Page 2 - DATA U4; Controllers; Group
CNTR-2 CONTROLLER (Feb. 2009) CON TROLLER DATA U4 ™ I/O Controllers Group V 1 24 All of the local remote controllers feature liquid crystal LED displays and are easy to operate. This is a middle-scaled air conditioning management system, in which up to 2,000 indoor units can be centrally controlled ...
Page 3 - Interface
CONTROLLER (Feb. 2009) CNTR-3 CONTROLLER DATA U4 1-1. Function table of controllers LMAP03U: LonWorks ® Interface Controls up to 50 Groups/ 50 Indoor,Details refer to its description. PAC-YG31CDA: BACnet ® Interface Software Controls up to 500 Groups/ 500 Indoor, For details, see its description. (S...
Page 4 - Local remote controller; DATA U3; Functions; System example; LOCAL REMOTE CONTROLLER
CNTR-4 CONTROLLER (Feb. 2009) CON TROLLER DATA U4 2-1. Deluxe MA remote controller [PAR-21MAA] 2. Local remote controller DATA U3 Functions PAR-21MAA ON/OFF FILTER CHECK OPERATION CLEAR TEST TEMP. MENU BACK DAY MONITOR/SET CLOCK ON/OFF ERROR CODE AFTER TIMER TIME SUN MON TUE WED THU FRI SAT ONOFF Hr...
Page 6 - Function to limit; Power supply; CENTRALIZED CONTROLLER AG-150A
CNTR-6 CONTROLLER (Feb. 2009) CON TROLLER DATA U4 ON/OFF Run and stop operation for a single group Operation mode switching Switches between Cool / Dry / Auto / Fan / Heat.Operation modes vary depending on the air conditioner unit.Auto mode is the CITY MULTI R2- and WR2-Series only. Temperature sett...
Page 7 - External dimension
CONTROLLER (Feb. 2009) CNTR-7 CONTROLLER DATA U4 ON/OFF Run and stop operation for a single group Operation mode switching Switches between Cool / Dry / Fan / Heat / Auto. Operation modes vary depending on the air conditioner unit. Auto mode is only for the CITY MULTI ® R2- and WR2-Series. Temperatu...
Page 8 - ting up a LOSSNAY and central controller system, connect a; ABS
CNTR-8 CONTROLLER (Feb. 2009) CON TROLLER DATA U4 2-5. LOSSNAY M-NET remote controller [PZ-52SF] LOSSNAY remote controller LOSSNAY unit LOSSNAY unit LOSSNAY remote controller LOSSNAY remote controller LOSSNAY unit LOSSNAY unit LOSSNAY unit LOSSNAY unit LOSSNAY unit LOSSNAY unit LOSSNAY remote contro...
Page 9 - Auto only supported for the CITY MULTI
CONTROLLER (Feb. 2009) CNTR-9 CONTROLLER DATA U4 Auto only supported for the CITY MULTI R2- and WR2-Series. ® ( ) For PDFY/PEFY/PFFY by setting Dip SW 7-1 to ON and limits to HIGH fan speed only. 3. sYsTEM CONTROLLER 3-1. System group controller [PAC-SF44SRA]
Page 10 - LOSSNAY
CNTR-10 CONTROLLER (Feb. 2009) CON TROLLER DATA U4 3. sYsTEM CONTROLLER Unit:mm[in.] System remote controller LOSSNAY remote controller LOSSNAY remote controller LOSSNAY LOSSNAY LOSSNAY MA remote controller MA remote controller (Front view) (Side view) (Rear view) 5- 1 / 8 3 / 32 23 / 32 1- 13 / 16 ...
Page 11 - System remote controller; CONTROLLER
CONTROLLER (Feb. 2009) CNTR-11 CONTROLLER DATA U4 3. System remote controller DATA U3 CONTROLLER Cntr- 12 3-2. Schedule timer [PAC-YT34STA] ON/OFF MONITOR WEEKLY SET COLLECTIVE PATTERN Sun Mon Tue Wed Thu F r i Sat OPERATION GROUP CHECK SET TEMP. ON/OFF MODE TEMP. ON TIMER OFF PROH. PERMIT ON OFF Th...
