Carrier PC 111- User Manual
Carrier PC 111– User Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 3 – Processor Board —; Table 1 — Pin Terminal Connector J1; Fig. 1 — Processor Board
- Page 5 – Relay Board —; The relay board is used to control 24-v; Display Board —; The display board is located in the; Thermistors —; The processor uses up to 5 thermistors to
- Page 6 – Table 3 — Output Pin and Terminal Assignments
- Page 10 – Economizer —; Economizer control is used to control the; Fig. 13 — Thermistor T3 and T4 Locations,
- Page 18 – Demand Limit —; The demand limit function provides a; SPACE TEMPERATURE RESET — 4 SENSOR AVERAGING APPLICATION; Fig. 26 — Space Temperature Sensor Averaging
- Page 19 – Fig. 29 — 115-Volt Field Wiring to Accessory
- Page 21 – Smoke Control Modes —; Fig. 30 — Remote SASP Wiring; Fig. 31 — External Alarm Indication
- Page 22 – Table 5 — Smoke Control Modes
- Page 23 – Table 7 — Switch Functions; Air Pressure Tubing —; Table 8 — Tubing Size
- Page 24 – Fig. 32 — Smoke Control Wiring
- Page 25 – Initial Check; Fig. 33 — Modulating Power Exhaust and Inlet
- Page 26 – Table 9 — Potentiometer Inputs and Ranges; Configuration Header —; The configuration header is a; Table 10 — Configuration Header and; DIP Switches —; The DIP switches configure the unit for
- Page 27 – Table 12 — DIP Switches; Adjusting Set Points —
- Page 28 – Supply Fan Control with IGV Option —; The inlet; Supply Fan Control with VFD Option —; The VFD
- Page 29 – SPEED CTRL; STOP; Fig. 39 — Differential Pressure Switch for Inlet; Fig. 40 — Variable Frequency Drive Keypad
- Page 30 – Table 13 — VFD Set Point (Frequency Command) for Duct Pressure; The power exhaust VFD will modu-
- Page 31 – START UNIT
- Page 32 – Table 16 — Quick Test, Unit Configuration and Switch Check
- Page 34 – Table 19 — Sensor Resistance Values; If the quick test steps do not operate as described above, a; OPERATING INFORMATION; The VAV control system uses a 2-digit
- Page 35 – Operating Sequence —
- Page 36 – Head Pressure Control —
- Page 42 – Table 20 — Compressor Loading and Unloading Sequences
- Page 43 – Table 20 — Compressor Loading and Unloading Sequences (cont)
- Page 44 – TROUBLESHOOTING; Table 21 — Controls Troubleshooting
- Page 45 – Table 22 — Operation Status Codes; Restart Procedure —
- Page 46 – Table 23 — Diagnostic Codes; The processor monitors the low-pressure switch. If the
- Page 49 – Fig. 49 — Processor Board Test Points
- Page 51 – Step 2 — High-voltage relay resistance check.; Table 27 — Terminal Strip J6 Connection; Table 28 — Terminal Strip J5 Connector
- Page 52 – Enthalpy Sensor Checkout —; Table 29 — Enthalpy Sensor Checkout; Economizer Motor —
- Page 53 – Fig. 54 — Supply Fan Variable Frequency Drive
- Page 54 – Table 30 — Carrier Default Program Parameter Values (Supply Fan VFD)
- Page 56 – Fig. 56 — Variable Frequency Drive Terminal Block
- Page 57 – Unit Wiring —
- Page 58 – LEGEND AND NOTES FOR FIG. 57
- Page 62 – SERVICE TRAINING; • Unit Familiarization
- Page 63 – CONTROL SETTINGS
- Page 64 – ELECTRICAL
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111
Catalog No. 534-763
Printed in U.S.A.
