Page 2 - TABLE OF CONTENTS; Please read and understand these; stone; INTRODUCTION; WARNING; GENERAL INFORMATION
2 TABLE OF CONTENTS Packaging..........................................Page. 2Introduction.......................................Page. 2General.Information...........................Page. 2Massachusetts.and.New.York....Requirements.................................Page. 4Cold.Climate.Insulation.........
Page 3 - Table 1
3 Note: Installation and repair should be done by a qualified service person. The appliance should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bed- ding material, etcetera. It is imperati...
Page 4 - Flame appearance will diminish 4% per; Table 4; Figure 1; Table 2; REQUIREMENTS FOR THE COMMON-; Figure 2
4 NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE. These.appliances.must.be.isolated.from.the. gas.supply.piping.system.(by.closing.their. individual.manual.shut-off.valve).during.any. pressure. testing. of. the. gas. supply. piping. system. at. test. pressures. equal. to. or. less than .1/2.psi...
Page 5 - LOCATION; Figure 3; Figure 3 - Typical Installation; COLD CLIMATE INSULATION; Cross Corner
NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE. 5 LOCATION In. selecting. the. location,. the. aesthetic. and. functional. use. of. the. appliance. are. primary. concerns.. However,. vent. system. routing. to. the.exterior.and.access.to.the.fuel.supply.are. also.important... Due to high tempera...
Page 6 - Figure 6 - Side Elevation View; Termination Heights For Vents; Vertical Vent Termination Clearances; These instructions should be used as a; Vertical Vent Termination Clearances; Figure 4; Horizontal Vent Termination Clearances; Figure 6; Minimum; Figure 4 - Multiple Terminations
6 NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE. 3" (76 mm) Termination Kit Combustible Projection greater than 2-1/2 inches in length Horizontal Vent Termination Clearances Combustible Projection 2-1/2 inches or less in length 24" (610 mm) Ventilated Or Unventilated Soffit Figure 6 - ...
Page 7 - ExTERIOR HORIZONTAL VENT TERMINATION CLEARANCE REQUIREMENTS; Minimum Clearances; condensation; Figure 7; NOTE: Local Codes Or Regulations May Require
NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE. 7 ExTERIOR HORIZONTAL VENT TERMINATION CLEARANCE REQUIREMENTS Minimum Clearances Canadian Installation * US Installation ** A. =. Clearance. above. grade,. veranda,. porch,. deck. or.balcony. 12.inches.(30.cm).* 12.inches.(30.cm).** B. =. Clearanc...
Page 8 - Shelf Height; Figure 8; MINIMUM CLEARANCES TO COMBUSTIBLES; When the; Figure 9; Top Vent - with 2 Feet Vertical Vent and One 90 Degree Elbow
8 NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE. *Note: 3 in. (75 mm) above any horizontal/inclined vent component. **Note: See Page 9, Step 1 for clearance requirements to the nailing flange located at each side of the unit and any screw heads adjacent to it. The.appliance.should.be.mounted.o...
Page 9 - Figure; DO NOT; DETAILED INSTALLATION STEPS; Page 9
NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE. 9 Left Side Front Corner of Fireplace Shown (Right Side Requirements the Same) Unit Being Secured By Its Nailing Flanges To The Framing Note: The nailing flanges, combustible members and screw heads located in areas directly adjacent to the nailin...
Page 10 - Fireplace Dimensions; FIREPLACE AND FRAMING SPECIFICATIONS; Framing Dimensions
10 NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE. E A B D Top View Front View 5-3/32 (129) Right Side View 14-1/8 8-1/2” (216) 5-1/4” (133) (359) 26-15/32 (672) C 25-29/32 (658) 25-1/2 (648) 7 2-1/2 (64) (178) 19-5/8 (498) Gas Inlet (This Side Only) Electrical Inlet 8-3/8 (213) F G H J Firepla...
