Page 4 - Coil frost prevention; MS MICROPROCESSOR CONTROL
4 1-1. COOL ( ) OPERATION 2. Indoor fan speed control Indoor fan operates continuously at the set speed by FAN SPEED CONTROL button regardless of the thermostat's OFF- ON. In AUTO the fan speed is as follows. 1. Thermostat control Thermostat turns ON or OFF by the difference between room temperature...
Page 7 - Indoor fan speed control; In AUTO the fan speed is as follows.; Thermostat control; The indoor fan maintains the actual speed of the moment.; Low outside temperature operation; door fan rotation does not stop.; MSZ, MSY MICROPROCESSOR CONTROL
7 2-1. COOL ( ) OPERATION 2. Indoor fan speed control Indoor fan operates continuously at the set speed by FAN SPEED CONTROL button regardless of the thermostat's OFF- ON. In AUTO the fan speed is as follows. 1. Thermostat control Thermostat turns ON or OFF by the difference between room temperature...
Page 9 - Gradation of fan speed in initial
9 (2) Cold air prevention control MSZ-A09/12/15/17 MSZ-FD MSZ-FE MSZ-D MSZ-GE When the compressor is not operating, ( ) if the temperature of room temperature thermistor is less than 66°F (19°C), the fan stops. ( ) if the temperature of room temperature thermistor is 66°F (19°C) or more and ( ) if t...
Page 10 - Time chart of defrosting in HEAT mode (reverse type)
10 set position set speed set position set speed Indoor fan Compressor normal Outdoor fan R.V. coil (21S4) OFF (COOL) OFF Maximum frequency horizontal Horizontal vane Very Low (temperature of indoor coil thermistor > 64 °F) 30 seconds 30 seconds 30 seconds 40 seconds 5 seconds 5 seconds 40 second...
Page 11 - MUZ
11 (2) Mode change In case of the following conditions, the operation mode is changed. COOL mode changes to HEAT mode when 15 minutes have passed with the room temperature 2 - 4°F (1 - 2°C) below the set temperature. HEAT mode changes to COOL mode when 15 minutes have passed with the room temperatur...
Page 12 - Function of main parts
12 <SWING operation>In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”.According to the temperature of indoor coil thermistor RT12 at starting of this operation, next downward blow time is decided. Then when the downward blow has been fi...
Page 17 - -8. OPERATIONAL FREQUENCY CONTROL OF OUTDOOR UNIT
17 2-8. OPERATIONAL FREQUENCY CONTROL OF OUTDOOR UNIT 1. Outline The operational frequency is as following: First, the target operational frequency is set based on the difference between the room temperature and the set tempera- ture. Second, the target operational frequency is regulated by discharg...
Page 19 - Other models; (a) Reference value of target discharge temperature; Applied model
19 (3) Control data F E DC B A Ta rget discharge temperature Operational frequency of the compressor 30 50 70 90 110 130 23 38 53 69 84 99 (Hz) (Hz) ( Other models ) ( MUZ-FE18 MUZ-GE24 MUY-GE24 ) (a) Reference value of target discharge temperature COOL / HEAT ( MUZ ) °F/°C Applied model A B C D E F...
Page 20 - is repeated as shown in the graph until the breaker is turned OFF.; NOTE; heat control is turned ON.; Power; or more
20 2. Pre-heat control ON condition (1) Pre-heat control is turned ON for 15 or 30 minutes after the breaker is turned ON. (2) 30 min. after the unit is stopped, pre-heat control is turned ON for 15 or 30 minutes and turned OFF for 30 minutes. This is repeated as shown in the graph until the breaker...
Page 21 - MXZ MICROPROCESSOR CONTROL
21 3-1. INVERTER SYSTEM CONTROL POWER SUPPLY NOISE FILTER CIRCUIT RESISTOR RELAY SMOOTHING CAPACITOR CURRENT TRANSFORMER COMPRESSOR REACTOR P W V U N IPM PFC U W MS 3~ V + 3-1-1. Inverter main power supply circuit Function of main parts NAME FUNCTION INTELLIGENT POWER MODULE (IPM) It supplies 3-phas...
Page 27 - and
27 (1) LEV opening correction by discharge temperature The target discharge temperature is determined according to frequency zone and number of operation unit of the com-pressor. <Correction> COOL DRY HEAT Discharge temperature ● 2 ● 2 ● Each correction • (Each gas pipe temperature thermistor ...
Page 31 - -5. DISCHARGE TEMPERATURE PROTECTION CONTROL
31 3-4. HEAT DEFROSTING CONTROL (1) Starting conditions of defrosting When the following conditions a) ~ c) are satisfied, the defrosting starts. a) The defrost thermistor reads 26.6°F or less. b) The cumulative operation time of the compressor has reached any of the set values (defrost interval: 40...
Page 32 - COOL
32 COOL Fan speed changes so that the condensing temperature stays within the target range. Fan speed Revolution per minutes (rpm) MXZ-2B20NA- 1 MXZ-3BMXZ-4B 1 100 100 2 150 150 3 200 200 4 250 250 5 300 300 6 350 350 7 400 400 8 450 450 9 500 500 10 550 550 11 600 600 12 650 650 13 700 700 14 750 7...
Page 33 - Compressor uses 50 W when pre-heat control is turned ON.; Coil frost prevention; ON
33 1. Pre-heat control is turned ON for 15 or 30 minutes, after the breaker is turned ON. 2. 30 minutes after the unit is stopped, pre-heat control is turned ON for 15 or 30 minutes and turned OFF for 30 minutes. This is repeated as shown in the graph until the breaker is turned OFF. When the defros...
Page 35 - MFZ MICROPROCESSOR CONTROL; speed becomes Very Low. In AUTO the fan speed is as follows.
35 4 MFZ MICROPROCESSOR CONTROL 3. Coil frost prevention Refer to MXZ MICROPROCESSOR CONTROL, COOL OPERATION (3-8.2.). 2. Indoor fan speed control Indoor fan operates continuously at the set speed by FAN SPEED CONTROL button regardless of the thermostat's OFF-ON. In AUTO the fan speed is as follows....
Page 36 - Fan speed
36 1. Thermostat control Refer to MXZ MICROPROCESSOR CONTROL, HEAT OPERATION (3-10.1.). 4-3. HEAT ( ) OPERATION 2. Indoor fan speed control (1) Indoor fan operates at the set speed by FAN SPEED CONTROL button. In Auto the fan speed is as follows. 3. High pressure protection In HEAT operation, the in...
Page 37 - -4. AUTO CHANGE OVER ··· AUTO MODE OPERATION; In case of the following conditions, the operation mode is changed.
37 4-5. INDOOR FAN MOTOR CONTROL (1) Rotational frequency feedback control The indoor fan motor is equipped with a rotational frequency sensor, and outputs signal to the microprocessor to feed-back the rotational frequency. Comparing the current rotational frequency with the target rotational freque...
Page 38 - (1) Cold air prevention in HEAT operation; Indoor fan motor (Lower) in COOL OPERATION; operation is performed in table D~H for more cooling.
38 4-6. AUTO VANE OPERATION Horizontal vane (1) Cold air prevention in HEAT operation When any of the following conditions occurs in HEAT operation, the vane angle changes to Vertical position automati-cally to prevent cold air blowing on users. Compressor is not operating. Defrosting is performed. ...