit Connection Sizes—in.
Installation (Applicable to all Models) 9 2.5 Piping Considerations All piping below the elevated floor must be located so that it offers the least resistance to air flow. Careful planning of the piping layout under the raised floor is required to prevent the air flow from being blocked. When instal...
Page 18 - Figure 6
Installation (Applicable to all Models) 12 Figure 6 Piping connections for split system fan coil units - Downflow models PIPING OUTLE T LOCATIONS(See Cabinet and FloorPlanning Dimensional Datafor Piping Opening Sizes.) DPN000376Rev. 01 Condensate Drain3/4" FP TField pitch a minimumof 1/8" (3...
Page 20 - Figure 8
Installation (Applicable to all Models) 14 Figure 8 Piping connections for water/glycol and GLYCOOL units - Downflow models DPN000364Rev. 01 Condensate Drain3/4" FPTField pitch a minimumof 1/8" (3.2mm) per ft. (305mm).The drain line must comply withall applicable codes Humidifier Water Suppl...
Page 21 - Figure 9
Installation (Applicable to all Models) 15 Figure 9 Piping connections for water/glycol and GLYCOOL units - Upflow models PIPING OUTLET LOCATIONS(See Cabinet and Floor PlanningDimensional Data for PipingOpening Sizes.) Piping outlet locations through the plenumthe same as the unit. See below fordesc...
Page 24 - Humidifier Supply Water—Optional Infrared; Facility Fluid and Piping Maintenance; ing; Electrical Connections; accessible from the exterior.; compressor is rotating properly.; remote disconnect switch. Refer to unit electrical schematic.
Installation (Applicable to all Models) 18 2.5.2 Humidifier Supply Water—Optional Infrared • 1/4" supply line; maximum water pressure is 150 psi (1034kPa) • Size humidifier supply line for 1 gpm (3.8 l/m), with a minimum water pressure of 20 psi (138kPa)• Do not supply de-ionized water to the hu...
Page 25 - Figure 12 Electrical connections; Terminal Block - for customer connections
Installation (Applicable to all Models) 19 Figure 12 Electrical connections 1. Electric conduit knockouts on top and bottom of electric box. Knockout size 1-3/4" (44.5mm). 2. Three-phase connection . Electric service connection terminals when factory disconnect is NOT supplied. 3. Three-phase co...
Page 26 - Figure 13 Electrical field connections for Liebert iCOM; Upflow Models with Liebert iCOM
Installation (Applicable to all Models) 20 15. Heat rejection connection . Field-supplied 24V Class 1 wiring to interlock heat rejection from pigtails 70 + 71 which are factory-connected to compressor side switch (self-contained units only) or to GLYCOOL relay (K11, GLYCOOL units only). On Dual Cool...
Page 27 - Balancing the Air Distribution; Table 3
Installation (Applicable to all Models) 21 2.8 Balancing the Air Distribution 2.8.1 Under-Floor Discharge Systems The systems are designed for constant air delivery, therefore any unusual restrictions within the air circuit must be avoided. For under-floor air distribution, observe the following gui...
Page 28 - Checklist for Completed Installation
Installation (Applicable to all Models) 22 2.9 Checklist for Completed Installation ___ 1. Unpack and check received material.___ 2. Proper clearance for service access has been maintained around the equipment.___ 3. Equipment is level and mounting fasteners are tight.___ 4. Piping completed to refr...
Page 29 - Air-Cooled Models—Self-Contained Compressor; Condenser Location; denser to the steel supports or concrete pad.; with local and national codes.
Air-Cooled Models—Self-Contained Compressor 23 3.0 A IR -C OOLED M ODELS —S ELF -C ONTAINED C OMPRESSOR 3.1 Condenser Location The air-cooled condenser should be located for maximum security and maintenance accessibility. Avoid ground level sites with public access or areas that contribute to heavy ...
Page 30 - Figure 14 Air-cooled condensers
Air-Cooled Models—Self-Contained Compressor 24 Figure 14 Air-cooled condensers Table 4 Air-cooled condenser statistics Model Number of Fans Connection Sizes (OD Copper) Net Weight lb (kg) “A” Dimension in (mm) Hot Gas (in.) Liquid (in.) 083 1 7/8 5/8 295 (133.8) 42 (1067) 104 1 1-1/8 5/8 315 (142.8)...
