Page 2 - TABLE OF CONTENTS
CPS3000PIE 1 TABLE OF CONTENTS SAFETY AND EMC INSTRUCTIONS ………….……………………………………….………1 I N S TAL L I N G Y O U R E P S … … … … … … … … … … . … … … … … … … … … … … … … . … … 3 BASIC OPERATION …………………………………………...................................................4 REPLACING THE BATTERY …………………….……………………………...
Page 3 - SAFETY AND EMC INSTRUCTIONS
CPS3000PIE 2 K01-0000010-00 SAFETY AND EMC INSTRUCTIONS (SAVE THESE INSTRUCTIONS) This manual contains important safety instructions. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or ...
Page 4 - DO NOT USE WITH OR NEAR AQUARIUMS!; DO NOT USE WITH LASER PRINTERS!
CPS3000PIE 3 DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! DO NOT use in any circumstance that would affect operation or safety of any life support equipment or with any medical applications or patient care. DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire or electric shock, do not ...
Page 5 - INSTALLING YOUR EPS; AUTOMATIC VOLTAGE REGULATOR; HARDWARE INSTALLATION GUIDE; recharging the external
CPS3000PIE 4 INSTALLING YOUR EPS UNPACKING Inspect the EPS upon receipt. The box should contain the following: EPS unit x1; Installation Guide x1; User manual x1; Warranty card x1. AUTOMATIC VOLTAGE REGULATOR Utility power is inconsistent. The EPS increases low voltage to computer safe 220 volts. Th...
Page 6 - BASIC OPERATION; DESCRIPTION
CPS3000PIE 5 BASIC OPERATION DESCRIPTION 1. AC Outlets The unit has two Schuko outlets and one terminal for connected equipment which ensures temporary uninterrupted operation of your equipment during a power failure. Max. output of 1a is 20A; Max. output of 1b is 15A; Max. output wattage of (1a+1b)...
Page 7 - Power On Indicator; Installation Guide; Step 1; Step 3
CPS3000PIE 6 10. Power On Indicator This LED is above the power switch. It illuminates when the utility condition is normal and the EPS outlets are providing power, free of surges and spikes. 11. LCD Module Display High resolution and intelligent LCD display shows all the EPS information with icons ...
Page 8 - REPLACING THE BATTERY
CPS3000PIE 7 6. If the battery box or the battery connection has a switch, please turn it on first. 7. Turn on the BATTERY SW. on the back of the machine (Step 5) Step 5 Step 6 8. Make the AC input connection and turn on the Power Switch on the front panel. The Power On Indicator and the LCD Module ...
Page 9 - CONTACT WITH GROUNDED BATTERY CAN RESULT IN; DEFINITIONS FOR ILLUMINATED LCD
CPS3000PIE 8 CAUTION! A battery can present a high risk of short circuit current and electrical shock. Take the following precautions before replacing the battery: 1. Remove all watches, rings or other metal objects. 2. Only use tools with insulated handles. 3. Do not lay tools or metal parts on top...
Page 10 - EPS Status Inquiry and Functions Setup; Display
CPS3000PIE 9 6. SILENT MODE Icon: This icon illuminates whenever the EPS is in silent mode. The buzzer will not beep during the battery mode until the battery reaches low capacity. 7. OVER LOAD Icon: This icon will illuminate and an alarm will sound to indicate the battery supplied outlets are overl...
Page 13 - TROUBLESHOOTING; Problem
CPS3000PIE 12 Battery Icon Flash Beep Once Battery Missing- In Line Mode Battery Missing. Turn the EPS off, check battery wiring and presence of battery Fault Icon 1. Rapid Beep 2. Recurring Beep 3. Long Beep 1. Low Battery Output-Off -- Insufficient battery capacity. 2. Over Charge or AVR Error-- I...
Page 14 - TECHNICAL SPECIFICATIONS
CPS3000PIE 13 TECHNICAL SPECIFICATIONS Model CPS3000PIE Capacity (VA) 3000VA Capacity (Watts) 2250W Operation Technology AVR ( Single Boost & Single Buck ) AC Input Input Voltage Range 140Vac – 300Vac Input Frequency Range 50/60 Hz +/- 3 Hz (auto sensing) AC Output Number of Phase Single Phase O...