Page 2 - TABLE OF CONTENTS
2 TABLE OF CONTENTS Unit Features & Benefits ..............................................................................3-4 Model Identification Options ..........................................................................5-6 General Data RSNA-B Series ......................................
Page 4 - Features Below Correspond to Photos on Page 3
4 UNIT FEATURES & BENEFITS—RSNA-B SERIES 1. All models feature Copeland ® Scroll ® compressors for maxi- mum efficiency and quiet operation. 2. Louvered condenser compartment for protecting the coil against yard hazards and/or weather extremes. 3. One-piece top with a drip lip to help keep water...
Page 5 - MODEL IDENTIFICATION—RSNA-B SERIES
R S N A — B 036 J K 010 X X Factory Installed Options (See Next Page) Heating Capacity (Factory Installed)000 = No Resistance Heat005 = 05 KW Resistance Heat (018-030)010 = 10 KW Resistance Heat (024-048)015 = 15 KW Resistance Heat (036-048) Drive PackageK = Direct Drive Electrical DesignationJ = 20...
Page 6 - OPTIONS—RSNA-B SERIES; FACTORY INSTALLED OPTION CODES; Instructions for Factory Installed Option(s) Selection; After a basic rooftop model is selected, choose a
6 OPTIONS—RSNA-B SERIES Option Code Side Flow AA No Option AK x FACTORY INSTALLED OPTION CODES Example: RSNA-B036JK000 XX (where XX is factory installed option) Example: No Options RSNA-B036JK000 Example: Options with Sideflow RSNA-B036JK000AK Note: Factory installed economizer is not available on t...
Page 7 - GENERAL DATA—RSNA-B SERIES
7 GENERAL DATA—RSNA-B SERIES Model RSNA-B Series B024JK B030JK B036CK B036JK Cooling Performance 1 Gross Cooling Capacity Btu [kW] 24,800 [7.27] 31,200 [9.14] 37,400 [10.96] 37,400 [10.96] EER/SEER 2 11.8/13 11.1/13 11.7/13 11.7/13 Nominal CFM/ARI Rated CFM [L/s] 800/800 [378/378] 1000/1000 [472/472...
Page 11 - SYSTEMS PERFORMANCE—RSNA-B SERIES; GROSS SYSTEMS PERFORMANCE DATA—RSNA-B024; GROSS SYSTEMS PERFORMANCE DATA—RSNA-B030
11 SYSTEMS PERFORMANCE—RSNA-B SERIES GROSS SYSTEMS PERFORMANCE DATA—RSNA-B024 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C] CFM [L/s] 880 [415] 800 [378] 680 [321] 880 [415] 800 [378] 680 [321] 880 [415] 800 [378] 680 [321] DR ➀ .21 .20 .18 .21 .20 .18 .21 ....
Page 12 - GROSS SYSTEMS PERFORMANCE DATA—RSNA-B036; GROSS SYSTEMS PERFORMANCE DATA—RSNA-B042
12 SYSTEMS PERFORMANCE—RSNA-B SERIES GROSS SYSTEMS PERFORMANCE DATA—RSNA-B036 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C] CFM [L/s] 1320 [623] 1200 [566] 1020 [481] 1320 [623] 1200 [566] 1020 [481] 1320 [623] 1200 [566] 1020 [481] DR ➀ .21 .20 .17 .21 .20 ...
Page 13 - GROSS SYSTEMS PERFORMANCE DATA—RSNA-B048; GROSS SYSTEMS PERFORMANCE DATA—RSNA-B060
GROSS SYSTEMS PERFORMANCE DATA—RSNA-B048 ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C] CFM [L/s] 1760 [831] 1600 [755] 1360 [642] 1760 [831] 1600 [755] 1360 [642] 1760 [831] 1600 [755] 1360 [642] DR ➀ .20 .19 .17 .20 .19 .17 .20 .19 .17 OU T DOOR DRY BU L B ...