Page 12 - System
CNTR-12 CONTROLLER (Feb. 2009) CON TROLLER DATA U4 System group controller Schedule timer PAR-F27MEA-US PAR-21MAA PAC-YT51CRA LOSSNAY (Front view) (Side view) (Rear view) External dimension System example Unit:mm[in.] 5- 1 / 8 3 / 32 23 / 32 1- 13 / 16 3- 9 / 32 4- 23 / 32 3 / 4 130[ ] 2[ ] 18.5 [ ]...
Page 13 - Interlock operation with external system possible.
CONTROLLER (Feb. 2009) CNTR-13 CONTROLLER DATA U4 3. System remote controller DATA U3 CONTROLLER Cntr- 14 3-3. ON/OFF remote controller [PAC-YT40ANRA] 16 groups/50 units can be controlled. Up to 16 groups/50 units can be operated with one ON/OFF remote controller. A general-purpose interface is avai...
Page 14 - CENTRALIZED; remote
CNTR-14 CONTROLLER (Feb. 2009) CON TROLLER DATA U4 PZ-52SF LOSSNAY PAC-YT51CRB PAR-F27MEA-US PAR-21MAA (Front view) (Side view) (Rear view) 4- 23 / 32 5- 1 / 8 3- 9 / 32 1- 13 / 16 3 / 4 23 / 32 External dimension System example Unit:mm[in.] 130[ ] 120 [ ] 18.1 [ ] 19 [ ] 46[ ] 83. 5 [ ] CENTRALIZED...
Page 15 - Installation plate; Auto mode is only for the CITY MULTI
CONTROLLER (Feb. 2009) CNTR-15 CONTROLLER DATA U4 3. sYsTEM CONTROLLER 1 2 6 3 GROUP SELECT MODE TEST RUN AIR DIRECTION FAN SPEED ON/OFF 0 8 7 5 4 CLOCK/ PATTERN PROHIBITION TIMER MODE TEMP. REMOTE G-50A CENTRAL CONTROLLER 9 INS. DEL. SCREEN BACK ENTER VENTILATION RESET ON/OFF Operation mode switchi...
Page 16 - MITSUBIS; Compatible
CNTR-16 CONTROLLER (Feb. 2009) CON TROLLER DATA U4 Central controller G-50A LAN Power supply unit PAC-SC50KUA M-MET 12V DC ME remote controller M-NET M-NET ME remote controller LOSSNAY M-NET remote controller ME remote controller LOSSNAY unit UP POWER RA TING MODE L WEIGHT SERIA L No. 2.11kg POWER S...
Page 17 - Field supplied power; CAUTION
CONTROLLER (Feb. 2009) CNTR-17 CONTROLLER DATA U4 3. sYsTEM CONTROLLER 3-4-1-2-2. TB3 and DC 12V, 0.2A G-50A can also receive power supply from TB3 connector of the R410A or R407C, R22 Outdoor unit. Yet, Outdoor unit down will lead down to G-50A too. The kind of connection is possible but not recomm...
Page 18 - manually turned back on.
CNTR-18 CONTROLLER (Feb. 2009) CON TROLLER DATA U4 Cntr- 19 3. System remote controller DATA U3 CONTROLLER 3-4-2-1. External signal input function External signal input requires the external I/O adapter (Model: PAC-YG10HA-E) sold separately. (1) External input Emergency stop/normal, run/stop and pro...
Page 19 - The connection cable can be e; Peel off the label; ft
CONTROLLER (Feb. 2009) CNTR-19 CONTROLLER DATA U4 3. System remote controller DATA U3 CONTROLLER Cntr- 20 (A) For level signal Red Orange CN2 X1 Run/stop or Emergency stop Power supply( 1) (DC12V or DC24V) This unit X1 This unit 32- 3 / 4 ft CN2 Power supply( 1) (DC12V or DC24V) X1 X2 Y1 Y2 Red Oran...
