PR2000LCD / PR2200LCD / PR3000LCD

User’s Manual

K01-0000252-00

(SAVE THESE INSTRUCTIONS)

This manual contains important safety instructions. Please read and follow all instructions carefully during installation and operation of the unit.

Read this manual thoroughly before attempting to unpack, install, or operate your UPS.

CAUTION!

To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area free of conductive

contaminants. (Please see specifications for acceptable temperature and humidity range).

CAUTION!

To reduce the risk of electric shock, do not remove the cover except to service the battery. Turn off and unplug the unit before

servicing the batteries. There are no user serviceable parts inside except for the battery.

CAUTION!

Hazardous live parts inside can be energized by the battery even when the AC input power is disconnected.

CAUTION!

The

UPS must be connected to an AC power outlet with fuse or circuit breaker protection. Do not plug into an outlet that is not

grounded. If you need to de-energize this equipment, turn off and unplug the unit.

CAUTION!

To avoid electric shock, turn off the unit and unplug it from the AC power source before servicing the battery or installing a computer

component.

CAUTION!

To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch circuit over current protection in

accordance with the National Electric Code, ANSI/NFPA 70.

DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT!

CyberPower Systems does not sell products for life support or medical

applications.

DO NOT

use in any circumstance that would affect the operation and safety of life support equipment, medical applications, or

patient care.

DO NOT USE WITH OR NEAR AQUARIUMS!

To reduce the risk of fire or electric shock, do not use with or near an aquarium.

Condensation

from the aquarium can cause the unit to short out.

DO NOT LIFT USING FACEPLATE.

Two people are required to lift this unit. Lift this unit from sides only.

INTRODUCTION

Thank you for selecting a CyberPower Systems UPS product. This UPS is designed to provide unsurpassed power protection, operation and

performance during the lifetime of the product.

UNPACKING

Inspect the UPS upon receipt. The box should contain the following:

(a) UPS unit (b) User’s manual (c) Emergency Power Off cable (gray) (d) PowerPanel

®

Business Edition software CD (e) Serial cable (f) USB

A+B type cable (g) Warranty registration card (h) Function Setup Guide

OVERVIEW

The PR2000LCD/PR2200LCD/PR3000LCD UPS provides complete power protection from utility power that isn't always consistent. The

PR2000LCD/PR2200LCD/PR3000LCD features surge protection against power surges and maintenance free batteries for long lasting battery

backup during power outages. In addition to ensuring consistent power to your computer system and the

PR2000LCD/PR2200LCD/PR3000LCD also includes software that will automatically save your open files

and shutdown your computer system during a utility power loss.

AUTOMATIC VOLTAGE REGULATOR

The

PR2000LCD/PR2200LCD/PR3000LCD

stabilizes inconsistent utility power voltage to nominal levels that

are safe for equipment. Inconsistent utility power may be damaging to important data files and hardware,

but with Automatic Voltage Regulation (AVR),

damaging voltage levels are corrected to safe levels. AVR

automatically increases low utility power and decreases high utility power to a consistent and safe

110/120 volts.

HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT

1.

Ensure that the equipment plugged into the outlets does not exceed the UPS unit’s rated capacity (1920VA/1920W for PR2000LCD,

2200VA/1980W for PR2200LCD, 3000VA/2700W for PR3000LCD). If the rated capacities of the unit are exceeded, an overload condition

may occur and cause the UPS unit to shut down or the circuit breaker to trip.

HARDWARE INSTALLATION GUIDE

1. Your new UPS may be used immediately upon receipt. However, to ensure the battery’s maximum

charge capacity, it is recommended that you charge the battery for at least 8 hours. Your UPS is equipped

with an auto-charge feature. When the UPS is plugged into an AC outlet, the battery will automatically

charge whether the UPS is turned on or off.

2. Note: This UPS is designed with a safety feature to keep the system from being turned on during shipment.

The first time you turn the UPS on, you will need to have it connected to AC power or it will not power up.

3. With the UPS unit turned off and unplugged, connect your computer, monitor, and any other

peripherals requiring battery backup into the

battery power supplied outlets.

DO NOT plug a laser printer, paper shredder, copier, space heater, vacuum, sump pump or other large

electrical devices into the “Battery and Surge Protected Outlets”. The power demands of these devices may overload and damage

the unit.

4. Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall outlet). Make sure the wall branch outlet is protected by a fuse or circuit

breaker and does not service equipment with large electrical demands (e.g. air conditioner, copier, etc…). The warranty prohibits the use of

extension cords, outlet strips, and surge strips.

5. Press the power switch to turn the unit on. The Power On indicator light will illuminate and the unit will “beep”.

If an overload is detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn the UPS off and unplug at

least one piece of equipment from the battery power supplied outlets. Make sure the circuit breaker is depressed and then turn the UPS on.

6. To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times.

7. To store the UPS for an extended period, cover it and store with the battery fully charged. While in storage, recharge the battery every three

months to ensure battery life.

8. Insure the wall outlet and UPS are located near the equipment being attached for proper accessibility.

9. The LCD module is wall-mountable for extended distance control. Follow the steps below for installation procedure.

a. Remove the LCD module from the front panel.

b. Hang the LCD module on the wall.

c. Replacing the LCD on the UPS - To place the LCD back on the UPS, roll up the LCD cable, return it to the space between the front panel &

battery cover, and replace the LCD.



DESCRIPTION
Front Panel

1

Power Switch / Power On Indicator

Used as the master on/off switch for equipment connected to the battery power supplied outlets.

2

Online Indicator

This LED is illuminated when the utility power is normal and the UPS outlets are providing power, free of surges and spikes.

3

On Battery Indicator

During a severe brownout or blackout, this LED is illuminated and an alarm sounds (two short beeps followed by a pause) to indicate the

UPS is operating from its internal batteries.

