Carbon Dioxide Sensor

Product Information Sheet

210-2000

Overview

CPC’s CO

2

sensor (P/N 210-2000) is a non-dispersive

infrared analyzer designed for measuring

environmental CO

2

concentration in ventilation

systems and indoor spaces. Its measurement range of

0-2000 or 0-5000 ppm covers the range required to

monitor compliance with ASHRAE and other
ventilation efficiency standards.

An LCD display is available to provide local indication

of CO

2

concentration and facilitate the setup and

calibration process. An adjustable setpoint relay is

available for direct control and alarm applications.

Microprocessor-based digital electronics and a

unique self-calibration algorithm improves long-term

stability and accuracy

Mounting

Before mounting, remove the door from the circuit

board by pressing a screwdriver against the locking
tab on the top of the enclosure. Pry the circuit board





away from the mounting plate using a screwdriver
inserted into the two tab slots on the top of the

enclosure.

Choose a location for the sensor with good air

circulation, away from ventilation inlets, doors,
windows, or other points where fresh air enters the

room. The sensor should be mounted at least 4-1/2

feet above the floor. The environment temperature

must be within 32°–112°F (0°–50°C).


If wiring will be coming in through the mounting

plate from the back, punch out openings in the

mounting plate and use the plate as a template for

locating holes. Mount the mounting plate against a
wall or other flat surface by using the two mounting

holes and the screws provided (use wall anchors for

drywall installations).

NOTE: Sensors must be mounted vertically (straight

up and down) to ensure proper readings.







Figure 1 - CO

2

Sensor (exploded view)

Carbon Dioxide Sensor

Product Information Sheet

40

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Other Manuals for Emerson 210-2000

Summary

Page 2 - Carbon Dioxide Sensor; Product Information Sheet; Wiring; Power Wiring; Sensor Wiring

Carbon Dioxide Sensor Product Information Sheet 210-2000 Wiring The mounting plate has two sets of three-terminal connectors. The connector on the left side of the mounting plate is where sensor power and the signal- to-I/O-board connection is made. The connector on the right side is where connectio...

Page 3 - Setting Up the CO; Setpoint; Sensor Reassembly

Carbon Dioxide Sensor Product Information Sheet 210-2000 Setting the Volts/Amps Switch The front of the circuit board has a switch that controls whether the analog output sends a signal as voltage (V) or milliamps (mA). To work with CPC I/ O boards, this switch should be set to voltage (the DOWN pos...

Page 4 - Span; Replacing the Door

Carbon Dioxide Sensor Product Information Sheet 210-2000 Span The Span parameter determines whether you want to measure concentrations between 0-2000 ppm or 0- 5000 ppm. If set to 2000 ppm, the sensor’s analog output signal will be scaled properly so that the highest output voltage corresponds to 20...