Carrier GAS FURNACE 58MVP- User Manual
Carrier GAS FURNACE 58MVP– User Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – UNIT
- Page 3 – Fig. 3—Clearances to Combustibles; INSTALLATION; MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION; DÉGAGEMENT MINIMUM EN POUCES AVEC ÉLÉMENTS DE
- Page 6 – Step 2—Upflow Applications; Fig. 5—Condensate Trap
- Page 7 – FIRE, INJURY OR DEATH HAZARD; Fig. 6—Factory-Shipped Upflow Tube Configuration
- Page 8 – MINOR PROPERTY DAMAGE; Fig. 8—Horizontal Left Tube Configuration
- Page 12 – hot; UNIT DAMAGE HAZARD; Fig. 11—Proper Condensate Drainage; HORIZONTAL; Fig. 12—Prohibit Installation on Back; Fig. 13—Freeze Protection
- Page 13 – AIR FOR COMBUSTION AND VENTILATION
- Page 14 – National Fuel Gas Code ANSI; EXAMPLES: Determining Free Area
- Page 16 – multiplied by reduction; Factor; The Air Systems Design Guide-; Fig. 16—Crawlspace Horizontal Application
- Page 17 – RETURN AIR CONNECTIONS; FIRE HAZARD; Side return-air openings can ONLY be used in UPFLOW; Table 3—Filter Information; AIR FILTER LOCATED IN BLOWER COMPARTMENT; Filter Type
- Page 18 – Fig. 17—Filter Installed for Side Inlet; Fig. 18—Bottom Filter Arrangement
- Page 19 – The gas valve inlet pressure tap connection is suitable to; Step 6—Electrical Connections; Proper polarity must be maintained for 115-v wiring. If; Table 4—Maximum Capacity of Pipe*
- Page 20 – Fig. 22—Disconnect Switch and Furnace
- Page 21 – FIRE OR ELECTRICAL SHOCK HAZARD
- Page 23 – Diagram
- Page 24 – Fig. 25—Control Center
- Page 25 – UNIT MAY NOT OPERATE; ASTM SPECIFICATION; Connections
- Page 26 – A 2-in. diameter pipe must be used within the furnace; NOTE; Fig. 28—Combustion-Air Inlet Pipe Assembly; CASING WIDTH
- Page 27 – Table 7—Maximum Allowable Pipe Length (ft); UNIT SIZE
- Page 29 – Step 8—Condensate Drain
- Page 30 – Step 1—General
- Page 31 – Table 9—Other than Direct Vent Termination Clearance
- Page 32 – Excessive airflow caused by improper A/C switch setup; Table 10—Furnace Setup Switch Description; MIN; Table 11—Blower Off Delay Setup Switch; DESIRED HEATING; Fig. 31—Roof Termination Required; ROOF
- Page 33 – Fig. 32—Freeze Protection; CONDENSATE TRAP
- Page 34 – Step 4—Purge Gas Lines; If a power interruption occurs during a call for heat; Fig. 35—A/C or CF Airflow Selection Chart
- Page 35 – calls for heat; Inducer Prepurge Period; -The furnace control CPU turns on; Fig. 38—Filling Condensate Trap
- Page 40 – See note 2
- Page 42 – * Orifice numbers shown in
- Page 43 – Onl
- Page 44 – Fig. 47—Redundant Automatic Gas Valve; Fig. 48—Burner Orifice; BURNER
- Page 45 – Table 14—Gas Rate Cu Ft/Hr
- Page 46 – Fig. 50—Amp Draw Check with Ammeter; THERMOSTAT SUBBASE; CONTROL TERMINALS
- Page 47 – CHECKLIST
- Page 48 – CHECKLIST—INSTALLATION
58MVP
Variable-Capacity Condensing Gas Furnace
Installation, Start-Up, and Operating Instructions
For Sizes 040-120, Series 180
For use by Beutler Heating and Air for Renaissance Builders
Index
Page
SAFETY CONSIDERATIONS .....................................................3
DIMENSIONAL DRAWING ........................................................2
Clearances to Combustibles......................................................3
CODES AND STANDARDS ........................................................5
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS........5
INTRODUCTION ..........................................................................5
APPLICATIONS............................................................................5
General ......................................................................................5
Upflow Applications .................................................................6
Horizontal Left (Supply-Air Discharge) Applications ............8
Horizontal Right (Supply-Air Discharge) Applications ..........9
LOCATION..................................................................................11
General ....................................................................................11
Low-Heat Only Installation ....................................................12
Furnace Location Relative to Cooling Equipment ................13
AIR FOR COMBUSTION AND VENTILATION ....................13
INSTALLATION .........................................................................16
Installation In Horizontal Applications ..................................16
Air Ducts .................................................................................16
General Requirements .......................................................16
Ductwork Acoustical Treatment .......................................17
