Page 2 - TABLE OF CONTENTS; READING THE SERIAL TAG
TABLE OF CONTENTS The serial tag is a permanently affixed label on which is recorded vital electrical and refrigeration data about your Traulsen product, as well as the model and serial number. This tag is located in the right interior compartment on all standard TU Series Full-Size Undercounter mod...
Page 3 - II. GENERAL INFORMATION; Positions
-2- II. GENERAL INFORMATION II. a-INTRODUCTION: This manual applies to the following models only: TU Series Full-Size Undercounter RefrigeratorsTU044HT, TU072HT & TU100HT TU Series Full-Size Undercounter FreezersTU044LT & TU072LT II. b-MODEL DESIGNATIONS: TU 044 HT Positions 1 2 3 Position 1...
Page 6 - The use of reclaiming equipment is required.; Disconnect the electrical power to the; Disconnect electrical.
-5- VI. CONDENSER COIL VI. a-REPLACEMENT INSTRUCTIONS: Disconnect the electrical power to the machine and follow lockout/tag out procedures. This procedure requires the use of re-frigerants, be certain the work area is well ventilat-ed. Safety goggles and gloves shall be worn since refrigerants may ...
Page 7 - Compressor models will vary with each cabinet
VIII. COMPRESSOR VIII. a-COMPRESSOR: Disconnect the electrical power to the machine and follow lockout/tag out procedures. This procedure requires the use of re- frigerants, be certain the work area is well ventilated. Safety goggles and gloves shall be worn since refrig-erants may cause burns to th...
Page 8 - a qualified technician.
-7- IX. WIRING DIAGRAM NOTE: Refer to the wiring diagram below (applies to refrigerators and freezers units) for any service work performed by a qualified technician.
Page 10 - See “SYSTEM ACCESS.”; CONTAINED
-9- X. SERVICE PROCEDURES & ADJUSTMENTS (cont’d) X. d-EVACUATING SYSTEM(cont’d): 1) Access the refrigeration system as outlined under “SYSTEM ACCESS.”2) Connect low (blue) side of gauge manifold to schrader valve on compressor process line and high (red) side of gauge manifold to schrader valve ...
Page 11 - XI. ELECTRICAL OPERATION; Certain procedures in this section re-
-10- X. PROCEDURES & ADJ. (cont’d) X. f-SYSTEM CLEAN UP/INTRODUCTION MASSIVE CONTAMINATION (cont’d):NOTE: The replacement compressor MUST NOT be installed until after system clean-up procedures have been completed.1) Remove the burned-out compressor as outlined under “COMPRESSOR”.2) Remove the c...
Page 14 - XIII. SERVICE PARTS LIST; ITEM
-13- XIII. SERVICE PARTS LIST ITEM DESCRIPTION PART NUMBER Casters All Models6” Adjustable - No Lock SER-60538-00 6” Adjustable - With Lock SER-60538-01 Leg All Models6” Leg SER-60542-00 Door All ModelsDoor - Hinges on the Left 200-60593-00 Door - Hinges on the Right 200-60593-01 Door Gasket 341-601...
Page 15 - XIV. SERVICE ASSISTANCE
-14- XIV. SERVICE ASSISTANCE XIV. a-SERVICE INFORMATION: NOTE: Before calling for service, please check the following: Is the electrical cord plugged in? Is the fuse OK or circuit breaker on? Clean condenser coil Is the power switch on? Reset microprocessor control values to factory defaults. If aft...
Page 16 - Quality Refrigeration; raulsen
HOURS OF OPERATION:Monday thru Friday 7:30 am - 4:30 pm CST Quality Refrigeration © 2009 Traulsen - All Rights Reserved T raulsen 4401 Blue Moud Road Fort Worth, TX 76106Phone (800) 825-8220 Fax (817) 740-6757Website: www.traulsen.com