Page 2 - Chromalox 8003 User's Manual; C o n t e n t s
Chromalox 8003 User's Manual i C o n t e n t s Model Identification .................................................................................................................................... Page ii Dimensions and Panel Cutout ..................................................................
Page 3 - Model Identification
ii Chromalox 8003 User's Manual Model Identification Model 8003 1/8 DIN Temperature Controller Code Output 1 - Heat or Cool 1 SPDT Relay, 3 Amps at 250 Vac (Resistive) orSSR Drive, 14V @ 20mA, Jumper Selectable Code Output 2 - Cool or Alarm 1 Relay, 2 Amps at 250 Vac (Resistive) orSSR Drive, 14V @ 2...
Page 5 - Wiring; Operating
2 Chromalox 8003 User's Manual Warnings: • When a relay output is used to drive an inductive load, it is suggested that you connect an externalsnubber network (RC) across the terminals inaccordance with the following table (or useChromalox snubber P/N 0149-01305): • Do not run sensor input wires tog...
Page 6 - Hardware Setup; Move the jumpers to the desired position as shown in
Chromalox 8003 User's Manual 3 Hardware Setup To select the output type(s) and the alarm contact settings:1. Remove the instrument from its case. 2. Move the jumpers to the desired position as shown in the diagram. 3. Set J304 and J305 as shown in the following figure. PZ22 PZ21 PZ20 PZ19 PZ18 PZ17 ...
Page 7 - General Operation; Configuration Procedure; Note
4 Chromalox 8003 User's Manual General Operation There are two setup modes for the 8003: • Configuration Mode• Operator Mode In general, the Configuration Mode is the initial setup ofthe controller when first installed. Input type and alarmsetup are examples of Configuration Mode settings. TheOperat...
Page 8 - R a n g e; minimum
Chromalox 8003 User's Manual 5 P1 = Input Type and Standard Range R a n g e 0 = TC type L 0 / +800 ° C 1 = TC type J 0 / +800 ° C 2 = TC type K 0 / +999 ° C 3 = TC type N 0 / +999 ° C 4 = RTD type Pt 100 -199 / +500 ° C 5 = RTD type Pt 100 -19.9 / +99.9 ° C 8 = TC type L 0 / +999 ° F 9 = TC type J 0...
Page 9 - P11 = Alarm 2 Operative Mode; Available only when P10 is different from 0.; P12 = Alarm 2 Inhibit; Available only when P10 is different from 0; : The Alarm Inhibit disables the alarm action after a; P13 = Type of OFFSET Applied to the Measured Value
6 Chromalox 8003 User's Manual P9 = Alarm 1 Inhibit Available only when P7 is different from 0. OFF = inhibit disabledON = inhibit enabled Note : The Alarm Inhibit disables the alarm action after a setpoint change. At startup, it automatically enables thealarm when the process temperature reaches th...
Page 11 - SMART function; —This parameter may be programmed; SMART function in heating control only; SMART function in heating/cooling only; —This
8 Chromalox 8003 User's Manual P22 = Alarm 2 Relay Action This parameter is available only if P10 is different from 0and P16 is different from OFF. r = Reverse (relay de-energized in alarm condition)d = Direct (relay energized in alarm condition) P23 = Automatic Adjustment of "Relative Cooling G...
Page 12 - SMART Function; the SMART function is disabled.; Operator Mode
Chromalox 8003 User's Manual 9 SMART Function SMART automatically determines the best PID controlparameters for your application. To enable the SMART function, push the SMRTpushbutton. The SMRT LED will light or flash accordingto the algorithm automatically selected. When the SMART function is enabl...
Page 13 - Output Power Off
10 Chromalox 8003 User's Manual The upper display will show the measured value while thelower display will show the programmed setpoint value(we define this status as “normal display mode”). Pushbutton functionality during operating mode : FUNC = Stores the new value of a selected parameter and incr...
Page 14 - Push the; pushbutton. The lower display shows the cue,
Chromalox 8003 User's Manual 11 td Derivative (rate), range 1 second to 9 minutesand 59 seconds. If 0, derivative is disabled. C Heating cycle time, range 1 to 200 seconds (30seconds or greater recommended for relay outputs). C2 Cycle Time for Output 2 (heat/cool controlselected), range 1 to 200 sec...
Page 15 - Error Messages; Overrange or Underrange Indications; : When an overrange condition is detected, the
12 Chromalox 8003 User's Manual Error Messages Overrange or Underrange Indications The instrument shows the OVERRANGE conditionswith the following indication on the upper display: The instrument shows the UNDERRANGE conditionswith the following indication on the upper display: Burn-out conditions ar...
Page 16 - Error List; When a configuration parameter error is
Chromalox 8003 User's Manual 13 Error Messages The instrument has a self-diagnostic algorithm. When anerror is detected, the instrument shows “Err” indicationon the lower display while the upper display shows thecode of the detected error. Error List 100 Write EEPROM error. 150 CPU error. 200 Write ...
Page 18 - Returns
Chromalox 8003 User's Manual 15 submit a claim as provided above shall specifically waiveall claims for damages or other relief, including but notlimited to claims based on latent defects. In no eventshall buyer be entitled to incidental or consequentialdamages and buyer should hold Chromalox harmle...