Page 31 - Refrigerant Piping; Equivalent Length
Air-Cooled Models—Self-Contained Compressor 25 3.3 Refrigerant Piping All refrigeration piping should be installed with high temperature brazed joints. Prevailing good refrigeration practices should be employed for piping supports, leak testing, dehydration and charg- ing of the refrigeration circui...
Page 32 - Fan Speed Control Systems; Variable Fan Speed Control Piping; and; Table 6; Table 7
Air-Cooled Models—Self-Contained Compressor 26 3.4 Fan Speed Control Systems The Variable Fan Speed Control systems (FSC & VFD) uses pressure-activated electronic fan speed control systems and remotely located thermostat(s) to ensure operation at ambient temperatures as low as 0°F (-18°C). For t...
Page 33 - Variable Fan Speed Control Materials Supplied; Note; downstream Schrader valve. See piping schematic (
Air-Cooled Models—Self-Contained Compressor 27 Variable Fan Speed Control Materials Supplied • Built-in, pre-wired condenser control box• Air-Cooled condenser• Piping access cover to be reinstalled when piping is complete• Bolts—four per leg (3/8" x 5/8")• Terminal block for two-wire, 24V in...
Page 34 - Variable Fan Speed Charging; Refrigerant charging requires unit operation. Refer to; Installation; charge data in; Tables 6; CAUTION; Fan speed suction pressure transducer settings; Function
Air-Cooled Models—Self-Contained Compressor 28 Variable Fan Speed Charging 1. Check unit nameplate for refrigerant type to be used. Unit control configurations differ depending on refrigerant type. 2. Refrigerant charging requires unit operation. Refer to 2.9 - Checklist for Completed Installation ....
Page 35 - Liquid Return
Air-Cooled Models—Self-Contained Compressor 29 Figure 15 General arrangement—Air-cooled models with fan speed control DPN000349Rev. 3 CondenserCoil SchraderValve FusiblePlug EvaporatorCoil Hot GasBypassValve Traps* every25 ft. (7.6m)of rise SolenoidValves SightGlass FilterDryer Liquid Return Shutoff...
Page 37 - Liebert Lee-Temp Piping
Air-Cooled Models—Self-Contained Compressor 31 3.5 Air-Cooled Condenser with Liebert Lee-Temp “Flooded Condenser” Head Pressure Control System The Liebert Lee-Temp system consists of a modulating type head pressure control valve and insulated receivers with heater pads to ensure operation at ambient...
Page 38 - condenser. After completing this step, proceed to; Lee-Temp Receiver Refrigerant Level; Sight Glass Levels; Lee-Temp suction pressure transducer settings
Air-Cooled Models—Self-Contained Compressor 32 6. After four hours, check the pressure readings and, if they have not changed, break vacuum with dry nitrogen. Pull a second and third vacuum to 250 microns or less. Recheck the pressure after two hours. 7. Remove the jumper hose installed previously f...
Page 41 - Water-Cooled Models—Self-Contained Compressor; sensor; Condenser; is available as an option.
Water-Cooled Models—Self-Contained Compressor 35 4.0 W ATER -C OOLED M ODELS —S ELF -C ONTAINED C OMPRESSOR 4.1 Piping Considerations Manual shutoff valves should be installed at the supply and return lines of each unit. This will pro- vide for routine maintenance or emergency isolation of the unit....
Page 44 - Water Regulating Valve; Figure 21 Johnson Controls valve adjustment; Adjustment; top of valve spring housing.
Water-Cooled Models—Self-Contained Compressor 38 4.3 Water Regulating Valve The water regulating valve automatically regulates the amount of fluid necessary to remove the heat from the refrigeration system, permitting more fluid to flow when load conditions are high and less fluid to flow when load ...
Page 45 - Figure 22 Metrex Valve adjustment; Manual Flushing; Motorized Ball Valve—Digital Scroll Compressors; assembly consists of the brass valve, linkage and actuator.; Control Method; discharge pressure back into control range.
