Page 2 - MGE; Galaxy; TM; 000 : Specification guide
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec. E - 2 Contents 1 - UPS definition .................................................................................
Page 4 - - Operating principle; - Parallel operation with redundancy
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec. E - 4 2 - Operating principle The double-conversion UPS (also called on-line) shall operate as defined below. 2....
Page 5 - - Sizing and general characteristics
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec. E - 5 2.6 - UPS maintenance For maintenance purposes, all electronic components shall be accessible from the fro...
Page 6 - - Limitation of harmonics upstream of the UPS; - Electrical characteristics
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec. E - 6 3.5 - Limitation of harmonics upstream of the UPS The UPS system shall not draw a level of harmonic curren...
Page 10 - - Environment conditions
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec. E - 10 7 - Environment conditions 7.1 - UPS (not including battery) 7.1.1 - Operation The UPS, not including the...
Page 11 - - Battery management
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec. E - 11 9 - Battery management As the life of the batteries is very sensitive to operating conditions, the batter...
Page 12 - 0 - User interface and communication
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec. E - 12 10 - User interface and communication 10.1 - User interface UPS operation shall be facilitated by a user ...
Page 13 - 1 - Maintainability
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec. E - 13 10.1.3 - Status indications with mimic panel Indication of status conditions shall be distinct of the gra...
Page 14 - 2 - Standards and tests; 3 - Test procedures and quality system
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec. E - 14 12 - Standards and tests 12.1 - Standards All equipment shall be designed and built in accordance with ac...
Page 15 - - Functional components - organisation of supplier services; 6 - Installation services
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec. E - 15 14 - Services 14.1 - Maintenance The supplier shall propose contracts covering four levels of maintenance...
Page 16 - 7 - Electrical diagram
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec. E - 16 17 - Electrical diagram Battery Normal AC input UPS 1 Bypass AC input Load Battery Normal AC input UPS 2 ...
Page 18 - Appendix. Comparison table
MGE TM Galaxy TM 6000 : Specification guide Parallel UPS, three-phase, 250 to 3000 kVA* * Power rating for an N+1 redundant configuration APC By Schneider Electric Edition - 03/2009 Spec. E - 18 Appendix. Comparison table Type of UPS Total rated power (kVA) at PF 0.8 kVA Manufacturer Range of produc...