Carrier 48/50HJ004-014 - Manual
Carrier 48/50HJ004-014 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – File a claim with the; Step 2 — Provide Unit Support; Deck pans; S u p p l y; SIDE VIEW; R1 = Return from building to HVAC
- Page 3 – Step 3 — Field Fabricate Ductwork —; Secure all; Supply
- Page 6 – Step 4 — Rig and Place Unit —; Flue vent discharge must have a minimum horizontal clear-; HVAC UNIT; Fig. 4 — Supplemental Energy Recovery Section Equipment Support; UNIT SIZE
- Page 11 – Step 8 — Make Electrical Connections
- Page 13 – Pass the control wires through the hole provided in the cor-
- Page 27 – LEGEND; Fig. 7 — Power Wiring Connections; Contactor; COMP —; Compressor; IFC; National Electrical Code; TB; Terminal Block
- Page 28 – Fig. 8 — Light Commercial Thermidistat
- Page 29 – Fig. 11 — Energy Recovery Section Supply-Air Hood Assembly
- Page 30 – Fig. 13 — Light Commercial; Fig. 14 — Light Commercial Thermidistat
- Page 31 – Step 3 — Install Light Commercial Thermidistat
- Page 36 – ROOFTOP UNIT; ENERGY RECOVERY; Fig. 17 — Unit Operation Flow Diagram
- Page 38 – TROUBLESHOOTING; Use Tables 3 and 4, and Fig. 19 and 20 when troubleshooting this unit.
- Page 40 – PremierLink; COMMS —; Communications; OAT; Outdoor Air Temperature Sensor; PWR; Power; SAT; Supply Air Temperature Sensor; Fig. 20 — Typical Wiring Schematic (with PremierLinkTM Controls)
- Page 43 – COMBINED ELECTRICAL (COBRA ENERGY RECOVERY UNIT)
- Page 44 – IV. LIGHT COMMERCIAL THERMIDISTAT ACCESSORY
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 111
Catalog No. 534-80122
Printed in U.S.A.
Form 48/50HJ,62AQ-2SIS
Pg 1
9-02
Replaces: 48/50HJ,62AQ-1SIS
Book 1
1
4
4
Tab
1a 1b 6a 6b
Installation, Star t-Up,
and Service Supplement
CONTENTS
Page
SAFETY CONSIDERATIONS
. . . . . . . . . . . . . . . . . . . . . . 1
GENERAL
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-29
Step 1 — Inspect Shipment
. . . . . . . . . . . . . . . . . . . . . . 2
Step 2 — Provide Unit Support
. . . . . . . . . . . . . . . . . . . 2
• ROOF CURB
Step 3 — Field Fabricate Ductwork
. . . . . . . . . . . . . . . 3
Step 4 — Rig and Place Unit
. . . . . . . . . . . . . . . . . . . . . 6
• POSITIONING
Step 5 — Install Flue Hood (48HJ Only)
. . . . . . . . . 11
Step 6 — Install Gas Piping (48HJ Only)
. . . . . . . . . 11
Step 7 — Install External Trap for Condensate
Drain
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Step 8 — Make Electrical Connections
. . . . . . . . . . 11
• FIELD POWER SUPPLY
• FACTORY-SUPPLIED NON-FUSED
DISCONNECT
• FIELD CONTROL WIRING
• HEAT ANTICIPATOR SETTINGS
Step 9 — Assemble and Mount
Supply-Air Hood
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Step 10 — Mount the Barometric Relief Damper
. . 28
Step 11 — Set the Outdoor Cooling and
Heating Thermostats
. . . . . . . . . . . . . . . . . . . . . . . . . . 29
LIGHT COMMERCIAL THERMIDISTAT
ACCESSORY
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30-34
General
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Power
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Dehumidification Equipment and Connections
. . . 30
Step 1 — Select Light Commercial
Thermidistat Location
. . . . . . . . . . . . . . . . . . . . . . . . . 30
Step 2 — Set DIP Switches
. . . . . . . . . . . . . . . . . . . . . . . 30
Step 3 — Install Light Commercial Thermidistat
. . 31
Step 4 — Set Light Commercial Thermidistat
Configuration
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Step 5 — Conduct Light Commercial
Thermidistat Start-Up and Checkout
. . . . . . . . . . . 33
Step 6 — Make Final Settings
. . . . . . . . . . . . . . . . . . . . 34
OPERATIONAL INFORMATION
. . . . . . . . . . . . . . . . . . 34
PRE-START-UP
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
START-UP
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
SERVICE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35-37
TROUBLESHOOTING
. . . . . . . . . . . . . . . . . . . . . . . . . 38-41
ROOFTOP UNIT AND ENERGY$RECYCLER2
START-UP CHECKLIST
. . . . . . . . . . . . . . . . CL-1, CL-2
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precau-
tions in the literature, tags and labels attached to the unit, and
other safety precautions that apply.
Verify that the power source supplied to the unit matches
the voltages and amperages listed on the unit rating plate.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for all brazing operations.
GENERAL
Carrier’s factory-installed optional COBRA Energy Recov-
ery units precondition ventilation air for the rooftop unit during
winter and summer operation and recover energy from the
building exhaust air. These units are designed to satisfy the
higher ventilation requirements and other building codes while
minimizing energy costs.
Factory installation of the energy recovery section provides
the benefit of reduced field-installation time, single point pow-
er connections, and the assurance of a factory test for the com-
plete COBRA Energy Recovery unit. The energy recovery sec-
tion requires less maintenance than other energy recovery
systems and can be serviced by any qualified refrigeration
technician.
NOTE: Because of the location of the energy recovery section,
the unit nameplate has been moved to the opposite end of the
rooftop section, on the upper, right-hand part of the panel.
IMPORTANT: This is a supplemental instruction for the
48/50HJ and the 62AQ Installation, Start-Up and Service
Instructions. It is not intended to take the place of either
instruction or to be a complete piece in itself.
Disconnect gas piping from unit when leak
testing at pressure greater than
1
/
2
psig. Pres-
sures greater than
1
/
2
psig will cause gas
valve damage resulting in hazardous condi-
tion. If gas valve is subjected to pressure
greater than
1
/
2
psig, it must be replaced
before use. When pressure testing field-
supplied gas piping at pressures of
1
/
2
psig or
less, a unit connected to such piping must be
isolated by manually closing the gas valve.
Before performing service or maintenance operations on
unit, turn off main power switch to unit and install a lock-
out tag. Electrical shock could cause personal injury.
COBRA™ Energy Recovery Units
48/50HJ004-014 with 62AQ060-300
Single-Package Rooftop Units
with Energy Recovery Capability
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
2 INSTALLATION Step 1 — Inspect Shipment — File a claim with the shipping company if shipment is incomplete or damaged. SeeFig. 1 for a typical shipping packaging for a COBRA™ energyrecovery unit. Step 2 — Provide Unit Support ROOF CURB — The COBRA energy recovery unit can use afull-perimeter roof c...
3 If electric control power or gas service is to be routed through the basepan, a field-installed accessory thru-the-bottom connection must be used. Attach the accessory to thebasepan per the information in the accessory installationinstructions. Thru-the-bottom connections must be installedbefore u...
6 Step 4 — Rig and Place Unit — Keep unit upright and do not drop. Spreader bars are not required if top crating isleft on unit. Rollers may be used to move unit across a roof.Remove the bottom wooden skids that are under the unit byremoving the wooden plates that hold the bottom woodenframe to the ...