Water-Cooled Models—Self-Contained Compressor 39 Figure 22 Metrex Valve adjustment Manual Flushing The valve may be flushed by rotating the socket head screw clockwise. This screw must be in the OUT position (counterclockwise) for normal valve operation. 4.4 Motorized Ball Valve—Digital Scroll Compr...
Page 46 - mixing arrangement with the common port at the valve outlet.
Water-Cooled Models—Self-Contained Compressor 40 4.4.2 Adjustment Both pressure thresholds can be shifted simultaneously over a 50psi (345kPa) range (the 35psi [241kPa] differential remains constant). The ball valve setpoint offset parameter in the Liebert iCOM Service menu can be adjusted from 0 to...
Page 47 - the drycooler to steel supports or concrete pad.
Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor 41 5.0 G LYCOL /GLYCOOL-C OOLED M ODELS —S ELF -C ONTAINED C OMPRESSOR 5.1 Drycooler Location The drycooler should be located for maximum security and maintenance accessibility. Avoid ground- level sites with public access or areas which contrib...
Page 48 - Glycol Piping; General Guidelines; ing, fluid chemistry and fluid maintenance.
Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor 42 5.4 Glycol Piping These guidelines apply to the field leak checking and fluid requirements for field piping systems. General Guidelines • Equipment damage and personal injury can result from improper piping installation, leak check- ing, flui...
Page 49 - Room dew point temperatures; Dry Bulb
Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor 43 NOTICE Risk of debris or precipitate clogging pipes. Can cause equipment damage.Galvanized pipe must not be used in or with systems or units that contain glycol. The phosphates in the inhibitor can react with the zinc in the galvanized pipe, ...
Page 50 - Filling Instructions; GLYCOOL; Volume in standard Type “L” copper piping; Volume
Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor 44 5.4.1 Expansion Tanks, Fluid Relief Valves and Other Devices An expansion tank must be provided for expansion and contraction of the fluid due to temperature change in this closed system. Vents are required at system high points to vent trapp...
Page 51 - information and take necessary steps to ensure safety of use.; drycooler and related equipment.; in which the system is operating.; occur from either freezing or corrosion from water.
Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor 45 5.5.2 Glycol Solutions When considering the use of any glycol products in a particular application, you should review the lat- est Material Safety Data Sheets and ensure that the use you intend can be accomplished safely. For Material Safety ...
Page 52 - Ethylene glycol concentrations; Apparent Specific Gravity; Do not mix products of different manufacturers.
Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor 46 NOTICE Risk of corrosion from water impurities. Can cause equipment damage.The quality of water used for dilution must be considered because water may contain corrosive elements which reduce the effectiveness of the inhibited formulation. Wat...
Page 53 - Figure 23 Drycoolers and pump packages; apart on single pump packages and 30-; Angles located
Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor 47 Figure 23 Drycoolers and pump packages Notes 1. Single pump packages are 17-1/4" (438 mm) wide. Dual pump packages ar 32-1/4" (819 mm) wide. 2. Mounting holes are 15-1/4" (387 mm) apart on single pump packages and 30- 1/4" (76...
Page 54 - Fitting
Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor 48 Figure 24 Pump packages—expansion tank Table 17 Mounting hole dimensional data PUMP PACKAGE A in (mm) B in (mm) C in (mm) SINGLE (0.75 - 7.5 Hp) 15-1/4 (387.4) 2-1/2 (63.5) 22-1/2 (571.5) DUAL (0.75 - 5 Hp) 30-1/4 (768.4) 2-1/2 (63.5) 22-1/2 ...
Page 57 - FACTORY PIPING
Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor 51 Figure 27 General arrangement—GLYCOOL models with scroll compressor Field-SuppliedReducersRequired on 3-Ton Units PumpHousing Pump Unions* Unions* IsolationValves* ExpansionValve EvaporatorCoil DrycoolerCoil DrycoolerElectric Box PressurePort...
Page 59 - Motor Ball Valve—Digital Scroll Compressors; Refer to; - Motorized Ball Valve—Digital Scroll Compressors; for details on the motorized ball; For details, refer to
Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor 53 5.5.4 Motor Ball Valve—Digital Scroll Compressors Refer to 4.4 - Motorized Ball Valve—Digital Scroll Compressors for details on the motorized ball valve. 5.6 Condenser The condenser is designed to operate in conjunction with a drycooler. The ...
