Page 2 - C o n t e n t s; use so that you can operate this unit safely and correctly.; OPERATOR; this manual carefully and understand the contents.
C o n t e n t s Thank you for purchasing the SMC reduced wiring system EX250 series. Please read this instruction manual carefully and understand the contents before use so that you can operate this unit safely and correctly. Please keep this manual handy for future reference. OPERATOR This instruct...
Page 3 - SAFETY; IMPORTANT MESSAGES; Gives you helpful information.; NOTE; Otherwise injury or failure can result.; Do not operate beyond specification range.; Otherwise accident caused by malfunction can result.; Before performing maintenance:; Otherwise injury can result.; Handling precautions; Use the following UL-recognized DC power supply to combine with.
2 3 SAFETY The body of unit and this manual contain the essential information for the protection ofusers and others from possible injury and property damage and to ensure correcthandling.Please check that you fully understand the definitions of the following messages( symbols ) before going on to re...
Page 4 - Product Summary; Up to 32 Inputs can be connected to the SI Unit using Input Blocks.; System configuration general
4 5 Product Summary Power supply for Output Block (for high wattage load)24VDC Connecting to bus at upper level(EtherNet/IP) Power supply for output/input and control24VDC Solenoid valve Output Block(for high wattage load) Power Block Output Block(for low wattage load) SI Unit applicable to EtherNet...
Page 5 - SI Unit Model Indication Method; Mounting/Installation; SI Unit body; Part Names; Communication protocol
6 7 SI Unit Model Indication Method Tie-rod (2 pcs.)Accessory Note1 : For wiring method, refer to subsection "Wiring" (page 12) in this manual.Note2 : For display and setting method, refer to subsection "Display/Setting" (page 15) in this manual. Dimensions ( unit : mm ) BUS BUS PWR ...
Page 6 - Layout of the Input Block; Layout of the EX9 series Output Block / Power Block; Be sure to combine with the Power Block for use.; Position of End Plate; Output Block side) at the right end of the manifold.
8 9 Mounting/Installation (continued ) Layout of the Input Block Position the Input Block on the left side of the SI Unit. Layout of the EX9 series Output Block / Power Block Position the Output Block / Power Block on the right side of the SI Unit and betweenthe SI Unit and solenoid valve or End Pla...
Page 7 - Specifications; Basic specifications
10 11 Specifications Sensor input area 1 0 I/O mapping Offset (word) Input data MSB LSB MSB LSB 15 8 7 0 0 1 Input area mapping 15 14 L : Fixed to Low Item Status Condition SP Solenoid power supply status 0 No supply voltage 1 Supply voltage OK DI Status of sensor power supply 0 Short circuit 1 Norm...
Page 8 - Wiring; Communication wiring; Tighten the lock nut on cable side by turning it; Power supply wiring; Aligning the key groove with the
12 13 Wiring 4 3 2 1 1 3 4 2 M12 12 +Rx 3 - Tx 4 - Rx 12345678 Shield RJ45 6.7 47.3 45 2000 Model No. : EX9-AC020EN-PSRJ +Tx Wiring diagram Cable core wire external color Terminal No. Pin assignment of plug connector Pin assignment of plug connector White/OrangeOrangeWhite/Green Green 8 7 6 5 4 3 2 ...
Page 9 - SI; Connecting one or two power supplies to SI Unit.; A. Two power supplies; Settings for display
14 15 Wiring ( continued ) 24VDC 24VDC Brown : 24VDC (for solenoid valves/output) White : 0V (for solenoid valves/output) Grey : Earth Blue : 24VDC (for input and control) Black : 0V (for input and control) Cable Part No. : EX500-AP -S 24VDC Brown : 24VDC (for solenoid valves/output) White : 0V (for...
Page 10 - Enable DHCP; Default settings; Switch setting
16 17 1 2 3 4 5 6 7 8 ON 1 0 IP address 192.168.0.X 1 0 1 0 1 0 1 2 0 0 1 1 1 1 3 0 0 0 0 1 1 4 0 0 0 0 1 1 Remote control * 1 X 3 2 1 14 DHCP mode * 2 SW1 Communication setting CLEAR/HOLD Manual set up of IP address * 3 SW1 5 0 1 1 1 1 1 6 - - 0 1 - - 7 - - - - 0 1 SW1 Item Communication setting Co...
