Page 3 - CONTENTS
3 Warranty………………………………… Unpacking Rinnai Water Heater………… Installation Instructions…………………… Flue Requirements………………………... Dimensions………………………………… Technical Details..………………………… Features and Benefits……………………. Important Information…………………….. Operation without Remotes……………… Temperature Controls……………………....
Page 4 - UNPACKING RINNAI WATER HEATER
4 UNPACKING RINNAI WATER HEATER • After unpacking the appliance check for damage, if the heater is damaged contact your supplier immediately. Do not install a damaged appliance before checking with your supplier. • A heater accessories pack is inside the carton. One remote control is supplied with t...
Page 5 - INSTALLATION INSTRUCTIONS
5 IMPORTANT INFORMATION 1. Gas safety (Installation & Use) regulations 1998 are the ‘Rules in force’. In your own interest and that of safety, it is law that all gas appliances are installed by competent persons in accordance with the above regulations. Failure to install appliances correctly co...
Page 6 - INSTALLATION INSTRUCTIONS - POSITIONING
6 General Installation Information. Internal Installations The Rinnai Infinity 26i and the Rinnai HD50i are for internal installation in conjunction with the Rinnai Power flue system. The flue terminal clearances must be in accordance with the requirements of BS 5440. Consideration should be given t...
Page 7 - INSTALLATION INSTRUCTIONS - VENTILATION
7 General Information. The unit must be installed by a competent, authorised person. It is the installer’s responsibility to ensure that the unit has been installed to all current requirements. The Rinnai Infinity 26i and HD50i are room sealed appliances. Ventilation requirements of BS 5440 allow ro...
Page 8 - INSTALLATION INSTRUCTIONS - CONNECTIONS
8 INSTALLATION INSTRUCTIONS - CONNECTIONS Water Supply. Where the water supply pressure exceeds 12 bar, an approved pressure reducing device is required at the inlet of the appliance. To achieve the rated flow a minimum water supply pressure of 1.4 bar is required at the appliance inlet. The unit wi...
Page 9 - FLUE REQUIREMENTS - POSITIONING
9 Dimension Terminal Position Distance A Directly below an opening, air brick, opening windows, etc. 300mm B Above an opening, air brick , opening window, etc. 300mm C Horizontally to an opening, air brick , opening window, etc. 300mm D Below gutters, soil pipes or drain pipes. 75mm E Below eaves. 2...
Page 10 - FLUE REQUIREMENTS - INSTALLING
10 FLUE REQUIREMENTS - INSTALLING General. The flue must be installed in accordance with: Manufacturers Installation Instructions British Standards including BS5440 Gas Safety (Installation and Use) Regulations IGE/UP/10 Part1 Edition 2. Building Regulation J The flue must be installed by a competen...
Page 11 - DIMENSIONS
Page 12 - TECHNICAL DETAILS
12 TECHNICAL DETAILS * Factory Setting ** Minimum operation flow based on temperature setpoint and inlet conditions. Infinity Model Infinity 26i HD50i Units Installation Internal Internal Nat Gas Press Low 1.9 1.9 mbar Nat Gas Press High 8.5 8.5 mbar LPG Press Low 2.3 2.3 mbar LPG Press High 10.8 10...
Page 13 - FEATURES AND BENEFITS
13 Congratulations on purchasing the Technologically Advanced, Temperature Controlled, Rinnai Hot Water System. • The Rinnai Infinity 26i and HD50i NEVER RUN OUT of hot water. As long as electricity, water, and gas supplies are connected, hot water is available when hot water taps are open. • Built ...
Page 14 - IMPORTANT INFORMATION; DO
14 Excessively hot water is dangerous, especially for young children and the infirm. The water heater allows you to control the temperature of your hot water to safe levels. Do stay with children whenever they are in the bathroom. Do take them out of the bathroom if you need to answer the phone or d...
Page 16 - Turn On by opening the hot water tap; OPERATION WITHOUT REMOTES
16 Rinnai Infinity and HD products have no pilot light and when installed without Temperature Controllers, the appliance will operate automatically as soon as a hot water tap is opened. The burner ignites with electronic ignition and the flame extinguishes as soon as water flowing through the applia...
Page 17 - TEMPERATURE CONTROLS - GENERAL
17 TEMPERATURE CONTROLS - GENERAL When deciding on the best position for the temperature controls, the following points should be taken into account. • Fit the controls out of reach of children (suggested height from the floor 1.5m.) • Avoid positions where the controllers will become hot. Do not fi...
Page 18 - TEMPERATURE CONTROLS - INSTALLATION
18 TEMPERATURE CONTROLS - INSTALLATION Universal Temperature Controller MC-91-1A 1. Determine the most suitable position for the temperature controller. 2. Drill 3 holes in the wall as shown in fig 1, one for the cable and two for the securing screws. Ensure holes are drilled deep enough. Fit wall p...