Page 20 - NOTE; NET transmission line.
CNTR-20 CONTROLLER (Feb. 2009) CON TROLLER DATA U4 Cntr- 21 3. System remote controller DATA U3 CONTROLLER POWER GND 12VDC 9 1 CN2 5 1 CN1 RS232C Ethernet A B S M-NET NOTE Perform the LAN wiring before installation, and wire up to the body by the same method as wiring the M- NET transmission line. W...
Page 22 - Measurement status monitor (temperature
CNTR-22 CONTROLLER (Feb. 2009) CON TROLLER DATA U4 Operation (DIDO Controller) Measurement status monitor (temperature sensor/humidity sensor /measurement meter) Trend Graph (temperature/humidity) 3. sYsTEM CONTROLLER
Page 23 - Mounting with L-shape metal
CONTROLLER (Feb. 2009) CNTR-23 CONTROLLER DATA U4 3. sYsTEM CONTROLLER 3-5. Central controller [GB-50A] Operation mode switching Switches between Cool / Dry / Auto / Fan / Heat. (Group of LOSSNAY unit : automatic ventilation/ vent - heat interchange/ normal ventilation) Operation modes vary dependin...
Page 24 - control
CNTR-24 CONTROLLER (Feb. 2009) CON TROLLER DATA U4 3. sYsTEM CONTROLLER Central controller GB-50A LAN Power supply unit PAC-SC51KUA or PAC-SC50KUA M-MET ME remote controller M-NET M-NET ME remote controller LOSSNAY remote controller ME remote controller LOSSNAY unit 3-5-1. Power supply to GB-50A GB-...
Page 25 - system consisting multiple Outdoor units.; Indoor/outdoor transmission line; control use needs following considerations.; Outdoor unit will cause GB-50A to shut down the whole system.
CONTROLLER (Feb. 2009) CNTR-25 CONTROLLER DATA U4 3. sYsTEM CONTROLLER 3-5-1-2-2. TB3 of Outdoor unit. GB-50A can also receive power supply from TB3 connector of the R410A or R407C, R22 Outdoor unit. However, if the Outdoor unit shuts down, G-50A will also automatically shuts down. Therefore, this c...
Page 27 - conditioners, the “Malfunction” signal will be shown.
CONTROLLER (Feb. 2009) CNTR-27 CONTROLLER DATA U4 Cntr- 27 3. System remote controller DATA U3 CONTROLLER (A) For level signal Red Orange CN2 X1 Run/stop or Emergency stop Power supply( 1) (DC12V or DC24V) This unit 9 5 6 7 8 X1 9 5 6 7 8 This unit CN2 Power supply( 1) (DC12V or DC24V) X1 X2 Y1 Y2 R...
Page 31 - Fan speed setting (including Auto) varies depending on the model.; Microsoft
CONTROLLER (Feb. 2009) CNTR-31 CONTROLLER DATA U4 Operation mode switching Temperature setting Fan speed setting Models with 5 air flow speed settings: Hi/Mid-2/Mid-1/Low, Auto Models with 4 air flow speed settings: Hi/Mid/Low, Auto Models with 2 air flow speed settings: Hi/Low Fan speed setting (in...
Page 34 - Lead wire; connecting; Use
CNTR-34 CONTROLLER (Feb. 2009) CON TROLLER DATA U4 3. sYsTEM CONTROLLER (A) For level signal (4) Recommended circuit exampl e The contact relay , DC power source, extension cable, etc., must be prepared separately at the site. The connection cable can be extended up to 10m (32 ft). (Use a 0.3mm 2 (A...
