Automatic Voltage Regulators

increase low or decrease high voltage to computer
safe 110/120 volts. The AVR automatically provides
battery back-up power if line voltage drops below 90
volts or exceeds 140 volts.

AVR

INCONSISTENT

UTILITY POWER

CONSISTENT

SAFE POWER

IN

OUT

CP900D / CP1000D /

CP1200D / CP1285D / CP1500D

User’s Manual

K01-0000003-00

(SAVE THESE INSTRUCTIONS)

This manual contains important safety instructions. Please read and follow all instructions carefully during installation and operation of the
unit. Read this manual thoroughly before attempting to unpack, install, or operate your UPS.

CAUTION!

To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area free of conductive

contaminants. (Please see specifications for acceptable temperature and humidity range).

CAUTION!

To reduce the risk of electric shock, do not remove the cover except to service the battery. No user serviceable parts inside

except for battery.

CAUTION!

Hazardous live parts inside can be energized by the battery even when the AC input power is disconnected.

CAUTION!

UPS must be connected to an AC power outlet with fuse or circuit breaker protection. Do not plug into an outlet that is not

grounded. If you need to de-energize this equipment, turn off and unplug the unit.

CAUTION!

To avoid electrical shock, turn off the unit and unplug it from the AC power source before servicing the battery or installing a

computer component.

CAUTION!

To reduce the risk of fire, connected only to a circuit provided with 20 amperes maximum branch circuit over current protection in

accordance with the national Code, ANSI / NFPA 70.

DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT!

CyberPower Systems does not sell products for life support or medical

applications. DO NOT use in any circumstance that would affect operation or safety of any life support equipment or with any medical
applications or patient care.

DO NOT USE WITH OR NEAR AQUARIUMS!

To reduce the risk of fire or electric shock, do not use with or near an aquarium.

Condensation from the aquarium can cause the unit to short out.

DO NOT USE WITH LASER PRINTERS!

The power demands of these devices will overload and possibly damage the unit.

UNPACKING

Inspect the UPS upon receipt. The box should contain the following:
(1) UPS unit; (1) User’s manual; (1) PowerPanel™ Personal Edition software CD; (1) USB device cable; (1) Telephone cable; (1) Warranty
registration card; (1) Coaxial Cable

OVERVIEW

The CP900D / CP1000D / CP1200D / CP1285D / CP1500D provide automatic voltage regulation for
inconsistent utility power. The CP900D / CP1000D / CP1200D / CP1285D / CP1500D features
890/890/1080/1080/1500 Joules of surge protection, and provide battery backup during power outages.
The CP900D / CP1000D / CP1200D / CP1285D / CP1500D ensure consistent power to your computer
system and include software that will automatically save your open files and shutdown your computer
system during a utility power loss.

AUTOMATIC VOLTAGE REGULATOR?

The CP900D / CP1000D / CP1200D / CP1285D / CP1500D stabilize inconsistent utility power. The incoming utility
power may be damaging to important data files, but with Automatic Voltage Regulation, the computer will not experience
damaging voltage levels. An Automatic Voltage Regulator automatically increases low or decreases high voltage to a consistent,
computer safe 110v/120v. The unit’s powerful sealed lead-acid batteries will provide power only if the incoming voltage drops below 90v or
increases above 140v.

HARDWARE INSTALLATION GUIDE

1. Your new UPS may be used immediately upon receipt. However, recharging the batteries for at least 16 hours is recommended to insure

that the battery’s maximum charge capacity is achieved. A loss of charge may occur during shipping and storage. To recharge the
batteries, simply leave the unit plugged into an AC outlet. The unit will charge in both the ON as well as the OFF position.

2. With the UPS unit off and unplugged, connect your computer, monitor, and any externally powered data storage device (Zip drive, Jazz

drive, Tape drive, etc…) into the battery power supplied outlets. Plug your peripheral equipment (printer, scanner, speakers) into the full-
time surge protection outlets.

DO NOT plug a laser printer, paper shredder, copier, space heater, vacuum or other large electrical

device into the UPS. The power demands of these devices will overload and possibly damage the unit.

3. To surge protect a network connection, connect a network cable from the wall jack outlet to the IN jack of the UPS. Then connect a

network cable from the OUT jack on the UPS to the network device.

