Page 2 - Marley; MC; Fluid Cooler; Table of Contents
Marley / MC Fluid Cooler / Table of Contents Engineering Data Schematic 5 Support 11 Hoisting Info 12 Noise Attenuator Option 13 Freeze Protection 14 Water Quality 15 Specifications / Base Base 16 Thermal Performance 16 Performance Warranty 16 Coil 17 Design Loading 17 Construction 17 Mechanical Equ...
Page 3 - Water Distribution System; drainage at shutdown; Structure; Spherical roller bearings are rated at an L
Marley / MC Fluid Cooler / 3 ■ Water Distribution System Pressurized spray system distributes water evenly over the coil. Steel header box with PVC branch arms. Low-clog polypropylene nozzles—delivers precise distribution of water over the coil area. Marley's hot-dipped galvanized coil is tested at ...
Page 5 - Engineering Data : Schematic; SIDE ELEVATION; AIR INLET ELEVATION
Marley / MC Fluid Cooler / Engineering Data : Schematic 5 C H INSTALLED HEIGHT ACCESS ACCESS 4" INLET 4" OUTLET SIDE ELEVATION ALL MODELS AIR INLET ELEVATION MODELS 7012D081 - 7012H121 AIR INLET ELEVATION MODELS 7013F081 - 7013J121 AIR INLET ELEVATION MODELS 7014H081 - 7014K121 1249 108 1448...
Page 6 - NOTE; Use this bulletin for preliminary layouts only
Marley / MC Fluid Cooler / Engineering Data : Schematic 6 NOTE 1 Use this bulletin for preliminary layouts only . Obtain current drawings from your Marley sales representative. All table data is per cell. 2 Standard overflow is a 2" dia. F connection located on the side of the collection basin. ...
Page 11 - Engineering Data: Support; SUPPORTING STEEL; SINGLE CELL; VIEW A; Use this bulletin for preliminary layouts only.; Model
Marley / MC Fluid Cooler / Engineering Data: Support 11 Model D 7073 2640 7074 3640 7075 5320 C L AN CHOR BOLT C L AN CHOR BOLT A LENGTH CL ANCHOR BOLT CL ANCHOR BOLT HOLES FOR 3 / 8 " DIA. ANCHOR BOLTS 4 REQD 21 30 TOWER COLLECTION BASIN- AIR INLET FACE A SUPPORTING STEEL SINGLE CELL B C C NORM...
Page 12 - Engineering Data : Hoisting
Marley / MC Fluid Cooler / Engineering Data : Hoisting 12 B D C 80° MAX A 1 Hoisting operations can be dangerous and suitable safety precautions should be taken to protect personnel and the equipment being hoisted. 2 All hoisting equipment should be certified and comply with local and national safet...
Page 13 - must
Marley / MC Fluid Cooler / Engineering Data : Schematic : Attenuators 13 B A SIDE ELEVATION ALL MODELS AIR INLET ELEVATION D E C 1 Attentuators will result in an additional external resistance therefore the fan will be unable to deliver the same airflow resulting in a small reduction in performance....
Page 14 - Engineering Data: Freeze Prevention; Fluid Cooler Coil; not; Fluid Cooling Recirculating Water; “Operating Cooling; Electric Basin Heaters; CAUTION; Indoor Storage Tank
Marley / MC Fluid Cooler / Engineering Data: Freeze Prevention 14 Fluid Cooler Coil When the ambient temperature falls below 0°C, heat loss from the coil can be substantial even without recirculating water flowing over the coil. The process fluid, without an applied heat load, may be prone to freezi...
Page 15 - Engineering Data: Water Quality; Blowdown; MC Fluid Cooler; Water Treatment; MC Fluid Cooler User Manual
Marley / MC Fluid Cooler / Engineering Data: Water Quality 15 The MC Fluid Cooler can be a very effective air washer. Atmospheric dust able to pass through the relatively small louver openings will enter the recirculating water system. Increased concentrations can intensify systems maintenance by cl...
Page 16 - Water as the heat transfer fluid.; Performance Warranty:
Specifications Specification Value Marley / MC Fluid Cooler / Specifications: Base 16 1.0 Base: 1.1 Furnish and install a forced-draft, coun- terflow-type, factory assembled, film fill, industrial duty, galvanized steel, closed circuit fluid cooler. Unit shall consist of _____ cell(s), as shown on p...
Page 18 - Mechanical Equipment
Specifications Specification Value Marley / MC Fluid Cooler / Specifications: Base 18 take the above water quality and load carrying capabilities into account in the selection of their materials of manufac- ture. 7.0 Mechanical Equipment : 7.1 Fan(s) shall be forward curved cen- trifugal-type, which...
Page 19 - Hot Water Distribution System:
Specifications Specification Value Marley / MC Fluid Cooler / Specifications: Base 19 8.0 Drift Eliminators: 8.1 Drift eliminators shall be PVC, triple pass and shall limit drift losses to no more than 0.005% of the design water flow rate. 9.0 Hot Water Distribution System: 9.1 A pressured spray sys...
Page 20 - Specifications: Options; Stainless Steel Options; Replace paragraph 12.1 with the; All Stainless Fluid cooler; and customary contaminants. It is also the most expensive and dif-
Specifications Specification Value Marley / MC Fluid Cooler / Specifications: Options 20 Stainless Steel Options Stainless Steel Collection Basin: 12.1: Replace paragraph 12.1 with the following: The collection basin shall be heavy-gauge Series 300 stainless steel. Suction connections shall be equip...
Page 21 - Convenience and Safety Options; Add the following paragraph in
Specifications Specification Value Marley / MC Fluid Cooler / Specifications: Options 21 Convenience and Safety Options Top Access Platform: 11.2 Add the following paragraph in the Access section: There shall be an access platform at the top of the fluid cooler to allow access to the drift eliminato...
Page 22 - Access Door Platform:; Distribution System Access Door; Add the following paragraph in the; Control Options; Add the following paragraph in the
Specifications Specification Value Marley / MC Fluid Cooler / Specifications: Options 22 Access Door Platform: 11.4 Add the following paragraph in the Access section: There shall be an access platform at the base of the fluid cooler extending across the width of the casing. The platform shall be gal...
Page 23 - Vibration Limit Switch:; Submerged in basin water, in which zinc ions are present, copper
Specifications Specification Value Marley / MC Fluid Cooler / Specifications: Options 23 temperature at the coil and the other for set point. Process temperature input shall be obtained using a thermal sens- ing device on the process coil and wired back to the solid state temperature controller in t...
Page 24 - Marley Premium VFD System
Specifications Specification Value Marley / MC Fluid Cooler / Specifications: Options 24 in the off position for safety. The VFD system shall receive a speed reference signal from the Building Management System monitoring the tower fluid tem- perature. As an option to receiving the speed reference s...
Page 26 - • Where only a slight reduction in noise will satisfy—and the source; Miscellaneous Options; Add the following paragraph
Specifications Specification Value Marley / MC Fluid Cooler / Specifications: Options 26 ■ Sound produced by a standard MC Fluid Cooler operating in an unobstructed environment will meet all but the most restrictive noise limitations—and will react favorably to natural attenuation. Where the fluid c...
Page 27 - surrounding walls, it is possible that a proportion of the hot and
Specifications Specification Value Marley / MC Fluid Cooler / Specifications: Options 27 ■ Where a fluid cooler is installed in a building well or there are high surrounding walls, it is possible that a proportion of the hot and humid discharge air will be drawn back into the fans thus increasing th...