Table of Contents:

  • Page 2 – INSTALLATION; To avoid electrical shock hazard, boilers; WIRING; Hazard of Electrical Shock. Disconnect
  • Page 3 – ADJUSTING PRESSURE CONTROLS; Blowdown is an essential part of boiler operation. It is the best; SCHEMATIC WIRING DIAGRAM
  • Page 4 – MAINTENANCE; Hazard of Electric Shock. Disconnect all
  • Page 5 – RENEWAL PARTS IDENTIFICATION
Loading the manual

(Supersedes PQ435)

PQ435-1

cas

161-562795-001

JUNE, 1994

4

and

Installation, Operation

RENEWAL PARTS IDENTIFICATION

Type CAS-20CM Electric Steam Boiler

(Standard Trim is 100 PSI — 0-90 PSI Operating Pressure Range)

© 2010 Chromalox, Inc.

Model

Electric Capacity

BHP Rating

Voltage

Phase

Amperes Drawn

Contactor

20 kW

2.0

208

1

96

50A, 4 Pole

16/20 kW

1.6/2.0

208/230

3

45/51

60A, 3 Pole

CAS-20CM

20 kW

2.0

240

1

84

50A, 4 Pole

20 kW

2.0

346

3

34

40A, 3 Pole

20 kW

2.0

380

1

53

60A, 2 Pole

20 kW

2.0

480

3

24

30A, 3 Pole

Note:

Control circuit 120V

Boiler Serial No. ______________________________________________ Power Circuit Voltage __________________________

Model No. ___________________________________________________ Control Circuit Voltage __________________________

National Board No. ____________________________________________ Amps ___________Phase __________Cy __________

IMPORTANT –

This data file contains the National Board Registration Certificate approving your boiler. It must be kept near the boiler at all

times.

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - INSTALLATION; To avoid electrical shock hazard, boilers; WIRING; Hazard of Electrical Shock. Disconnect

INSTALLATION WARNING: To avoid electrical shock hazard, boilers must be suitably grounded to earth. Note: Chromalox boilers are pre-tested before shipment; no inter- nal piping or wiring is necessary. WARNING: Substitution of components or modification of wiring without prior consent ofChromalox voi...

Page 3 - ADJUSTING PRESSURE CONTROLS; Blowdown is an essential part of boiler operation. It is the best; SCHEMATIC WIRING DIAGRAM

SOLID STATE FLOATLESS LIQUID LEVELCONTROL SYSTEM This boiler is equipped with a solid state, floatless liquid level control which operates by sensing the electrical resistance ofwater. Note: Control will not work with de-ionized or demineral- ized water. Two probes are provided. The HI probe activat...

Page 4 - MAINTENANCE; Hazard of Electric Shock. Disconnect all

MAINTENANCE WARNING: Hazard of Electric Shock. Disconnect all power before working on boiler. 1. A monthly inspection should be made to ensure that all electri-cal connections are tight. 2. When steam or water leaks are observed, fittings should betightened immediately. 3. Every four months, the Sol...