4. Plug the UPS into a 2 pole, 3 wire grounding receptacle (wall outlet). Make sure the wall branch outlet is protected by a

fuse or circuit breaker and does not service equipment with large electrical demands (e.g. refrigerator, copier, etc…).
The warranty prohibits the use of extension cords, outlet strips, and surge strips.

5. Press the power switch to turn the unit on. The power on indicator light will illuminate and the unit will “beep” once.
6. If an overload is detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn the UPS off and unplug at

least one piece of equipment from the battery power supplied outlets. Wait 10 seconds. Make sure the circuit breaker is depressed and
then turn the UPS on.

7. To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times.
8. To store your UPS for an extended period, cover it and store with the battery fully charged. While in storage recharge the battery every

three months to insure battery life.

DESCRIPTION

1 Power Switch

Can be used as a master on/off switch for equipment connected to the battery power supplied outlets.

2 Power On Indicator

This LED is illuminated when the utility condition is normal and the UPS outlets are providing power, free of surges.

3 Using Battery Indicator

This LED is illuminated when the unit is running in the backup condition.

4 AVR Indicator

This LED is illuminated when the unit is running in the AVR mode.

5 Over Load Indicator

This LED is illuminated when the unit is overload. You will need to reduce the load.

6 Battery and Surge Protected Outlets

The unit has four battery powered/surge protected outlets for connected equipment and insures temporary
uninterrupted operation of your equipment during a power failure.

7 Full-Time Surge Protection Outlets

The unit has four always on surge suppression outlets.

8 Electrical Wiring Fault Indicator

This LED indicator will illuminate to warn the user that a wiring problem exists, such as bad ground, missing ground or reversed wiring. If
this is illuminated, user is advised to disconnect all electrical equipment from the outlet and have an electrician check to ensure the outlet is
properly wired. The unit will not provide surge protection without being plugged into a grounded and properly wired wall outlet.

9 Communication Protection Ports

Communication protection ports will protect any standard modem, fax , telephone line, broadband network or Ethernet connection.

10 Circuit Breaker

Located on the side of the UPS, the circuit breaker serves to provide overload and fault protection.

11 Serial/USB Ports to PC

The ports allow connection and communication from the USB or DB-9 serial port on the computer to the UPS unit. The USB port will
communicate with PowerPanel™ Personal Edition and the DB-9 port is for use with a serial cable and the Microsoft UPS Service.

CAUTION!

Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery. Service the battery under the

supervision of personnel knowledgeable of batteries and their precautions.

CAUTION!

Use only the specified type of battery. See your dealer for replacement batteries.

CAUTION!

The battery may present a risk of electrical shock. Do not dispose of battery in a fire as it may explode. Follow all local

ordinances regarding proper disposal of batteries. Almost any retailer that sells lead-acid batteries collects used batteries for recycling, as
required by most state laws.

CAUTION!

Do not open or mutilate the batteries. Released electrolyte is harmful to skin and eyes and may be toxic.

CAUTION!

A battery can present a high risk of short circuit current and electrical shock. Take the following precautions before replacing the

battery:
1.Remove all watches, rings or other metal objects.
2.Only use tools with insulated handles.
3.Do not lay tools or metal parts on top of battery or any terminals.
4.Wear rubber gloves and boots.
5.Determine if the battery is inadvertently grounded. If grounded, remove the source of ground.

CONTACT WITH GROUNDED BATTERY

CAN RESULT IN ELECTRICAL SHOCK!

Model

CP900D

CP1000D

CP1200D

CP1285D

CP1500D

Capacity

900VA / 560W

1000VA / 580W

1200VA / 720W

1285VA / 750W

1500VA / 900W

Input Voltage on Utility

90V to 140V

Input Frequency

60 Hz ± 3 Hz

On-Battery Output Voltage

120Vac ± 5%

Transfer Time

4ms Typical

Max. Load for UPS Outlets

900VA / 560W

1000VA / 580W

1200VA / 720W

1285VA / 750W

1500VA / 900W

Max. Load for Full-Time
Surge Protection outlets (8 Outlets)

12 Amps

On-Battery Output Wave Form

Simulated Sine Wave Form

Operating Temperature

+ 32°F to 95° F / 0° C to 35° C

Operating Relative Humidity

0 to 95% NON-CONDENSING

Size (L x W x H)

13 1/8” x 4” x 9 7/8”