Page 35 - LAN connector of this device.; LAN
CONTROLLER (Feb. 2009) CNTR-35 CONTROLLER DATA U4 3. sYsTEM CONTROLLER When using the LAN connection function, connect the LAN cable to the LAN connector of this device. Procure the LAN cable at the site, and use 100 BASE-TX Straight cable. For a description of the IP address setting method, refer t...
Page 36 - Malfunction List
CNTR-36 CONTROLLER (Feb. 2009) CON TROLLER DATA U4 3-6-4. Browser screens of AG-150A Condition List (Overview) Condition List (Block) Malfunction List Weekly Schedule Malfunction Log Operation °F 3. sYsTEM CONTROLLER
Page 39 - Models with 2 air flow speed settings: Hi/Low; United States and other countries.
CONTROLLER (Feb. 2009) CNTR-39 CONTROLLER DATA U4 3. sYsTEM CONTROLLER 3-7. Central controller [GB-24A] Operation mode switching Switches between Cool / Dry / Auto / Fan / Heat / Setback. (Group of LOSSNAY unit : automatic ventilation/ vent - heat interchange/ normal ventilation) *Operation modes va...
Page 40 - MA: MA remote controller
CNTR-40 CONTROLLER (Feb. 2009) CON TROLLER DATA U4 3. sYsTEM CONTROLLER Centralized controller GB-24A LAN Power supply unit PAC-SC51(50)KUA M-NET ME remote controller M-NET M-NET ME remote Indoor unit Indoor unit Indoor unit Indoor unit Mr.Slim Outdoor unit Outdoor unit Outdoor unit controller LOSSN...
Page 41 - Centralized controller
CONTROLLER (Feb. 2009) CNTR-41 CONTROLLER DATA U4 3. sYsTEM CONTROLLER Fig. 3 GB-24A, TB3 scheme. Centralized controller GB-24A Indoor/outdoor transmission line TB3 ME remote cotroller CN41 (3) Power supply of M-NET from outdoor unit connector TB3. GB-24A can also receive power supply from R410A/R40...
Page 43 - following specifications.
CONTROLLER (Feb. 2009) CNTR-43 CONTROLLER DATA U4 3. sYsTEM CONTROLLER 4). Recommended circuit example CN 2 Lead wire Details of each terminal No.1 Green Common (External ground) No.2 Black ON/OFF No.3 Brown Malfunction/normal (2). External signal output function 1). Exter nal output When one or mor...
Page 45 - Malfunction Log
CONTROLLER (Feb. 2009) CNTR-45 CONTROLLER DATA U4 3. sYsTEM CONTROLLER 3-7-4. Browser screens of GB-24A Operation (without Setback) Condition List (Overview) Operation (with Setback) Malfunction Log Malfunction List Condition List (Block)
Page 46 - Measurement status monitor (temperature
CNTR-46 CONTROLLER (Feb. 2009) CON TROLLER DATA U4 3. sYsTEM CONTROLLER Operation (DIDO Controller) Measurement status monitor (temperature sensor/humidity sensor /measurement meter) Trend Graph (temperature/humidity) Weekly Schedule
Page 47 - Table 3-8-1 Equivalent power consumption of controllers
CONTROLLER (Feb. 2009) CNTR-47 CONTROLLER DATA U4 3. sYsTEM CONTROLLER PAC-SC50KUA supplies DC powers of 24V and 12V at TB2 and TB3 respectively; the former is for central control transmission use and the latter is for G-50A operation and LAN function use. 3-8-1. When using PAC-SC50KUA as the power ...
Page 48 - -3 Connectable number of system controller when 1 G-50A is used.; -4 Connectable number of system controller when 1 GB-50A is used.; down on the whole system.
CNTR-48 CONTROLLER (Feb. 2009) CON TROLLER DATA U4 Cntr- 31 3. System remote controller DATA U3 CONTROLLER 3- 8 -2. When supply power to 1 G-50A, the PAC-SC50KUA can supply power to other system controllers as follows. 0123456789 101112 0 1 2 3 4 5 - V V V V V V V V V V V V V V V V V V V V V V V V V...