Form 48/50F,J-3T
Pg 1
3-00
Replaces: 48/50F,J-1T
Book 1
1
Tab
1a 1b
Controls Operation,
and Troubleshooting
CONTENTS
Page
SAFETY CONSIDERATIONS
. . . . . . . . . . . . . . . . . . . . . . 2
GENERAL
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Rooftop Information
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
VAV Control System
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Processor Board
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
• P1 — SUPPLY-AIR SET POINT
• P2 — ECONOMIZER POSITION
• P3 — RESET LIMIT
• P4 — DEMAND LIMIT
• P5 — ECONOMIZER MINIMUM POSITION
• P6 — WARM-UP SET POINT
• P7 — SASP RESET TEMPERATURE
• PROCESSOR BOARD OUTPUTS
• CONFIGURATION HEADER AND DIP SWITCH
ASSEMBLY
Relay Board
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Display Board
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Thermistors
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
• T1 — SUPPLY-AIR TEMPERATURE THERMISTOR
• T2 — RETURN-AIR TEMPERATURE THERMISTOR
• T3 — SATURATED CONDENSING TEMPERATURE,
CIRCUIT 1
• T4 — SATURATED CONDENSING TEMPERATURE,
CIRCUIT 2
• T10 — RESET TEMPERATURE
Compressor Operation
. . . . . . . . . . . . . . . . . . . . . . . . . . . 7
• CONTROL RELAY (CR)
Accessory Board
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
• P3 — RESET LIMIT
• P5 — ECONOMIZER MINIMUM POSITION
• P6 — MORNING WARM-UP TEMPERATURE
Single-Step Demand Unit
. . . . . . . . . . . . . . . . . . . . . . . . . 7
Demand Limit Control Module (DLCM)
. . . . . . . . . . . 7
Economizer
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
• ENTHALPY CONTROL
• DIFFERENTIAL ENTHALPY
Supply Fan Variable Frequency Drive (VFD)
. . . . . 12
High Capacity Modulating Power
Exhaust Variable Frequency Drive
. . . . . . . . . . . . 12
Temperature Reset
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
CONTROLS INSTALLATION
. . . . . . . . . . . . . . . . . . 13-25
Control Wiring
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
• NIGHT SETBACK THERMOSTAT
• SPACE TEMPERATURE RESET ACCESSORY
(50DJ900021)
Space Temperature Reset
. . . . . . . . . . . . . . . . . . . . . . 13
• INSTALLATION
• CONFIGURATION
• OPERATING SEQUENCE
Demand Limit
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
• SINGLE-STEP DEMAND LIMIT
• TWO-STEP DEMAND LIMIT
• INSTALLATION
• CONFIGURATION
• OPERATING SEQUENCE
Page
Control From Remote Building Management
System (BMS)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
• OCCUPIED/UNOCCUPIED
• NIGHT SETBACK CONTROL
• UNIT SUPPLY AIR SET POINT ADJUSTMENT
• DEMAND UNIT (1-STAGE OR 2-STAGE)
• SUPPLY DUCT PRESSURE SET POINT ADJUSTMENT
• EXTERNAL ALARM SIGNAL
• REMOTE ECONOMIZER CONTROL
Smoke Control Modes
. . . . . . . . . . . . . . . . . . . . . . . . . . . 21
• FIRE SHUTDOWN MODE
• PRESSURIZATION MODE
• EVACUATION MODE
• SMOKE PURGE MODE
• INSTALLATION
• CONFIGURATION
• OPERATING SEQUENCE
Air Pressure Tubing
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
• INLET GUIDE VANES
• SUPPLY FAN VARIABLE FREQUENCY DRIVE
• MODULATING POWER EXHAUST
START-UP
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25-31
Initial Check
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Configuration Header
. . . . . . . . . . . . . . . . . . . . . . . . . . . 26
DIP Switches
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Adjusting Set Points
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Potentiometers
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Supply Fan Control with IGV Option
. . . . . . . . . . . . 28
Supply Fan Control with VFD Option
. . . . . . . . . . . . 28
Modulating Power Exhaust Option or
Accessory) (48FK,JK and 50FK,JK Units)
. . . . . 30
High Capacity Power Exhaust
(48FM and 50FM,FS Units)
. . . . . . . . . . . . . . . . . . . . 30
START UNIT
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31-34
Quick Test Program
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
OPERATING INFORMATION
. . . . . . . . . . . . . . . . . . 34-44
Digital Display
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
• CODES 0 THROUGH 8, CAPACITY STEPS
• CODES 20 THROUGH 30 AND 88, OPERATIONAL
STATUS
• CODES 51 THROUGH 87, DIAGNOSTIC
INFORMATION
Operating Sequence
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
• SIZE 034, 038 AND 048-088 UNITS
• SIZE 044 UNITS
• SIZE 104 UNITS
Head Pressure Control
. . . . . . . . . . . . . . . . . . . . . . . . . . 36
Supply Fan Control with IGV
. . . . . . . . . . . . . . . . . . . . 38
Supply Fan Control with VFD
. . . . . . . . . . . . . . . . . . . . 38
Modulating Power Exhaust (48FK,JK and
50FK,JK Units Option or Accessory)
. . . . . . . . . . 38
High Capacity Modulating Power Exhaust
(48FM and 50FM,FS Units)
. . . . . . . . . . . . . . . . . . . . 38
Unit Staging
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
48FK,JK034-104
48FM078-104
50FK,FY,JK,JY034-104
50FM,FS078-104
Variable-Air Volume Rooftop Units
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Other Manuals for Carrier PC 111
Summary
3 The VAV control system monitors and controls the follow- ing functions of the rooftop unit:• supply-air temperature (unit capacity) • morning warm-up or electric heat (if equipped) • head pressure control, fan cycling • economizer position • diagnostic display • unit check-out (quick test) • suppl...
5 All of the potentiometers must be set before the unit is start- ed in order for the unit to function properly. See Start Up, Po-tentiometers section on page 27 for information on establishingset points. Each of the potentiometers has a valid range that isused by the control. The valid range is def...
6 Table 3 — Output Pin and Terminal Assignments LEGEND *Circuit 1. †Circuit 2. **U2 is not used on 044 units. ††OFC2 on 034-048 units; OFC3 on 054-104 units. || Used on 054-104 units only. OUTPUT PIN- TERMINAL NAME RATING DEVICE J6-1 Stage 1Compressor Relay (K1)* 24 vac CR1 J6-2 Stage 2Compressor Re...