Page 20 - TEMPERATURE CONTROLS
20 TEMPERATURE CONTROLS The purpose of a Temperature Controller is to enable the user to have complete control over the hot water supply. Used correctly, the hot water unit will supply hot water at the temperature selected, even when the water flow is varied, or when more than one tap is used. Adjus...
Page 21 - TEMPERATURE CONTROLS - OPERATING
21 Remote temperature controllers are a feature that provides control over the water temperature. Rinnai Infinity and HD water heaters can be operated with 1, 2, 3, 4 or no temperature controllers. The Universal controller MC-91-1A comes as standard with all Infinity water heaters, and are optional ...
Page 22 - Using 1 Universal Temperature Controller.
22 TEMPERATURE CONTROLS - OPERATING Using 1 Universal Temperature Controller. Press the On/Off button on the temperature controller. The ON indicator will glow on the Temperature Controller. This indicates that the heater is ready to supply hot water when a tap is opened. Adjusting Temperature Simpl...
Page 23 - Using 2 or more Universal Temperature Controllers.
23 Using 2 or more Universal Temperature Controllers. Switching the system ON. Using hot water. Bathroom temperatures should be no more than 50 0 C. The hot water system and all controllers can be switched ON and OFF from any controller by pressing the On/Off button as shown. When the system is turn...
Page 25 - Using High Temperature Display Controllers.
25 Using High Temperature Display Controllers. You will need to program the Master controller if you want to display and use temperatures over 50 0 C. Programming only needs to be done on Master universal controllers; other universal controllers will not allow this, and Deluxe Kitchen Controllers ar...
Page 26 - Note; To turn off your hot water system.
26 Note To turn off your hot water system. Additional safety features. During normal operation the system is left on. To turn the system off simply press the On/Off button on any temperature controller (where fitted). This will shut the water heater down completely including the temperature controll...
Page 27 - TEMPERATURE CONTROLS - INFORMATION
27 TEMPERATURE CONTROLS - INFORMATION Do not push the On/Off button on the Master controller after transferring priority of temperature selection to a Secondary controller as the system will shut down. Do Not Turn OFF the Master Controller Temperature priority can not be switched to another controll...
Page 28 - TESTING
28 TESTING 1. Purge gas, hot water and cold water supply lines before making the final connection of the water heater. Swarf in either the gas or water supplies may cause damage. 2. Turn on gas and cold water supplies. 3. Test for water leaks and gas escapes near the unit. 4. Isolate gas and electri...
Page 29 - GAS PRESSURE SETTING; Contact Rinnai UK before
29 GAS PRESSURE SETTING The working gas pressure on the water heater is electronically controlled and factory set. Under normal circumstances it does not require adjustment during installation. Perform this procedure only if the unit is not operating correctly and all other possible causes for incor...
Page 31 - DIP SWITCH SETTING
31 DIP SWITCH SETTING Dip Switch Positions Explained OFF ON SW1 1 - Computer Programming LEGEND: 2 - Temperature Black Section indicates 3 - Temperature position of dip switch. 4 - Temperature 5 - Temperature OFF ON OFF ON 6 - Temperature 7 - Combustion OFF ON 8 - Combustion OFF ON SW2 1 - Gas Type ...
Page 33 - ERROR MESSAGES
33 ERROR MESSAGES Rinnai water heaters have the ability to check their own operation continuously. If a fault occurs, an error code will flash on the Digital Display if you have temperature controllers installed. This assists with diagnosing the fault, and may enable you to overcome a problem withou...
Page 34 - Troubleshooting without controllers; Installations with circulation pumps
34 ERROR MESSAGES Troubleshooting without controllers If you have not installed temperature controllers and experience the following symptoms, please carry out the suggestions below. If symptoms continue, please contact Rinnai for advice. NOTE: Faults caused by insufficient gas/water supply or gas/w...
Page 35 - RESTARTING THE RINNAI WATER HEATER; Hot water system incorporating secondary recirculation
35 RESTARTING THE RINNAI WATER HEATER Following a power cut the heaters should be restarted in this manner. Standard system. Single or multiple water heaters without remote controllers. The heaters will automatically reset without any user involvement. Single or multiple water heaters with remote co...
Page 36 - WIRING DIAGRAM
Page 37 - DIAGNOSTIC POINTS
37 DIAGNOSTIC POINTS Diagnostic Points- To be read in conjunction with the wiring diagram.
Page 38 - SPECIFICATION
38 SPECIFICATION Model ………………………………………………..…....…………..... Infinity 26i and HD50i Installation …………………………………………...………...……... Internal location only Fuel …………………………………………………..….……………... Natural Gas or LPG * Control ………………………………………………….……………...…….….….. Modulating Input …………………………………………………...…..……….………...
Page 39 - SERVICE CONTACT; Rinnai
39 SERVICE CONTACT Rinnai Rinnai UK LTD. 9 Christleton Court Manor Park Runcorn Cheshire WA7 1ST Tel. 01928 531870 Fax. 01928 531880 E-mail. [email protected] Web. www.rinnaiuk.com REU-V2632FFU 28/1/5 rev3
Page 40 - COMMISSIONING CHECK LIST