Emerson 210-2000- Manual
Emerson 210-2000– Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – Carbon Dioxide Sensor; Product Information Sheet; Wiring; Power Wiring; Sensor Wiring
- Page 3 – Setting Up the CO; Setpoint; Sensor Reassembly
- Page 4 – Span; Replacing the Door
Carbon Dioxide Sensor
Product Information Sheet
210-2000
Overview
CPC’s CO
2
sensor (P/N 210-2000) is a non-dispersive
infrared analyzer designed for measuring
environmental CO
2
concentration in ventilation
systems and indoor spaces. Its measurement range of
0-2000 or 0-5000 ppm covers the range required to
monitor compliance with ASHRAE and other
ventilation efficiency standards.
An LCD display is available to provide local indication
of CO
2
concentration and facilitate the setup and
calibration process. An adjustable setpoint relay is
available for direct control and alarm applications.
Microprocessor-based digital electronics and a
unique self-calibration algorithm improves long-term
stability and accuracy
Mounting
Before mounting, remove the door from the circuit
board by pressing a screwdriver against the locking
tab on the top of the enclosure. Pry the circuit board
away from the mounting plate using a screwdriver
inserted into the two tab slots on the top of the
enclosure.
Choose a location for the sensor with good air
circulation, away from ventilation inlets, doors,
windows, or other points where fresh air enters the
room. The sensor should be mounted at least 4-1/2
feet above the floor. The environment temperature
must be within 32°–112°F (0°–50°C).
If wiring will be coming in through the mounting
plate from the back, punch out openings in the
mounting plate and use the plate as a template for
locating holes. Mount the mounting plate against a
wall or other flat surface by using the two mounting
holes and the screws provided (use wall anchors for
drywall installations).
NOTE: Sensors must be mounted vertically (straight
up and down) to ensure proper readings.
Figure 1 - CO
2
Sensor (exploded view)
Carbon Dioxide Sensor
Product Information Sheet
40
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Other Manuals for Emerson 210-2000
Summary
Carbon Dioxide Sensor Product Information Sheet 210-2000 Wiring The mounting plate has two sets of three-terminal connectors. The connector on the left side of the mounting plate is where sensor power and the signal- to-I/O-board connection is made. The connector on the right side is where connectio...
Carbon Dioxide Sensor Product Information Sheet 210-2000 Setting the Volts/Amps Switch The front of the circuit board has a switch that controls whether the analog output sends a signal as voltage (V) or milliamps (mA). To work with CPC I/ O boards, this switch should be set to voltage (the DOWN pos...
Carbon Dioxide Sensor Product Information Sheet 210-2000 Span The Span parameter determines whether you want to measure concentrations between 0-2000 ppm or 0- 5000 ppm. If set to 2000 ppm, the sensor’s analog output signal will be scaled properly so that the highest output voltage corresponds to 20...