Page 60 - Chilled Water Models; HILLED; installed near the base of the unit or below the elevated floor.
Chilled Water Models 54 6.0 C HILLED W ATER M ODELS 6.1 Piping Considerations Manual shut-off valves should be installed at the supply and return lines to each unit. This will pro- vide for routine service and emergency isolation of the unit.Consideration of the minimum water temperature to be suppl...
Page 61 - Figure 30 Chilled water general arrangement - Downflow (BF) models
Chilled Water Models 55 Figure 30 Chilled water general arrangement - Downflow (BF) models SL-11899Pg. 6 A B FlowSwitch(optional) ChilledWaterReturn ChilledWaterSupply ChilledWaterReturn ChilledWaterCoil ChilledWaterCoil 2-Way ChilledWater Valve ChilledWaterSupply ShutoffValves * HoseBibs * 3-WAY VA...
Page 62 - Split System Models; PLIT; Location Considerations; ing guidelines and to; Figure 35 - Detail of ceiling hanging bracket; for dimensional data.
Split System Models 56 7.0 S PLIT S YSTEM M ODELS Three condensing unit styles are available: two air-cooled and one water/glycol-cooled condensing unit. 7.1 Location Considerations 7.1.1 Air-Cooled Condensing Units To assure an adequate air supply, it is recommended that all condensing units be loc...
Page 64 - Check system for leaks with a suitable leak detector.; evaporator units include a nitrogen holding charge only. See; Unit refrigerant charge
Split System Models 58 Refrigerant charge requirements: Total refrigerant charge will be required only if units are evacuated during installation or maintenance. Total refrigerant charge = evaporator + lines + condensing unit. Once all piping is complete, check for leaks and dehydrate the field pipi...
Page 65 - Figure 31 Refrigerant piping diagram; bodies “bottom out” or until a definite resistance is felt.; Line coupling sizes; connecting quick connects.
Split System Models 59 Figure 31 Refrigerant piping diagram 7.3.2 Quick Connect Fittings Be especially careful when connecting the quick connect fittings. Read through the following steps before making the connections.1. Remove protector caps and plugs.2. Carefully wipe coupling seats and threaded s...
Page 66 - Outdoor Air-Cooled Condensing Units; UNIT DIMENSIONS
Split System Models 60 7.4 Outdoor Air-Cooled Condensing Units Figure 32 Outdoor air-cooled condensing unit—horizontal air discharge models A B C Shaded area indicates a minimum clearance of 18" (457mm) for proper air flow Shaded area indicates a minimum clearance of 18" (457mm) for proper a...
Page 67 - Horizontal air discharge piping and electrical connection data; Model Numbers
Split System Models 61 Table 26 Horizontal air discharge cabinet and floor planning dimensional data Model Numbers Dimensional Data in. (mm) Module Weight lb (kg) net 60 Hz 50 Hz A B C PFC042A-_L PFC041A-_L 48 (1219) 31 (787) 18 (457) 241 (109) PFH042A-_L — PFC042A-_H PFC041A-_H 53 (1343) 36-1/4 (91...
Page 69 - Piping and electrical connections - top air discharge
Split System Models 63 Table 28 Cabinet and floor planning dimensional data - prop fan condensing modules, top air discharge Model Numbers Dimensional Data in. (mm) Module Weight lb (kg) net 60 Hz 50 Hz A B C D PFC067A-_H PFC066A-_H 53 (1343) 36-1/4 (918) 38-1/2 (978) 5-1/2 (140) 488 (222) PFH067A-_...
Page 71 - Centrifugal Air-Cooled Condensing Units; Installing the Indoor Condensing Unit; Refer to drawings for unit dimensions and component locations.; Detail of ceiling hanging bracket; Use the Nylock nuts to “jam” the plain nuts.; the accessories during installation and service. (See; Table 30 - Indoor centrifugal; The units must be level in order to operate properly.; Indoor centrifugal condensing unit
Split System Models 65 7.5 Centrifugal Air-Cooled Condensing Units 7.5.1 Installing the Indoor Condensing Unit Refer to drawings for unit dimensions and component locations. The indoor condensing unit is usually mounted above the ceiling and must be securely mounted to the roof structure. The ceilin...