Page 11 - Input Block Model Indication Method; IE; Block type; Input Block
18 19 Input Block Model Indication Method EX250 IE Block type 1 2 3 Input points : 2, M12 connector (2pcs.) Input points : 4, M12 connector (2pcs.) Input points : 4, M8 connector (4pcs.) Input Block Model indication method Part Names No. Part names Application 1 Input equipment connector Connects th...
Page 12 - Input; Correlation between input number and Input Block; Input wiring
20 21 Wiring EX250-IE3 EX250-IE1/2 EX250-IE1 (M12 connector, 5 pin, Socket) EX250-IE2 (M12 connector, 5 pin, Socket) *1) Input No.1 is connected to the pin No.2 of the input connector "0", 2 input signals can be directly input from the input connector "0". *2) NC : Not connected EX25...
Page 13 - Install the Input Block after the setting; OE 1; Power supply type; Output specification; Display; EX9 Series Output Block/Power Block; Model Indication Method
22 23 Display/Setting EX250-IE1 EX250-IE2/IE3 0 0 1 1 EX250 EX250 0 0 1 1 2 2 3 3 EX250 EX250 Display Description PWR Lights up Power supply for sensor is ON. Off Power supply for sensor is OFF. 0, 1, 2, 3 Lights up Sensor signal input corresponding to the number is ON. (Logic "1") Off Senso...
Page 14 - Power Block; Output Block
24 25 Part Names Tie-rod (2 pcs.)Accessory Tie-rod (2 pcs.)Accessory Waterproof cap(for socket)(1 pc.) Dimensions ( unit : mm ) 59.8 72.6 21 Output Block 59.8 80.3 21 PWR PWR Power Block Mounting/Installation Refer to subsection "Mounting/Installation" (page 7) in this manual. Specifications...
Page 15 - Output connector pin layout; NC; Output wiring; Pin alignment and connection drawing of the Output Cable; Correlation between output number and Output Block
26 27 Wiring ( continued ) Output connector pin layout EX9-OET1, EX9-OEP1 (M12 connector, 5 pin, Socket) Output No.1 *1 Output No.0 NC *2 1 NC *2 3 GND 5 NC *2 4 4 1 1 4 4 1 1 2 2 3 3 2 2 3 3 5 5 5 5 Output connector "0" Output connector "1" Output wiring Cable wiring Pin alignment a...
Page 16 - Ground; Pin alignment and connection drawing of the Power Supply Cable; Power Cable; Power Cable Jumper; Cable wiring
28 29 Wiring ( continued ) M12 connector, 5 pin, Reverse key 1 Power supply for output (24VDC) 2 Power supply for output (0VDC) 5 Ground ( 3 Power supply for sensor (24VDC)) * ( 4 Power supply for sensor (0V)) * 4 4 1 1 4 4 1 1 2 2 3 3 2 2 3 3 5 5 5 5 Power supply connector(Socket) Power input conne...
Page 17 - Option; Ethernet Communication Cable
30 31 Wiring ( continued ) Display Output Block PWR PWR Power Block The Power Supply Cable (for Power Supply Connector of Power Block) is a bypasscable which can be used when the Power Block is positioned next to the SI Unit. Option E X 5 0 0 - A P 0 5 0 - S How to order Cable length (L) Connector s...
Page 18 - Waterproof Cap; Check that the connected load does not exceed the; Overall system; Troubleshooting
32 33 Option ( continued ) Waterproof Cap Mounted on the unused ports of the Input Block, Output Block and Power Block.The proper use of this Waterproof Cap can achieve IP67 Enclosure. (The Waterproof Capsare delivered together with the Power Block as accessories.) 9 E X 5 0 0 - AW How to order Conn...
Page 19 - EtherNet/IP compatible communication
34 Troubleshooting ( continued ) MS LED statusNormal status : Green light ONFatal failure : Red light ON 1 The effect of noise is possible. Check the installation conditions. If the troublecannot be solved even if the installationconditions are checked, contact oursales branch. NS LED statusOffline/...