33.3 x 10.0 x 24.9cm

Net Weight

22.2 lbs

24.4 lbs

25.6 lbs

Typical Battery Recharge Time

8 hours typical from total discharge

Typical Battery Life

3 to 6 years, depending on number of discharge/recharge cycles

Battery Type

Spill-proof, Maintenance-free, sealed lead-acid

Safety Approvals

UL1778(UPS), cUL107., FCC/DoC Class B

Model

iMac G4

Desktop PC

Desktop PC

Desktop PC

Desktop PC

with LCD Monitor

with 15” Monitor

with 17” Monitor

with 21” Monitor

CP900D

105 minutes

75 minutes

60 minutes

40 minutes

35 minutes

CP1000D

105 minutes

75 minutes

60 minutes

40 minutes

35 minutes

CP1200D

145 minutes

90 minutes

66 minutes

50 minutes

42 minutes

CP1285D

145 minutes

90 minutes

66 minutes

50 minutes

42 minutes

CP1500D

170 minutes

100 minutes

75 minutes

58 minutes

48 minutes

IMPORTANT SAFETY WARNINGS

INSTALLING YOUR UPS SYSTEM

BASIC OPERATION

TROUBLE SHOOTING

TECHNICAL SPECIFICATIONS

1. Turn off and unplug all connected equipment.
2. Turn the UPS off and unplug it from the AC power source.
3. Turn the UPS upside down.
4. Remove the retaining screw.
5. Slide the battery compartment cover (front panel) completely off of the unit.
6. Remove the batteries from the compartment.
7. Disconnect the battery wires from the batteries.
8. Install the replacement batteries by connecting the red wire and black wire to the same color

wires from the battery pack.

9. Put the batteries back into the compartment.
10. Slide back the battery compartment cover and tighten the retaining screw.
11. Recharge the UPS for 8-16 hours to fully charge the battery.

REPLACING THE BATTERY

REMINDER:

Batteries are consider HAZARDOUS WASTE and must be disposed of properly. Almost any retailer that sells lead-acid

batteries collects used batteries for recycling, as required by most state laws.

Additional troubleshooting information can be found at

www.cyberpowersystems.com/support.htm

Problem

Possible Cause

Solution

Full-time surge protection outlets

stop providing power to equipment.

Circuit breaker button is projecting

from the side of the unit.

Circuit breaker has

tripped due to an

overload.

Turn the UPS off and unplug at least one piece of equipment.

Wait 10 seconds, reset the circuit breaker by depressing the

button, and then turn the UPS on.

The UPS does not perform

expected runtime.

Recharge the battery by leaving the UPS plugged in.

Contact CyberPower Systems about replacement batteries at

[email protected]

Battery is slightly worn out.

Battery not fully charged.

The UPS will not turn on.

The on/off switch is designed

to prevent damage by rapidly

turning it off and on.

Turn the UPS off. Wait 10 seconds and then turn the UPS on.

The unit is not connected to an

AC outlet.

The unit must be connected to a 110/120v 60Hz outlet.

The battery is worn out.

Contact CyberPower Systems about replacement batteries at

[email protected]

Mechanical problem.

Contact CyberPower Systems at

[email protected]

PowerPanel™ Personal Edition

is inactive (all icons are gray).

The USB cable is not

connected.

Connect the USB cable to the UPS unit and an open USB port

on the back of the computer. You must use the cable that came

with the unit.

The USB cable is connected

to the wrong port.

Check the back of the computer for an additional USB port.

Move the cable to this port.

The unit is not providing

battery power.

Shutdown your computer and turn the UPS off. Wait 10

seconds and turn the UPS back on. This should reset the unit.

EXPECTED RUNTIME IN MINUTES

(Due to the differences in computer components, the runtime will vary.)

12 Coax/Cable/DSS Surge Protection

The Coax/Cable/DSS surge protection ports will protect any cable modem, CATV converter, or DSS receiver.

13 Outlets Designed for AC Adapters

The unit has four outlets spaced to allow AC power adapter blocks to be plugged into the UPS without blocking adjacent outlets.

Note: Only one of these two ports can be used to communicate with your computer at one time.
Note: To install PowerPanel™ Personal Edition Software the computer will need Microsoft

R

Internet Explore 5.0 or higher installed.

Note: If using the Serial Port please read the directions to configure the Microsoft

R

UPS service on our website

http://www.cyberpowersystems.com/ups_service.asp . If you need a serial cable please contact CyberPower technical support at
[email protected]

TO REPLACE THE BATTERY