Page 11 - Back wall of chase/enclosure; Schedule 40 Pipe; Table 6; Proper Sizing of Gas Line; Right Side; Step 2. ROUTING GAS LINE
NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE. 11 C Back wall of chase/enclosure (including any finishing materials) D A B Model No. A B C D LSM40-2 in. 50-5/8 83-5/8 59-1/8 41-7/8 mm 1286 2124 1502 1064 LSM45-2 in. 56-3/4 89-7/8 63-1/2 44-7/8 mm 1441 2283 1613 1140 Figure 13 - Corner Framing ...
Page 12 - VENT RESTRICTOR INSTALLATION; Step 3. INSTALL THE VENT SYSTEM; See Approved Vent Components on; These fireplaces must be vented directly; Note: The restrictor is included within the
12 NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE. Figure 15 Figure 16 AIR INLET BAFFLE GRATE VENT RESTRICTOR INSTALLATION RESTRICTOR APPLIANCE VENT OUTLET Install.the.restrictor.as.shown.from inside.the.unit,.in.the.inner.fireplace.collar. When.vertically.terminating.the.vent.system.above the....
Page 13 - Figure 17 and Figures 25 through 27 on; Secure VentTM; Figure 5 on Page 6; Effective Vent Length; Model; Table 7
NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE. 13 Termination Flashing And Storm Collar Firestop/Spacer SV8 6/12/24/36/48 Vent Sections 40' Max (12.2 M) 6' Min (1.8 M) 1" (25 mm) Minimum Clearance to Combustibles VERTICAL TERMINATION SYSTEMS (ROOF) See. Figure 17 and Figures 25 through 27 ...
Page 15 - Figure 22 - Roof Framing; on; Swivel Joint; Storm
NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE. 15 Framing Dimensions for Roof Inches (millimeters) Pitch C D 0/12 13 in. (330 mm) 13 in. (330 mm) 6/12 13 in. (330 mm) 15-1/2 in. (394 mm) 12/12 13 in. (330 mm) 20-1/2 in. (541 mm) C D Figure 22 - Roof Framing Figure 24 G. . Continue installation...
Page 16 - Table B; Ceiling; Table A; Maximum; VERTICAL VENT FIGURES/TABLES; • Secure VentTM (rigid vent pipe) is shown; A Vent Restrictor, as shown in Figure 15 on Page
16 NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE. Figure 27 - Top Vent - THREE ELBOWS V H1 H V1 Ceiling Firestop/Spacer (SV8BF) Wall Firestop/Spacer (SV8HF) Table B H + H1 Maximum V Minimum feet (meter) feet (meter) 10 (3.1) 2.5 (0.762) 15 (4.65) 3.5 (1.06) 20 (6.2) 4.5 (1.37) H + H1 = 20 feet...
Page 17 - TYPICAL HORIZONTAL VENT INSTALLATION; Support the vertical portion of the venting system; to
NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE. 17 Vertical Rise SV8E90 Elbow Horizontal / Inclined Run SV8HTS Termination Shown Firestop/Spacer SV8 L6/12/24/36/48 Vent Sections Support Bracket Spacing Every 3 ft (914 mm) SV8HTS Termination Shown Support Brackets Building Support Framing Ceilin...
Page 18 - For wall thicknesses greater than; Venting Connection and Exterior Wall Recessing; See Figure 12 on Page 10 for Minimum; Distance to Base of Appliance; Step B; IMPORTANT: The vent termination is hot
18 NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE. Horizontal terminations have been designed to perform in a wide range of weather condi- tions. Our terminations meet or exceed industry standards.When selecting the locations of your horizontal terminations, do not place the termina- tion where...
Page 19 - Table 8; range of exterior wall thicknesses.; zontal vent run is needed, then; HORIZONTAL VENT FIGURES/TABLES; • Secure VentTM
NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE. 19 H V Wall Firestop/Spacer (SV8HF) Ceiling Firestop/Spacer (SV8BF) Table C H Maximum V Minimum feet (meter) feet (meter) 3.5 (1.07) 2.5 (0.762) 6.5 (1.98) 3.5 (1.07) 8.5 (2.6) 4.5 (1.37) 10.5 (3.2) 5.5 (1.68) 12.5 (3.8) 6.5 (1.98) 14.5 (4.4) 7.5 ...
