Page 3 - Safety Precautions; Symbols and Terms; : Indicates a part which must be grounded.; WARNING
1 Safety Precautions • Before instralling this unit,make sure you read all the “Safety Precautions”. • This manual describes the installation of LM ADAPTER and wiring to the outdoor unit. • Please read the installation manual of air-conditioning units with regards to the installation method of air-c...
Page 4 - CAUTION
2 CAUTION Do not install the unit where combustible gas may leak. If the gas leaks and accumulates around the unit, an explosion may result. Do not use in any special environment. Using in any place exposed to oil(including machine oil), steam and sulfuric gas may deteriorate the performances signif...
Page 5 - Verify that the following parts are appended to the product.; -2 Environment Specifications
3 1. Parts Include 2. Specifications Verify that the following parts are appended to the product. 2-2 Environment Specifications 2-1 External View Name Shape Quantity Main Unit Binding band 1 3 Installation manual 1 · The external interface file (XIF) is necessary for the product. Upon verifying the...
Page 6 - assure sufficeint intervals.; network can be found in “ FTT-10A Free Topology Transceiver; Functions; -5 List of LM ADAPTER Functions
4 2-3 Connected Air Conditioning Equipment 2-4 L ON W ORKS ® Network Specifications * The proper communication is not obtainable when communication intervals exceed its performance, assure sufficeint intervals. * ACK Service is recommended for the network service. * Detailed specifications for the L...
Page 7 - Prepare the following prior to installing the unit.; -1 Locally Procured Parts
3. Installation <Notes> Prepare the following prior to installing the unit. Read and understand the contents of Chapter 1 “Safety Precautions ” before performing the installation. 3-1 Locally Procured Parts 5 Contents Power wireand ground wire M-NETtransmission wire Screw To install the main b...
Page 8 - -2 Installation Method; • LM ADAPTER is not waterproof type.
6 3-2 Installation Method • LM ADAPTER is not waterproof type. • LM ADAPTER shall be installed in a control panel box (steel : thickness 1 mm (3/64 in) or more). Please prepare the control panel box in consideration with installation space as shown in the Fig. (Install in an area capable of withstan...
Page 10 - -4 Electrical Wiring
8 P.B. L.B. TB1 PE L1L2 Main Power Switch 3A Unit Body Unit Body CN31 3 1 3 AC250V2A T ZNR2 F 1 T2 CN33 DSA1 ZNR1 Unit Body 7 3 1 5 CN71 SWL(Service Switch) (Service LEDL LED) 1 3 4 3 2 1 56 CN45 T1 CN65 2 1 CN21 3 1 CN32 1234 CNL12 CN605 5 4 3 2 1 LED402(5VM) LED502(3150RST) 6 4 3 2 1 M-NETPower Su...
Page 11 - equipment connected with L; Explanation of function switch
9 Note: Function switch setting of LM ADAPTER is different according to the management item of the equipment connected with L ON W ORKS ® . Carefully set the system. SW1-1 ON OFF Function switchof local prohibit local prohibit effective local prohibit invalidity ON OFF LOSSNAY is operatedfrom L ON W...
Page 12 - -1 If not used together with system controller.
10 4. System Settings <Notes> This chapter only describes the system settings of this product.For the installation work and electrical work, refer to the last chapter “ 3. Installation ”. Read and understand the contents of Chapter 1 “Safety Precautions ” before performing the installation. 4-...
Page 13 - -2 If used together with system controller.
11 4-2 If used together with system controller. SW1-2 [ON] SW2-1 [ON] Centralized controller (system controller) M-NET transmission line (Centralized control line) M-NET address 201 to 250 [factory setting 247] (* Setting of position 100 not required.) (Note:1) When connecting LOSSNAY, register the ...
Page 14 - -3 Initialization Settings of L; Network; subject to additional constraints, particularly on distance.
12 4-3 Initialization Settings of L ON W ORKS ® Network (1) System Specifications • Up to 64 FTT-10/FTT-10A transceivers are allowed per network segment. • LPT-10 transceivers may be used on network segments with FTT-10/FTT-10A transceivers, but are subject to additional constraints, particularly on...
Page 15 - Confirming Operation; -1 Flow of Onsite Adjustments
13 5. Confirming Operation 5-1 Flow of Onsite Adjustments …… …… …… Test run by unit and local remote controller Refer to 5-4 (1) Test run by LM ADAPTER Refer to 5-4 (2) Test run from the L ON W ORKS ® network Refer to 5-4 (3) There are the following two methods to perform a test run from the L ON W ...
Page 16 - nv1n Request ON/OFF command input
14 5-4 Test Run Perform the test run according to the test procedure of the test run check list. (1) Test run of units by local remote controller * Confirm that all units are running normally. (2) Test-operation of the indoor unit from LM ADAPTER Turn on SW1-9 of LM ADAPTER. Finally turn OFF SW1-9, ...
Page 21 - Test run check sheet; Appendix : Test run check sheet
19 Test run check sheet ON OFF ON OFF Operation from L ON W ORKS ® network Confirmation of operating status Error Operation m o d e Set temperature ON OFF Operation m o d e Set temperature temperature Intake 01020304050607080910111213141516171819202122232425262728293031323334353637383940414243444546...