Page 2 - TABLE OF CONTENTS
TABLE OF CONTENTS The serial tag is a permanently affixed sticker onwhich is recorded vital electrical and refrigeration dataabout your Traulsen product, as well as the modeland serial number. This tag is located in the rightinterior compartment on all full size undercounter andequipment stand model...
Page 3 - II. RECEIPT INSPECTION
-2- II. RECEIPT INSPECTION All Traulsen products are factory tested for perfor-mance and are free from defects when shipped. Theutmost care has been taken in crating this product toprotect against damage in transit. All interior fittingshave been carefully secured and the legs or castersare boxed an...
Page 6 - deep
VI. d - REMOVING THE POWERPACK:1. Remove the louver panel by first removing the four(4) black plastic plugs that are located in each cornerof the powerpack louver assembly. These conceal four(4) Phillips head screws which hold the louver in place.Remove these screws as well, and set both them andthe...
Page 12 - cannot
VII. INTELA-TRAUL ® (continued) -11- Listed below are the available parameters in the order they appear, using the down arrow key on the controller. You can use either the up or down arrow keys to scroll through the options. Thermostat Set Point High Defrost Lockout 2 Thermostat Set Point Low Defros...
Page 13 - SET
VII. i - ADJUSTING THE THERMOSTAT SET POINT LOW: This parameter sets the low point of the desired cabinet temperature range. Typically, freezers will rangefrom –6 ° F to -4 ° F (-21 ° C to –20 ° C) and refrigerators will range from 32 ° F to 34 ° F ( 0 ° C to 1 ° C) for this parameter setting. This ...
Page 16 - DEFROST ICON
FREEZER SET INTELA-TRAUL ° F ° C This parameter allows a service technician to start a defrost cycle at any time. This parameterwill override any lockout settings. Follow the instructions to enter the customer access code on page 9. When the control displays Thermostat Set High, press the down arrow...
Page 17 - Setting
The defrost lockout parameters allow the customer to prevent the unit from going into a defrost cycle for two hours during a set timeframe. Customers can set up to four defrost lockout parameters. They are all programmed the same way. The parameters will be set for the time the lockout is to start. ...
Page 18 - text will display when conditions warrant.
VII. p - ADJUSTING THE ROOM TEMPERATURE OFFSET: The room temperature offset parameter allows a service technician or end user the ability to have thedisplay show a temperature that is within three degrees of the actual temperature being read by thecabinet air sensor. This allows for continuity of re...
Page 20 - FIND YOUR PROBLEM HERE
-19- VIII. TROUBLE SHOOTING GUIDE FIND YOUR PROBLEM HERE REMEDY 1. Condensing unit fails to start. a. Check if cord & plug has been disconnected. b. Check INTELA-TRAUL ® temperature setting. 2. Condensing unit operates for a. Are doors closing properly? prolonged periods or continuously. b. Dirt...
Page 21 - IX. WARRANTY INFORMATION; STANDARD DOMESTIC WARRANTY
IX. WARRANTY INFORMATION -20- STANDARD DOMESTIC WARRANTY TRAULSEN & CO., INC. warrants new equipment to the original purchaser, when installed within the United States against defective material and workmanship for one (1) year from the date of original installation. Under this warranty, TRAULSE...
Page 24 - Quality Refrigeration
Traulsen & Co., Inc. 4401 Blue Mound Road Fort Worth, TX 76106Phone: (800) 825-8220 Fax-Svce: (817) 740-6757Website: www.traulsen.com HOURS OF OPERATION: Monday thru Friday 7:30 am - 4:30 pm CST Quality Refrigeration