Page 21 - CAUTION; Figures 35 and; the current CSA C22-1 Canadian; Verify proper operation after servicing.; ELECTRONIC; See Figure 36 for detailed; drawing of junction box /; see Figure 12 on Page
21 Step 4. FIELD WIRING CAUTION Ground supply lead must be con- nected to the wire attached to the green ground screw located on the outlet box. See Figures 35 and 36 . Failure to do so will result in a potential safety hazard. The appli- ance must be electrically grounded in accordance with local c...
Page 22 - Gas; WIRING
22 NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE. Step 5. REMOVE GLASS DOOR FRAME Remove.glass.door.assembly...See.Removing Glass Enclosure Panels.on. Page 26 . Step 6. CONNECTING GAS LINE All.codes.require.a.shut-off.valve.mounted.in. the.supply.line..The.orientation.of.the.shut-off. valve. s...
Page 23 - Never use an open flame to; Millivolt Appliance Checkout
NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE. 23 WARNING Never use an open flame to check for leaks. Turn.on.gas.supply.and.test.for.gas.leaks.using.a. gas.leak.test.solution.(also.referred.to.as.bubble. leak.solution).. Note: Using a soapy water solution is an effective leak test solution bu...
Page 24 - Excessive use of embers may result in sooting or poor flame.; Place logs 2 and 3; Mixture Of Volcanic Stone And Vermiculite
24 NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE. Step 1. . Install. the. ceramic. panels. per. the. instructions. provided. in. kit. (reference form #750182M). Step 2. . Place. a. mixture. of. volcanic. stone. and. vermiculite. around. the. burner.as.shown.in. Figure 43 . Step 3. ..Separate.t...
Page 27 - adjust the flame height as desired, by sliding; Main Burner Factory Air Shutter; Burner Air Shutter Adjustment Procedure
NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE. 27 Figure 52 - Burner Flame Appearance (Rustic Oak Logs Shown) LSM45-2 Figure 51 - Burner Flame Appearance (Birch Logs Shown) LSM40-2 To.adjust.the.flame,.rotate.the.air.shutter.toward. the. back. or. toward. the. front. of. the. fireplace.. Posit...
Page 28 - FINISHING REQUIREMENTS; door track and the surface of the finish material.
28 Glass Door Assembly Fireplace Finish Combustible Or Non-Combustible Material Bottom Of Fireplace 1/8 Inch Minimum Door Track Finish Combustible Or Non-Combustible Material Front Face Of Fireplace Floor Panel Figure 55 Figure 54 Non-combustible.materials,.such.as.surrounds.and.other.appliance.trim...
Page 29 - LENNOx HEARTH PRODUCTS; La chimenea caliente; Un foyer chaud peut causer; ADVERTENCIA; ATTACHING SAFETY IN OPERATION WARNINGS; Hot Fireplace Will Cause; LENNOx HEARTH PRODUCTS; AVERTISSEMENT
29 NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE. La chimenea caliente cau- sará quemaduras gravesNunca permita que los niños toquen el vidrio ni otras partes de la chimenea ADVERTENCIA Un foyer chaud peut causer de graves brûluresNe laissez jamais un enfant toucher à la vitre ou à toutes autr...
Page 31 - this installation assumes responsibility for this conversion.; assume les responsabilités liées à la conversion.; Burner Assembly
NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE. 31 In Canada: THE CONVERSION SHALL BE CAR- RIED OUT IN ACCORDANCE WITH THE REQUIREMENTS OF THE PROVINCIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE RE- QUIREMENTS OF THE CAN/CSA-B149.1 INSTALLATION CODE. LA CONVERSION DEVRA êTRE E...
Page 32 - VERIFY THE PROPER ORIFICE SIZE BE-; Millivolt & Electronic Gas Valves; Millivolt & Electronic Pilot Assemblies; Table 9
32 NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE. 1508 Elm Hill Pike, Suite 108 • Nashville, TN 37210 Figure 59 Step 8. .Reassemble.the.remaining.components. by. reversing. the. procedures. outlined. in. the. preceding.steps... Step 9. . Attach. the. conversion. label. provided. in.the.convers...