Page 49 - Cable fixture
CONTROLLER (Feb. 2009) CNTR-49 CONTROLLER DATA U4 3. sYsTEM CONTROLLER 9- 7 / 16 8- 27 / 32 10- 7 / 16 5- 29 / 32 2- 11 / 32 TB3 TB2 Cable fixture Cable fixture TB1 External dimension Unit:mm[in.] 265[ ] 150[ ] 59.2[ ] 240 [ ] 225 [ ]
Page 50 - Table 3-9-1 Equivalent power consumption of controllers
CNTR-50 CONTROLLER (Feb. 2009) CON TROLLER DATA U4 3. sYsTEM CONTROLLER PAC-SC51KUA supplies DC power of 22-30V and 24V at TB2 and TB3 respectively; the former is for centralized transmission use and the latter is for AG-150A operation and LAN function use. 3-9-1. When using PAC-SC51KUA as the power...
Page 51 - Total number of
CONTROLLER (Feb. 2009) CNTR-51 CONTROLLER DATA U4 3-9-2. When supply power to 1 AG-150A, the PAC-SC51KUA can supply power to other system controllers as follows. 0123456789 10 0 1 2 3 4 5 V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V V : Connectable V : Connectable Total number of Syst...
Page 53 - The TG-2000A can realize the following functions
CONTROLLER (Feb. 2009) CNTR-53 CONTROLLER DATA U4 3. sYsTEM CONTROLLER 3-10. Integrated centralized control software [TG-2000A] Main features of TG-2000A 1 Up to 2000 indoor units (40 AG-150, G-50A, GB-24 or GB-50A units) can be operated and monitored simultaneously . 2 The air-conditioner layout ca...
Page 54 - List of integral software functions; general equipment
CNTR-54 CONTROLLER (Feb. 2009) CON TROLLER DATA U4 3. sYsTEM CONTROLLER 3-10-2. List of TG-2000A functions 1: Compatible with TG-2000A Ver. 4.10 or later, G-50A Ver. 2.51 or later. 2: Compatible with TG-2000A Ver. 4.30 or later, G-50A Ver. 2.51 or later. 3: Compatible with TG-2000A Ver. 4.60 or late...
Page 56 - Item; auxiliary heater may not be handled by these units.
CNTR-56 CONTROLLER (Feb. 2009) CON TROLLER DATA U4 3-10-4. Requirements (system recommendations) We recommend the following software and hardware when using this application (TG-2000A). 3-10-5. Compatible Units The TG-2000A has two main functions: centralized control of air conditioners and cost acc...
Page 57 - Outdoor unit system; PC for central control; Necessary parts for the system
CONTROLLER (Feb. 2009) CNTR-57 CONTROLLER DATA U4 Cntr- 37 3. System remote controller DATA U3 CONTROLLER 3-11. Electric amount count software [PAC-YG11CDA] MITSUBISHI ELECTRIC offers charging function for the air conditioner system. Detailed output of every indoor on electricity consumption of air-...
Page 58 - Lighting
CNTR-58 CONTROLLER (Feb. 2009) CON TROLLER DATA U4 CONTROLLER Cntr- 38 3-12. PLC software for general equipment [PAC-YG21CDA (SW-PLC-GE)] MITSUBISHI ELECTRIC's Air Conditioner control system can combine control of general equipment like lighting, air condition- ers from others, and so on. Functions ...
Page 60 - If the quantity of G-50A exceeds 11 sets, one set of PLC is required; or; Demand
CNTR-60 CONTROLLER (Feb. 2009) CON TROLLER DATA U4 3-14. PLC software for demand input [PAC-YG41CDA] MITSUBISHI ELECTRIC's CITY MUL TI ® has its intelligent wa y to carry out peak-cut control while maximizing the air condition- ing effect. - Energy saving setting - Monitoring of current energy savin...
