Carrier 30XW150-400 - Manual
Carrier 30XW150-400 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 3 – GENERAL; Conventions Used in This Manual —; bold; bold italics; Display Module Usage; Comfort; Fig. 1 — Touch PilotTM Display
- Page 5 – Fig. 5 — Touch PilotTM Display Menu Structure
- Page 7 – Enter Password
- Page 8 – Fig. 7 — Navigator Display Module
- Page 9 – Table 2 —; LinkTM NavigatorTM Display Menu Structure; CONTROLS; Fig. 8 — Main Base Board
- Page 10 – Table 3 — Main Base Board Inputs and Outputs
- Page 11 – Fig. 9 — Compressor Protection Module
- Page 12 – Table 5 — Compressor Protection Module Inputs and Outputs*
- Page 15 – MLV/Condenser Board —; Table 8 — Auxiliary Board Outputs
- Page 16 – CAUTION; Fig. 12 — Energy Management Module
- Page 17 – Table 9 — Energy Management Module (EMM) Inputs and Outputs; Local Equipment Network —; Table 10 — Touch PilotTM Display Port; CONNECTOR; Fig. 13 — Touch PilotTM Display Wiring
- Page 18 – Table 11 — CCN Communication Bus Wiring; Remote Alarm and Alert Relays —; Reverse; CONFIGURATION; LinkTM CCN Communication Wiring
- Page 19 – Table 13 — Touch PilotTM User Configuration (USERCONF) Table; BACKLIGHT ALWAYS ON? — This configuration is used
- Page 20 – Machine Control Methods —; Fig. 15 — Equipment Start Screen
- Page 21 – Table 14 — Touch PilotTM Start/Stop Control
- Page 22 – STAT; DISPLAY NAME; Fig. 16 — Chiller Schedule Screen
- Page 23 – Table 17 — Navigator Start/Stop Control; ITEM
- Page 24 – OPER; TIME SCHED; Table 18 — Configuring Schedules with
- Page 25 – Entering Fluid Control Option —; Table 20A — Cooling Set Point Selection
- Page 26 – Status
- Page 27 – Chilled Water Fluid Type Selection —; Fig. 18 — 4 to 20 mA Set Point Control
- Page 28 – Cooler Pump Control —
- Page 29 – MSSL
- Page 30 – LAGP
- Page 35 – SETP
- Page 36 – DRGC
- Page 37 – Fig. 20 — Return Water Temperature Control Load Profile; Load; Fig. 19 — Leaving Chilled Water Temperature Control
- Page 38 – Fig. 21 — Return Water Reset; ree; Fig. 22 — Space Temperature Reset
- Page 39 – Demand Limit —; mand Limit Type Select
- Page 41 – Ice Storage Operation —; Cooling Setpoint 2; Broadcast Configuration —; mA Demand Limit
- Page 42 – Alarm Control
- Page 43 – Daylight Saving Time Configuration —; Table 32 — Daylight Savings Time Configuration; Capacity Control Overrides —; FLUD; us; Fig. 26 — Alarm Routing Control
- Page 44 – ENBL; Table 33 — Capacity Control Overrides
- Page 46 – Table 34 — 30XW Compressor Nominal Capacity; Head Pressure Control —
- Page 47 – Water Filter; Actual start-up should be done only; ing Setpoint 1; Operating Limitations; Table 35 — Temperature Limits for Standard Units; Main Power Supply
- Page 48 – Table 36 — Evaporator and Condenser Flow Rates; ft wg; Evaporator Flow Rate
- Page 49 – gpm; Pressure Drop; NIH —
- Page 51 – Condenser Flow Rate
- Page 54 – Operating Modes —; MODE; Table 37 — 30XW Operating Modes
- Page 56 – Sensors —
- Page 57 – Fig. 38 — Thermistor and Transducer Locations
- Page 59 – Table 39B — 5K Thermistor Temperature (°C) vs Resistance; SERVICE; Fig. 40 — Dual Leaving Water Thermistor Well; Fig. 39 — 5K Thermistor
- Page 60 – Fig. 42 — Economizer Assembly; Fig. 43 — Cutaway Views of the Electronic Expansion Valve
- Page 62 – Liquid Line Service Valve; OPEN; OPEN; DISASSEMBLY; Fig. 44 — Disassembly and Assembly of EXV Motor
- Page 63 – Compressor Assembly —; Table 42 — Unit Oil Quantities; Fig. 45 — Typical 06T Compressor; Fig. 46 — Typical Oil System
- Page 64 – Cooler; QUANTITY; Fig. 47A — Suction Service Valve Locking Device,
- Page 65 – Brine Freeze Setpoint; must; Evaporator Plug Component Parts; all; Fig. 48 — Elliott Tube Plug
- Page 66 – Fig. 49 — Cooler Head Recommended; WIRING
- Page 67 – Table 47 — High-Pressure Switch Settings; SWITCH SETTING
- Page 68 – Table 48 — Troubleshooting; Alarms and Alerts —; Current Alarm; ALRM; Fig. 52 — Alarm Description
- Page 69 – Table 49 — Alarm Codes
- Page 74 – Entering; EWTO
- Page 75 – Saturated Suction Temp,; SST
- Page 80 – PUMP
- Page 81 – Table 52 — Service Maintenance Alert Codes; CODE
- Page 83 – Service Test —
- Page 84 – Table 53 — Testing Circuit A Oil Solenoid
- Page 85 – Fig. 53 — 30XW Low Voltage Control Wiring Schematic
- Page 86 – APPENDIX A — TOUCH PILOT DISPLAY TABLES; to Appendix C for range and configuration default information.