Supply-Air Connections ....................................................17
Return-Air Connections.....................................................17
Filter Arrangement ..................................................................17
Bottom Closure Panel .............................................................18
Gas Piping ...............................................................................18
Electrical Connections ............................................................19
115-v Wiring......................................................................19
24-v Wiring........................................................................21
Accessories ........................................................................21
Venting ....................................................................................21
Removal of Existing Furnaces from
Common Vent Systems................................................21
Combustion-Air and Vent Piping .....................................22
Vent Termination .........................................................29
Multiventing.......................................................................29
Condensate Drain ....................................................................29
General ...............................................................................29
Application.........................................................................29
Condensate Drain Protection.............................................30
START-UP, ADJUSTMENTS AND SAFETY CHECK......30
General ...............................................................................30
Select Setup Switch Positions ...........................................32
Prime Condensate Trap With Water.................................33
Purge Gas Lines ................................................................34
Sequence of Operation ......................................................34
Single-Stage Thermostat and Two-Stage Heating
(Adaptive Mode) .....................................................35
Two-Stage Thermostat and Two-Stage Heating .........36
Cooling Mode...............................................................36
Thermidistat Mode .......................................................37
Super-Dehumidify Mode..............................................37
Continuous Blower Mode ............................................37
Heat Pump ....................................................................38
Component Test ...........................................................38
Adjustments .......................................................................38
Set Gas Input Rate .......................................................38
Set Temperature Rise ...................................................46
Set Thermostat Heat Anticipator .................................46
Check Safety Controls.......................................................46
Check Primary Limit Control ......................................46
Check Pressure Switch.................................................46
CHECKLIST......................................................................47
NOTE:
Read the entire instruction manual before starting the
installation.
A93040
ama
CERTIFIED
®
REGISTERED
ISO 9001:2000
As an Energy Star Partner,
Carrier Corporation has deter-
mined that this product meets
the ENERGY STAR guide-
lines for energy efficiency.
Horizontal Orientation
A04168
Visit www.carrier.com
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 6a 8a
PC 101
Catalog No. 535-80145
Printed in U.S.A.
Form 58MVP-15SI
Pg 1
9-04
Replaces: None
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
Fig. 2—Dimensional Drawing Dimensions (In.) UNIT SIZE A D E 040-14* 24-1/2* 22-7/8* 23* 060-14 17-1/2 15-7/8 16 080-14 21 19-3/8 19-1/2 080-20 21 19-3/8 19-1/2 100-20 21 19-3/8 19-1/2 120-20 24-1/2 22-7/8 23 * These dimensions reflect the wider casing for the Trophy (96.6 percent AFUE) furnace. A041...
SAFETY CONSIDERATIONS FURNACE RELIABILITY HAZARD Improper installation or misapplication of furnace may re-quire excessive servicing or cause premature componentfailure.Application of this furnace should be indoors with specialattention given to vent sizing and material, gas input rate, airtemperatu...
Step 2—Upflow Applications An upflow furnace application is where furnace blower is locatedbelow combustion and controls section of furnace, and conditionedair is discharged upwards.CONDENSATE TRAP LOCATION (FACTORY-SHIPPEDORIENTATION)The condensate trap is factory installed in the blower shelf andf...