Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual CONTENTS Contents .......................................................................................................... Page Safety & Installation ......................................................
Page 3 - IMPORTANT; READ THIS SECTION FIRST!; SAFETY
Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual IMPORTANT READ THIS SECTION FIRST! 1.1 Suppliers of articles for use at work are required under section 6 of the Health and Safety at Work Act 1974 to ensure as reasonably as is practical that the article wi...
Page 4 - FRONT PANEL CONTROLS; FRONT PANEL INDICATIONS
Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual 3 . 1 Enable Controls No Controls are enabled unless the enable controls key is inserted. While the enablecontrols key is inserted the buzzer will beep every few seconds. 3 . 2 Silence Alarm Switch To silenc...
Page 5 - FRONT PANEL INDICATIONS -
Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Page 4 of 10 FRONT PANEL INDICATIONS - Continued 4 . 2 System Fault Indicator The system fault indicator will illuminate under any abnormal condition. Certain conditionsmay be diagnosed without looking insid...
Page 6 - INTERNAL INDICATORS; INTERNAL CONTROLS
Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual 6.1 The panel has an internal DIL Switch, which provides the following functions:- INTERNAL INDICATORS SOUNDERS/C FAULT 1 2 3 4 5 6 SOUNDER O/C FAULT FUSE FAULT EARTH FAULT REM. SIG DISABLED SOUNDER DISABLED...
Page 7 - TERMINAL FUNCTIONS
Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Page 6 of 10 Smoke Detection Circuits 7.1 One to six smoke detection circuits are provided and supply 28 Volts ( + 5%) for the operation of trigger devices, (smoke detectors or heat detectors). Terminals for...
Page 8 - Remote Alarm Input; TERMINAL FUNCTIONS -; ANNEXE 1
Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Page 7 of 10 Remote Alarm Input 11.1 The sounder circuits may be operated remotely via the remote alarm input. 11.2 The input is labelled (Rem AL I/P) Connection of the AUX common negative to this point will...
Page 9 - ANNEXE 2
Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Page 8 of 10 ANNEXE 2
Page 10 - ANNEXE 3
Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual ANNEXE 3 Resistor monitoring wiring. Standard bases are used. Removal of a detectorindicates fault but detectors beyond the removed one will be inoperative. Line continuity unit wiring. Diode bases are used....
Page 11 - ANNEXE 4
Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Page 10 of 10 ANNEXE 4 K1006 PCB layout - 4 & 6 zone Sigma, fuse & option resistor locations K1002 PCB layout - 1 & 2 zone Sigma, fuse & option resistor locations