4

Fault

This LED is illuminated if there is a problem with the UPS.

5

Replace Battery Indicator

This LED is illuminated to remind users to replace the battery.

6

Status/Tab Button

For UPS status information, press the button for 1 second. For additional information including

the use of the button as a Tab, please refer to the

Function Setup Guide

.

7

Setup/Enter Button

Press the Setup button for 1 second to enter setup menu and then select the functions for

configuration. For more information about the Setup/Enter button, please refer to the

Function

Setup Guide

.

8

Control/Up Button

Press the Control button for 1 second to enter control menu and then select the functions for

configuration. This button is also used to scroll up. For more information about the Control/Up

button, please refer to the

Function Setup Guide

.

9

Test/Down Button

Press the Test switch for 1 second to enter test menu and then select the functions for

configuration. This button is also used to scroll down. For more information about the Test/Down

button, please refer to the

Function Setup Guide

.

10 Logs/Esc Button

Press the Logs button for 1 second to view the events or logs that have been recorded.

This button is also used to exit a menu. For more information about Logs/Esc button,

please refer to the

Function Setup Guide

.

Rear Panel

1

Battery and Surge Protected Outlets

The unit has ten battery powered and surge protected outlets for connected equipment to

ensure temporary uninterrupted operation of your equipment during a power failure.

(DO NOT plug a laser printer, paper shredder, copier, space heater, vacuum, sump

pump or other large electrical devices into the “Battery and Surge Protected Outlets”.

The power demands of these devices may overload and damage the unit.)

2

Serial/USB Ports to PC

The Serial and USB ports allow connection and communication between the

computer and the UPS unit. Note: Only one port can be used at a time.

3

EPO Port

Use the provided gray EPO cable to connect to a provided EPO contact switch.

Follow the appropriate circuit diagram to the right to wire the cable to your

EPO configuration. The EPO remote switch is a switch installed in an outside

area, connected to the unit via the Emergency Power Off cable. In case of an

emergency, it can be used to immediately cut-off power from the UPS.

4

TVSS Ground

The TVSS GND only used for dielectric voltage-withstand test on production.

5

SNMP/HTTP Network Slot

Remove the cover panel to install an optional RMCARD to remotely monitor

and manage your UPS over a network.

6

Input Circuit Breaker

Located on the back of the UPS, the circuit breaker provides overload and

fault protection.

7

Output Circuit Breaker

Located on the back of the UPS, the circuit breaker provides overload and fault protection.

8

AC Input Power Cord

Heavy-duty power cord.

REPLACING THE BATTERY

Replacement of batteries located in an

OPERATOR ACCESS AREA

.

1.

When replacing batteries, replace with the same number of the following battery: CyberPower / RB12170X4 for the PR2000LCD,

PR2200LCD and PR3000LCD. Contact CyberPower Systems about replacement batteries.

2.

CAUTION!

Risk of Energy Hazard, 12V, maximum 20 Ampere-hour battery. Before replacing batteries, remove conductive jewelry such

as chains, wrist watches, and rings. High energy conducted through these materials could cause severe burns.

3.

CAUTION!

Do not dispose of batteries in a fire. The batteries may explode.

4.

CAUTION!

Do not open or mutilate batteries. Released material is harmful to the skin and eyes. It may be toxic.

CAUTION - RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE. DISPOSE OF USED BATTERIES ACCORDING

TO LOCAL REGULATIONS.

BATTERY REPLACEMENT PROCEDURE:

1.

Turn off and unplug all connected equipment.

2.

Turn the UPS off and unplug it from the AC power source.

3.

Remove the front panel of the UPS.

4.

Remove two screws from the battery compartment cover and slide the cover completely off of the unit.

5.

Pull out the battery pack on the outside from the compartment. Disconnect the battery connector from the batteries.

6.

Before removing the battery pack on the inside, unlock the cable tie and pull out the battery wires. Disconnect the battery connector from

the batteries. Pull out the battery pack on the inside from the compartment.

7.

Install the replacement battery pack on the inside by connecting the wire bundle connector (composed of one red wire and one black wire)

to the connector from the battery pack. Lock the battery wires back with the cable tie.

8.

Install the replacement batteries on the outside by connecting the wire bundle connector (composed of one red wire and one black wire) to

the connector from the battery pack. Put the battery pack on the outside back into the compartment.

9.

Re-install the battery compartment cover and tighten the retaining screws.

10.

Put the front panel back on the UPS.

11.

Connect to AC power and charge the new batteries for up to 16 hours to insure a full charge.

Note: The battery pack on the outside has a fuse, while the battery pack on the inside has not.

REMINDER:

Batteries are considered

HAZARDOUS WASTE

and must be disposed of properly. Most retailers that sell lead-acid batteries

collect used batteries for recycling, as required by local regulations.

Status Menu/Switch

Operation Mode

Load Power

Load VA

Load Amps

Load Energy

Estimated Runtime

Battery Information

Input

Output

Last Self Test

Date & Time

NCL Output

Setup Menu/Switch

Setup Wizard

Utility Power

MIN O/P Voltage

MAX O/P Voltage

LCD Auto Sleep

Cycling Display

Audible Alarm

Temporarily Mute

Sensitivity

Charge Mode

Low Battery Warning

Date & Time

Battery Change Date

Firmware Update

Power Meter Reset

Back to Default

Delay Turn On

Delay Turn Off

Reboot Duration

Minimum Restore Capacity

Uptime on Battery

Reserve Runtime

BASIC OPERATION

INSTALLING YOUR UPS SYSTEM

IMPORTANT SAFETY WARNINGS

DEFINITIONS FOR ILLUMINATED LCD INDICATORS