Page 14 - INDOOR AIRFLO; AIRFLOW PERFORMANCE—RSNA-B SERIES
INDOOR AIRFLO W PERFORMANCE—208 V O L T S External Static Pressure—Inches W .C. [kPa] CFM [L/s] Air Deliver y/RPM/W atts—208 V olts Side Discharge—W et Coil Nominal Cooling Capacity Tons [kW] Motor Speed from Factor y Motor Speed RPM 730 775 820 865 905 940 0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0....
Page 16 - ELECTRICAL DATA – RSNA-B SERIES; Copper Wire Size —AWG; ELECTRICAL DATA—RSNA-B SERIES
ELECTRICAL DATA – RSNA-B SERIES Minimum Circuit Ampacity Minimum Overcurrent Protection Device Size 16/16 20/20 Maximum Overcurrent Protection Device Size 25/25 Compressor Motor No. 1 Volts 208/230 Phase 1 HP 2 1/6 RPM 3450 Amps (RLA) 10.4/10.4 Amps (LRA) Unit Information Unit OperatingVoltage Range...
Page 17 - ELECTRIC HEATER KITS—RSNA-B SERIES
B024JK No Heat — — 16/16 20/25 20/25 A10J 24.57/32.76 34.6/40.0 45/52 45/45 60/60 A05J 12.28/16.38 17.3/20.0 24/27 25/25 30/30 44/50 45/50 — — — — — 16/16 20/25 20/25 22/25 25/25 — — — RXQJ- Heater Kit Nominal kW Heater KBTU/Hr @ 208/240 V Heater Amp. @ 208/240 V Unit Min. Ckt. Ampacity @ 208/240 V ...
Page 18 - TOP VIEW; UNIT DIMENSIONS—RSNA-B SERIES
30% 2% 21% 2% 29% 2% 20% 2% CORNER WEIGHTS % OF TOTAL UNIT WEIGHT THERMOSTAT WIRING ENTRANCE ELECTRICAL POWER ENTRANCE BLOWER/EVAPORATORACCESS PANEL SIDE SUPPLYDUCT OPENING SIDE RETURNDUCT OPENING TOP COVER UNIT DIMENSIONSPACKAGEAIR CONDITIONERS OUTDOOR FAN GRILLEAND COMPRESSOR ACCESS CONTROLACCESS ...
Page 20 - TYPICAL INSTALLATIONS
Page 21 - SUPPLY AIR/PERFORMANCE; ACCESSORY EQUIPMENT; SUPPLY/RETURN DIFFUSER; ACCESSORIES
COMMON SUPPLY/RETURNCONCENTRIC AIR DIFFUSER SUPPLY AIR/PERFORMANCE NOTE: The location of the combination supply and return diffuser should not exceed 10 feet [3.05 m] above the floor level for units @ 1000 CFM[472 L/s] or less and 12 [3.66 m] to 14 feet [4.27 m] above the floor levelfor units with C...
Page 23 - ECONOMIZERS
[ ] Designates Metric Conversions RXRE-CAA30 (3 Position) Provided with enthalpy control, andmixed air sensor. Settings include fully open, fully closed and adjustablemid point. RXRD-CAM10 (Fully Modulating) Provided with enthalpy control, mixed air sensor and minimum position poten-tiometer for pro...
Page 28 - ROOFCURB ADAPTERS
[ ] Designates Metric Conversions PACKAGE AIR CONDITIONERS &GAS/ELECTRIC PACKAGE UNITSROOFCURB INSTALLATION (Full Perimeter) OLD MODEL OLD CURB MODEL NEW MODEL TO OLD MODELROOFCURB ADAPTER NEW MODEL PACKAGE ONLY 1 CABINET SIZE— ALL MODELS RSNA-B SMALL CABINET 20 SERIES RXPX-BACCA20RXRX-BACDB20RX...
Page 31 - WIRING SCHEMATICS—RSNA-B SERIES
Page 37 - NOTES
Page 40 - GENERAL TERMS OF LIMITED WARRANTY
Before proceeding with installation, referto installation instructions packagedwith each model, as well as complyingwith all Federal, State, Provincial, andLocal codes, regulations, and practices. RHEEMAIR CONDITIONINGDIVISION 5600 Old Greenwood Road, Fort Smith, Arkansas 72908 “In keeping with its ...