- Page 87 – APPENDIX A — TOUCH PILOTTM DISPLAY TABLES (cont)
- Page 105 – APPENDIX B — NAVIGATORTM DISPLAY TABLES; MODE — RUN STATUS
- Page 106 – APPENDIX B — NAVIGATORTM DISPLAY TABLES (cont)
- Page 107 – MODE — SERVICE TEST
- Page 108 – MODE — TEMPERATURE
- Page 109 – MODE — SET POINTS
- Page 110 – MODE — PRESSURE
- Page 111 – MODE — OUTPUTS
- Page 114 – MODE — TIMECLOCK
- Page 117 – MODE — OPERATING MODE
- Page 118 – APPENDIX C — CCN TABLES; STATUS DISPLAY TABLES
- Page 124 – CONFIGURATION TABLES
- Page 130 – SERVICE CONFIGURATION TABLES
- Page 133 – ACROSS-THE-LINE START — STANDARD CONDENSING
- Page 136 – 0XW UNIT NON-ECONOMIZED PIPING
- Page 139 – APPENDIX F —; GLOBAL TIME SCHEDULE CONFIGURATION FOR i-Vu; Fig. G — CCN Global Schedule Number
- Page 140 – INDEX
- Page 143 – Record Software Versions; (Press ENTER & ESCAPE simultaneously to obtain software versions); Record Configuration Information
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300024-01
Printed in U.S.A.
Form 30XW-1T
Pg 1
11-09
Replaces: New
Controls, Start-Up, Operation, Service
and Troubleshooting
CONTENTS
Page
SAFETY CONSIDERATIONS
. . . . . . . . . . . . . . . . . . . . . . 2
GENERAL
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Conventions Used in This Manual
. . . . . . . . . . . . . . . . 3
Display Module Usage
. . . . . . . . . . . . . . . . . . . . . . . . . . . 3
• TOUCH PILOT™ DISPLAY
• NAVIGATOR™ DISPLAY MODULE
CONTROLS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-18
General
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Main Base Board (MBB)
. . . . . . . . . . . . . . . . . . . . . . . . . . 9
Compressor Protection Module (CPM)
. . . . . . . . . . 10
Electronic Expansion Valve (EXV) Board
. . . . . . . . 13
MLV/Condenser Board
. . . . . . . . . . . . . . . . . . . . . . . . . . 15
Enable-Off-Remote Contact Switch (SW1)
. . . . . . . 16
Emergency On/Off Switch (SW2)
. . . . . . . . . . . . . . . . 16
Energy Management Module (EMM)
. . . . . . . . . . . . . 16
Local Equipment Network
. . . . . . . . . . . . . . . . . . . . . . . 17
Board Addresses
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Touch Pilot Display
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Control Module Communication
. . . . . . . . . . . . . . . . . 17
• RED LED
• GREEN LED
• YELLOW LED
Carrier Comfort Network
®
(CCN) Interface
. . . . . . . 18
Remote Alarm and Alert Relays
. . . . . . . . . . . . . . . . . 18
CONFIGURATION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 18-46
Touch Pilot Operation Configuration Tables
. . . . . 18
Machine Control Methods
. . . . . . . . . . . . . . . . . . . . . . . 20
Machine On/Off Control
. . . . . . . . . . . . . . . . . . . . . . . . . 20
• TOUCH PILOT MACHINE CONTROL
• NAVIGATOR DISPLAY MACHINE CONTROL
Entering Fluid Control Option
. . . . . . . . . . . . . . . . . . . 25
Cooling Set Point Selection
. . . . . . . . . . . . . . . . . . . . . 25
• SET POINT OCCUPANCY
Chilled Water Fluid Type Selection
. . . . . . . . . . . . . . 27
• FRESH WATER
• BRINE OR GLYCOL OPERATION
Cooler Pump Control
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
• COOLER PUMP CONTROL CONFIRGURATIONS
Machine Start Delay
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Circuit/Compressor Staging and Loading
. . . . . . . 29
• CIRCUIT/COMPRESSOR STAGING
• CIRCUIT/COMPRESSOR LOADING
Minimum Load Control
. . . . . . . . . . . . . . . . . . . . . . . . . . 29
Dual Chiller Control
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
