Page 2 - TABLE OF CONTENTS
• VRV ® Systems • Outdoor Units 1 • Outdoor Units • VRV ® COOLING ONLY • RXQ5-18P7W1B(A) TABLE OF CONTENTS RXQ5-18P7W1B(A) 1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Technical Specifications . . . . . . . . . . . ....
Page 3 - Specifications; -1 TECHNICAL SPECIFICATIONS
• Outdoor Units • VRV ® COOLING ONLY • RXQ5-18P7W1B(A) • VRV ® Systems • Outdoor Units 2 1 Specifications 3 Ou td oo r Un i VR V S ys te ms RX Q5 -1 8P 7W 1B ( V R V C o o l in g O n 1-1 TECHNICAL SPECIFICATIONS RXQ5P7W1B RXQ8P7W1B RXQ10P7W1B RXQ12P7W1B Capacity Cooling kW 14.0 22.4 28.0 33.5 COP Co...
Page 5 - -2 TECHNICAL SPECIFICATIONS
• Outdoor Units • VRV ® COOLING ONLY • RXQ5-18P7W1B(A) • VRV ® Systems • Outdoor Units 4 1 Specifications 3 1-2 TECHNICAL SPECIFICATIONS RXQ14P7W1BA RXQ16P7W1BA RXQ18P7W1BA Capacity Cooling kW 40.0 45.0 49.0 COP Cooling 3.23 3.17 3.02 Capacity range HP 14 16 18 Power input (nominal) Cooling kW 12.4 ...
Page 7 - -3 ELECTRICAL SPECIFICATIONS
• Outdoor Units • VRV ® COOLING ONLY • RXQ5-18P7W1B(A) • VRV ® Systems • Outdoor Units 6 1 Specifications 3 1-3 ELECTRICAL SPECIFICATIONS RXQ5P7W1B RXQ8P7W1B RXQ10P7W1B RXQ12P7W1B Power Supply Name W1 Phase 3N~ Frequency Hz 50 50 50 50 Voltage V 400 400 400 400 Current Nominal running current (RLA) ...
Page 9 - Options
• Outdoor Units • VRV ® COOLING ONLY • RXQ5-18P7W1B(A) • VRV ® Systems • Outdoor Units 8 2 Options 3 RXQ-P NOTES 1 All options are kits. 2 The option should be installed inside the outdoor unit. No. Item RXQ5P RXQ8P RXQ10P RXQ12P RXQ14P RXQ16P RXQ18P 1 COOL/HEAT SELECTOR KRC19-26A6 2 FIXING BOX KJB1...
Page 10 - Capacity tables; - 1 Cooling capacity tables
• VRV ® Systems • Outdoor Units 9 • Outdoor Units • VRV ® COOLING ONLY • RXQ5-18P7W1B(A) 3 Capacity tables 3 - 1 Cooling capacity tables 3 RXQ5P 3TW27302-1C NOTES 1 The above table shows the average value of conditions which may occur. 2 When indoor models FXFQ20M, FXFQ25M and VKM-models are connect...
Page 24 - Dimensional drawing & centre of gravity; - 1 Dimensional drawing
• VRV ® Systems • Outdoor Units 23 • Outdoor Units • VRV ® COOLING ONLY • RXQ5-18P7W1B(A) 4 Dimensional drawing & centre of gravity 4 - 1 Dimensional drawing 3 RXQ5P 3D051448 4-15x22.5-mm-Oblong holes (Foundation bolt hole) 722~737 (Pitch of foundation bolt holes) 497 (Pitch of foundation bolt h...
Page 28 - - 2 Centre of gravity
• VRV ® Systems • Outdoor Units 27 • Outdoor Units • VRV ® COOLING ONLY • RXQ5-18P7W1B(A) 4 Dimensional drawing & centre of gravity 4 - 2 Centre of gravity 3 RXQ5P 4D052145 Center of foundation bolt hole Center of foundation bolt hole Center of foundation bolt hole Center of foundation bolt hole...
Page 30 - Piping diagram
• VRV ® Systems • Outdoor Units 29 • Outdoor Units • VRV ® COOLING ONLY • RXQ5-18P7W1B(A) 5 Piping diagram 3 RXQ5P 4TW27305-1 Solenoid valve Solenoid valve Fan M Heat exchanger High pressure sensor High pressure switch INV Compressor Cappillary tube Cappillary tube Solenoid valve SV Cappillary tube ...
Page 34 - Wiring diagram
• VRV ® Systems • Outdoor Units 33 • Outdoor Units • VRV ® COOLING ONLY • RXQ5-18P7W1B(A) 6 Wiring diagram 6 - 1 Wiring diagram 3 RXQ5P 2TW27306-1 Power supply 3/N ~ 400/230V 50Hz 5 HP In-Out Out-Out (Note 2) ON OFF ON OFF F1 F2 F1 F2 Out-Multi Q1 Q2 Indoor (F1)(F2) Outdoor (F1)(F2) Front layer Rear...
Page 38 - - 2 External connection diagram
• VRV ® Systems • Outdoor Units 37 • Outdoor Units • VRV ® COOLING ONLY • RXQ5-18P7W1B(A) 6 Wiring diagram 6 - 2 External connection diagram 3 RXQ5-18P 3D051452B Power supply L1 L2 L3 N L1 L2 L3 N Main switch Power supply L N Main switch Switch Fuse L N Switch Fuse L N Switch Fuse OUTDOOR UNITS INDO...
Page 39 - Sound data; - 1 Sound pressure spectrum
• Outdoor Units • VRV ® COOLING ONLY • RXQ5-18P7W1B(A) • VRV ® Systems • Outdoor Units 38 7 Sound data 7 - 1 Sound pressure spectrum 3 NOTES 1 Over all (dB):(B, G, N is already rectified) 2 Operating conditons:• Power source: Y1: 380-415V 50Hz • JIS Standard 3 Measuring place: Anechoic chamber (Conv...
Page 41 - - 2 Sound power spectrum
• Outdoor Units • VRV ® COOLING ONLY • RXQ5-18P7W1B(A) • VRV ® Systems • Outdoor Units 40 7 Sound data 7 - 2 Sound power spectrum 3 NOTES 1 dBA = A-weighted sound power level. (A-scale according to IEC) 2 Reference acoustic pressure 0dB = 10E-6 μ W/m 2 . 3 Measured according to ISO 3744. RXQ5P 3TW27...
Page 43 - Installation
• Outdoor Units • VRV ® COOLING ONLY • RXQ5-18P7W1B(A) • VRV ® Systems • Outdoor Units 42 8 Installation 8 - 1 Service space 3 RXQ-P 3D051451B For single unit installation 300 or more 10 or more 10 or more 500 or more <Pattern 1> <Front> 100 or more 50 or more 50 or more 500 or more <...
Page 44 - - 2 Fixation and foundation of units
• VRV ® Systems • Outdoor Units 43 • Outdoor Units • VRV ® COOLING ONLY • RXQ5-18P7W1B(A) 8 Installation 8 - 2 Fixation and foundation of units 3 RXQ-P 3TW27239-6 NOTES 1 The proportions of cement:sand:gravel for the contrete shale be 1:2:4, and the reinforcement bars that their dirameter are 10mm, ...
Page 45 - Operation range; operation range
• Outdoor Units • VRV ® COOLING ONLY • RXQ5-18P7W1B(A) • VRV ® Systems • Outdoor Units 44 9 Operation range 3 RXQ-P 4TW27307-3 NOTES 1 These figures assume the following operation conditions: • indoor and outdoor units: • equivalent pipe length: 7.5m • level difference: 0m 2 Depending on operation a...