Table of Contents:
- Page 2 – Electrical Preparation:; Electrical Requirements for the Dell UPS; have an input cord option
- Page 3 – Electrical Wiring, Basic Installation Schematics; Suitable for all models except 5600W Online and 10kW
- Page 4 – Suitable for all models (including 5600W Online and 10kW); Electrical input location of Dell UPS
- Page 5 – Overcurrent Protection Devices:; All Dell UPS Rack Mount Models; 0kW WW Blades; Electrical input top entry
- Page 6 – Remove the cover-plate from the rear of the UPS
- Page 7 – Wire Colour; Receiving the Dell UPS; Inspecting the Equipment; Your model
- Page 8 – Installing the Dell UPS into the rack:; Amp PDU types for fit.; Actual carton may vary by model
Dell UPS Site Preparation Guide, EMEA (230V)
Revision 2, December 2012
Dell UPS Site Preparation Guide, EMEA.
Applies Dell Rackmount UPS Models, 3750W, 4200W, 5600W & 10kW
Note: This document is for guidance only. Actual installation instructions and safety cautions are included within the UPS User’s
Guide. Quick link to User’s Guides:
http://dellups.com/support_download.asp
> User Manuals and Publications.
Site Preparation Checklist
Installation site meets minimum environmental requirements.
Ensured all required accessories have been ordered with the UPS.
Electrical Preparation
Required electrical supply is available.
Scheduled an electrician to install the Dell UPS.
Provided a copy of this preparation guide to the electrician.
Made electrician aware of
Hardwiring the UPS
electrician’s checklist in the User’s Guide.
Site Preparation:
Physical Requirements for the Dell UPS
UPS Model
UPS Technology
Dimensions (mm, W x D x H)
Weight (installed, no battery)
3750W Rack
Online
4U, 438 x 790 x 171.5
65kg, 23kg
4200W Rack
Online
4U, 438 x 790 x 171.5
65kg, 23kg
5600W Rack
Line Interactive
4U, 438 x 790 x 171.5
72kg, 24kg
5600W Rack
Online
4U, 438 x 790 x 171.5
64kg, 24kg
10kW Rack
Online
5U, 438 x 823 x 214
110kg, 46kg
EBM* for 3750W/4200W
UPS
n/a
3U, 438 x 735 x 127
61kg, n/a
EBM* for all 5600W UPS
n/a
4U, 438 x 735 x 171.5
66kg, n/a
EBM* for 10kW
n/a
3U, 438 x 737 x 127
80kg, n/a
* EBM is an optional ‘external battery module’.
Environmental Requirements for the Dell UPS
Environmental Condition
Suitable Range
Temperature (Operation)
0 - 40C (32 - 104F)
Temperature (Storage, 24hr)
-15 - 60C (5 - 140F)
Temperature (Long-term Storage)
- 15 - 45C (5 - 113F)
Relative Humidity
0 - 95% (non-condensing)
Elevation (Operation)
0 - 3048m (0 - 10,000ft)
Elevation (Storage)
0 - 15,340m (0 - 50,000ft)
Heat Output for the Dell UPS
UPS Model
UPS Technology
Heat Loss, Watts / BTU (normal mode)
Heat Loss, Watts / BTU (battery mode)
3750W Rack
Online
188 / 640
375 / 1281
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
Dell UPS Site Preparation Guide, EMEA (230V) Revision 2, December 2012 4200W Rack Online 210 / 717 420 / 1434 5600W Rack Line Interactive 280 / 956 560 / 1921 5600W Rack Online 390 / 989 420 / 1433 10kW Rack Online 412 / 1420 754 / 2600 Optional accessories for Dell UPS Optional Accessory Importance...
Dell UPS Site Preparation Guide, EMEA (230V) Revision 2, December 2012 The REPO feature shuts down the protected equipment immediately and does not follow the orderly shutdown procedure initiated by any power management software. Any devices that are operating on battery power are also shut down imm...
Dell UPS Site Preparation Guide, EMEA (230V) Revision 2, December 2012 Basic Installation Schematic of Dell UPS, hardwired to overcurrent protection device Suitable for all models (including 5600W Online and 10kW) Electrical input location of Dell UPS If hardwiring input to UPS, input terminal block...