• DUAL CHILLER CONTROL FOR PARALLEL
APPLICATIONS
• DUAL CHILLER PUMP CONTROL FOR PARALLEL
CHILLER APPLICATIONS
• DUAL CHILLER CONTROL FOR SERIES
APPLICATIONS
• DUAL CHILLER PUMP CONTROL FOR SERIES
CHILLER APPLICATIONS
Page
Ramp Loading
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Temperature Reset
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
• RETURN WATER RESET
• SPACE TEMPERATURE RESET
• 4-20 mA TEMPERATURE RESET
Demand Limit
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
• SWITCH CONTROLLED DEMAND LIMIT
• EXTERNALLY POWERED CAPACITY BASED
DEMAND LIMIT
• EXTERNALLY POWERED CURRENT BASED
DEMAND LIMIT
• CCN LOADSHED CONTROLLED DEMAND LIMIT
Ice Storage Operation
. . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Broadcast Configuration
. . . . . . . . . . . . . . . . . . . . . . . . 41
• ACTIVATE
• BROADCAST ACKNOWLEDGER
Alarm Control
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
• ALARM ROUTING CONTROL
• ALARM EQUIPMENT PRIORITY
• COMMUNICATION FAILURE RETRY TIME
• RE-ALARM TIME
• ALARM SYSTEM NAME
Daylight Saving Time Configuration
. . . . . . . . . . . . . 43
Capacity Control Overrides
. . . . . . . . . . . . . . . . . . . . . 43
Head Pressure Control
. . . . . . . . . . . . . . . . . . . . . . . . . . 46
• LOW CONDENSER FLUID TEMPERATURE HEAD
PRESSURE CONTROL OPTION
PRE-START-UP
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46,47
System Check
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
START-UP
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47-53
Actual Start-Up
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Operating Limitations
. . . . . . . . . . . . . . . . . . . . . . . . . . . 47
• TEMPERATURES
• VOLTAGE
• MINIMUM FLUID LOOP VOLUME
• FLOW RATE REQUIREMENTS
OPERATION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54-59
Sequence of Operation
. . . . . . . . . . . . . . . . . . . . . . . . . . 54
Dual Chiller Sequence of Operation
. . . . . . . . . . . . . 54
• PUMP OPERATION
Operating Modes
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Sensors
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
• THERMISTORS
• TRANSDUCERS
SERVICE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59-67
Economizer Assembly
. . . . . . . . . . . . . . . . . . . . . . . . . . 59
Electronic Expansion Valve (EXV)
. . . . . . . . . . . . . . . 59
• MAIN EXV CONTROL
• ECONOMIZER EXV CONTROL
• EXV TROUBLESHOOTING PROCEDURE
Compressor Assembly
. . . . . . . . . . . . . . . . . . . . . . . . . . 63
• COMPRESSOR OIL SYSTEM
AQUAFORCE
®
30XW150-400
Water-Cooled Liquid Chillers
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
3 GENERAL This publication contains controls, operation, start-up, ser- vice and troubleshooting information for the 30XW150-400 water-cooled liquid chillers with electronic controls. The 30XW chillers are equipped with Comfort Link™ controls and electronic expansion valves. The AquaForce ® 30XW chi...
5 User interface Group display x 8 Main menu Status GENUNIT CIRCA_AN CIRCA_D CIRCB_AN CIRCB_D CIRCC_D CIRCC_AN STATEGEN RECLAIM MODES STRTHOUR FANHOURS FREECOOL QCK_TST1 QCK_TST2 SERV_TST Setpoint Schedule OCC1PO1S OCC2PO2S Service FACTORY FACTORY2 SERVICE1 CP_UNABL UPDTHOUR UPDHRFAN MAINTCFG Maint ...
7 Setting the Time and Date — The Comfort Link™ control has a time and date function. This can be useful for diagnostics to determine when alarms occur. The control is factory config- ured for the proper date and is set for the Eastern Time Zone. The date and time zone must be checked and corrected ...