Page 62 - and M-NET Adapter LMAP03U
CNTR-62 CONTROLLER (Feb. 2009) CON TROLLER DATA U4 3-15. LonWorks ® interface [LMAP03U] LMAP LMAP Building management system Protocol : L ON W ORKS ® Lighting Elevator System example CITY MULTI ® can easily combine into a Building Management System (BMS) via the L ON W ORKS ® and M-NET adapter LMAP0...
Page 63 - ACK Service is recommended for the network service.; Environment specification
CONTROLLER (Feb. 2009) CNTR-63 CONTROLLER DATA U4 Cntr- 43 3. System remote controller DATA U3 CONTROLLER <LMAP03U Network Variables> Request prohibit local Setpoint Request prohibit local Mode Request prohibit (note3,4) (note3,4) (note3,4) (note3, 4) (note3, 4) (note3, 4) local On/Off Prohibi...
Page 64 - External Dimensions; Usage Restrictions; monitor operating
CNTR-64 CONTROLLER (Feb. 2009) CON TROLLER DATA U4 3. sYsTEM CONTROLLER The DIDO controller is used in combination with a(n) AG-150A/G(B)-50A/GB-24A to operate general-purpose equipment, as well as to and error status. It is equipped with two sets of standard terminal s (Channels 1 and 2), and four ...
Page 66 - centralized control line from the R410
CNTR-66 CONTROLLER (Feb. 2009) CON TROLLER DATA U4 3-16-1. Specifications 3-16-1-1. Device Specifications * This figure omits the power supply line and only shows the transmission line. *1: The DIDO controller can be connected to G(B)-50A with Ver.3.20 or later. *2: The DIDO controller can be connec...
Page 67 - • CPEV; * CPEV: PE insulated PVC jacketed shielded communication cable
CONTROLLER (Feb. 2009) CNTR-67 CONTROLLER DATA U4 3. sYsTEM CONTROLLER 3-16-1. Specifications 3-16-1-2. Parts Purchased Separately Prepare the following parts to install this device. [Parts to be Purchased Separately] [Commercially available parts] Required Part Specification Unit fixing screws M4 s...
Page 68 - • Operation input ON/OFF
CNTR-68 CONTROLLER (Feb. 2009) CON TROLLER DATA U4 3. sYsTEM CONTROLLER 3-16-3. Interlock control The DIDO controller (PAC-YG66DCA) has an interlock control function, which enables operation or set temperature change on the M-NET devices such as indoor units and also enables signal output to the con...
Page 73 - CENTRALIZED CONTROLLER
CONTROLLER (Feb. 2009) CNTR-73 CONTROLLER DATA U4 3-17-2. Interlock control AI controller (PAC-YG63MCA) has an interlock control function, which enables operation or set temperature change on the M-NET devices such as indoor units. Interlock control covers the units connected to the AI controller wi...
Page 78 - OK
CNTR-78 CONTROLLER (Feb. 2009) CON TROLLER DATA U4 4. sYsTEM COMpONENT OK NO 1) SW4-4: OFF (Compressor ON/OFF, Low sound mode) 2) When SW4-4 on one outdoor unit in one refrigerant circuit system is set to ON (4 levels of on-DEMAND) (*3) 3) When SW4-4 on the two outdoor units in one refrigerant circu...
Page 79 - Lamp power source
CONTROLLER (Feb. 2009) CNTR-79 CONTROLLER DATA U4 4. sYsTEM COMpONENT CN51 XY L 1 L 2 Lamp power source Distant control board Relay circuit Adapter *1 Outdoor unit control board Preparations in the field L1 : Outdoor unit error display lamp L2 : Compressor operation lamp (compressor running state) X...
Page 81 - Input
CONTROLLER (Feb. 2009) CNTR-81 CONTROLLER DATA U4 Input Output ON/OFF (Pulse) input specification Caution: 3.The electric strength between accessible parts and control circuit should have 2750V or more. 1.Wiring should be covered by insulation tube with supplementary insulation.2.Use relays or switc...