Page 72 - Figure 35 Detail of ceiling hanging bracket; directed toward the air inlet of an adjacent unit.
Split System Models 66 Figure 35 Detail of ceiling hanging bracket 7.5.2 Ducting The total external static pressure for the inlet and outlet ducts, including grille, must not exceed 0.5 inches of H 2 O. Hood intake dimensions should be the same as the condensing unit duct dimen- sions.If the condens...
Page 73 - PIPING CONNECTIONS
Split System Models 67 Figure 36 3-ton centrifugal air-cooled condensing unit dimensional data & piping connections C D B A Customer-suppliedthreaded rods for module supportfrom ceiling (typ. 4) SL-11085 Pg. 4 Air Outlet Duct Connection Air Outlet Duct Dimension Note:Unit is evenly spaced inrefe...
Page 74 - or not to exceed 1 volt drop in control line.
Split System Models 68 Figure 37 3-ton centrifugal air-cooled condensing unit (con't.) DPN000207Rev0 Single- or three-phaseelectric servicenot by Liebert Optional factory-installeddisconnect switch Factory-wiredto componentson electric panel Line voltage electric powersupply conduit entrance Field-s...
Page 76 - AIR COOLED
Split System Models 70 Figure 39 5-ton centrifugal air-cooled condensing unit dimensional data (con't.) DPN000226_Rev0 Field-Supplied Unit DisconnectSwitch when Factory UnitDisconnect Switch is not Supplied Electric servicenot by Liebert OptionalFactory-InstalledDisconnect Switch AIR COOLED Line Vol...
Page 77 - Figure 40 Split systems general arrangement
Split System Models 71 Figure 40 Split systems general arrangement CondenserCoil 1/2" (12.7mm) NPTPressure Relief Valve PressureBalancingValve SightGlass CheckValve Lee-TempReceiver High-PressureSwitch ScrollCompressor ScrollCompressor Head-PressureControl withIntegral CheckValve Liquid LineSole...
Page 78 - Water and Glycol-Cooled Condensing Units; For installation guidelines, refer to; Installing the Indoor Condensing Unit on page 65.; For details, refer to sections; Water and glycol-cooled condensing unit data
Split System Models 72 7.6 Water and Glycol-Cooled Condensing Units For installation guidelines, refer to Installing the Indoor Condensing Unit on page 65. 7.6.1 Piping Considerations It is recommended that manual service shut-off valves be installed at the supply and return line to each unit. This ...
Page 79 - Cooled Models—Self-Contained Compressor
Split System Models 73 7.6.4 Glycol Systems For split system glycol systems, use drycooler and pump data found in 5.0 - Glycol/GLYCOOL- Cooled Models—Self-Contained Compressor . See Table 18 - Drycooler data . Electrical control interconnect to drycooler is wired from water/glycol condensing unit. F...
Page 83 - EFRIGERANT
R407C Refrigerant 77 8.0 R407C R EFRIGERANT Table 33 R407C pressure/temperature chart for operation and superheat (discharge/hot gas and suction gas) Temperature Gauge Pressure Temperature Gauge Pressure Temperature Gauge Pressure °F °C Psig kPa °F °C Psig kPa °F °C Psig kPa 0.0 -17.8 18.9 130 35.0 ...
Page 84 - Calculating Subcooling; Example; on; Why There Are Two R407C Temperature and Pressure Tables; heat or operating controls.; Use this table for subcooling calculation ONLY. See
R407C Refrigerant 78 8.1 Calculating Subcooling Example Measure the liquid pressure (e.g., 200 psig). Find the liquid saturation temperature at that pressure on Table 34 (e.g., 93°F). Measure the temperature of the liquid line (e.g., 90°F). Subtract the actual temperature from the liquid saturation ...
Page 85 - NOTES
Page 88 - Via Leonardo Da Vinci 8; Precision Cooling
Ensuring The High AvailabilityOf Mission-Critical Data And Applications. Emerson Network Power, the global leader in enabling business-criticalcontinuity, ensures network resiliency and adaptability througha family of technologies—including Liebert power and coolingtechnologies—that protect and supp...