Page 2 - Engineering Data - HRV; inches; inches
2 MODEL 94-EXCHANGER-MD - Includes 24 volt motorized damper 21.25" (540 mm) STALE AIR TO OUTSIDE FRESH AIR FROM OUTSIDE STALE AIR FROM INSIDE FRESH AIR TO INSIDE 15" (380 mm) 18.75" (475 mm) * A l l D u c t C o n n e c t i o n s 6 " ( 1 5 0 m m ) F I LT E R B A L A N C I N G C O L L ...
Page 3 - Motorized Damper Assembly
3 Motorized Damper Assembly Mount the damper motor by aligning the four (4) holes inthe mounting plate to the four holes on the unit’s top plate.This will automatically align the damper motor couplingwith the damper shaft. Align the damper in the fully closed position. Using a 1/8”Allen key to tight...
Page 4 - Installation; Clearances and Requirements; WARNING; CAUTION
4 Location Selection The HRV must be located in a heated space where it willbe possible to conveniently service the unit. Typically theHRV would be located in the mechanical room or an areaclose to the outside wall where the weather hoods will bemounted. If a basement area is not convenient or does ...
Page 5 - Not into a garage, workshop or other unheated space; • Should be located upstream (if there are prevailing; * Local code may require greater distances.; Weather Hood Clearances; Weatherhood Installation
5 • At least 3' (1 m) away from the corner of the building* • At least 3’ away from gas meter, electric meter or awalkway where fog or ice could create a hazard* • Not into a garage, workshop or other unheated space When installing the weather hood, its outside perimetermust be sealed with exterior ...
Page 6 - the; DRAIN HOSE PLUMBING; HARD PIPE PLUMBING; Air Duct Design and Installation
6 Stale Air Exhaust System The stale air exhaust system is accomplished by the posi-tive pressure created in the furnace ducting. The air handler blower must be running for this system to beeffective. Drain Connection (HRV Only) During a defrost cycle, the HRV may produce some con-densation. This wa...
Page 7 - Remote Control Connections
7 Remote Control Connections Electrical connections should be made by a qualified ser-v i c e t e c h n i c i a n . L o w v o l t a g e w i r e s f r o m t h e r e m o t econtrols are connected to the damper motor terminals. Identify the appropriate installation type and connect asper illustration. ...
Page 8 - Forced; REMOTE DEHUMIDISTAT; • anywhere humidity is a concern; Dehumidistat Operation; PROBLEMS
8 Installation NOTES: 1. Furnace blower is required to operate when ventilation is required. 2. Weatherhood arrangement is for drawing purposes only. Six feet (2 m) minimum separation required. Eighteen inches (460 mm) above grade minimum.3. Due to pressure differences in the equipment, airflows mus...
Page 9 - Balancing Procedure; CROSS SECTION AREA; Air Flow Balancing
9 It is necessary to have balanced air flow in an HRV. The vol-ume of air brought in from the outside must equal the volumeof air exhausted by the unit. If the air flow is not properly bal-anced, then: • The HRV may not operate at its maximum efficiency • A negative or positive air pressure may occu...
Page 10 - Placement of Pitot Tube HRV; Pitot Tube and Gauge; Pitot Tube Air Flow; with magnehelic gauge,; NOTE: Apply use of balancing dampers as required.
10 Forced Air Furnace Outdoors Cool Air Return Return Air Built-in balancing damper* in both air streams. *Unit is normally balanced withfurnace running at highest operational speed MAGNEHELIC MAGNEHELIC Placement of Pitot Tube HRV MAGNEHELIC Pitot Tube and Gauge Pitot Tube Air Flow Balancing Kit wi...
Page 11 - Maintenance
11 1. Inspect Exterior Hoods at least once a month. Make sure exhaust and fresh air supply hoods are notblocked or restricted by leaves, grass, or snow. In winter, itis especially important to make sure snow is not blockingthe hoods or that frost has not built up on the wire mesh(bird screen). WARNI...
Page 12 - Notes
12 Date Maintenance Performed Contractor Notes Maintenance Record Note: It is important to maintain this product regularly to ensure optimal performance.
Page 15 - T ube de Pitot et débitmètre; Nécessaire d’équilibrage; avec tube de Pitot incluant; Ce schéma n’est offert qu’à des fins d’illustration. Les
10 Placement du tube de Pitot (VRC) T ube de Pitot et débitmètre Nécessaire d’équilibrage des débits d’air avec tube de Pitot incluant un débitmètre à hélice, un tuyau flexible et une mallette. N.B. : Ce schéma n’est offert qu’à des fins d’illustration. Les orifices de raccordement pour les canalisa...
Page 16 - A TTENTION; Équilibrag
9 Dans un VRC, il est essentiel que le volume des circuits d’air soit équili- bré. La quantité d’air provenant de l’extérieur doit égaler la quantité évacuée par l’appareil. Les conséquences d’un déséquilibre des débits d’air pourraient être les suivantes : • Le VRC ne fonctionnera peut-être pas à s...
Page 17 - DÉSHUMIDISTAT À DISTANCE; *qui exige deux fils; s’emploie partout où il y a beaucoup d’humidité; Pièce N; Fonctionnement du déshumidistat; Basse tension - courant alternatif de 24 volts
8 Installation REMARQUES : 1. Il faut que la soufflante de la fournaise fonctionne lorsqu’on a besoin de ventilation. 2. L ’agencement ci-dessus des capuchons anti-intempéries n’est que pour les fins du dessin. En réalité, un écartement d’au moins 6 pieds (2 mètres) est requis. Ils doivent aussi êtr...
Page 18 - Connexions pour télécommandes; A VER
7 Connexions pour télécommandes Les raccordements électriques devraient être effectués par un technicien compétent. Les fils à basse tension pro ve na nt de s té lé co mm an de s so nt co nn ec té s au x bornes du moteur du registre. Identifiez le type d’installation approprié et raccordez tel qu’il...
Page 19 - comme protection contre les fuites d’eau de condensation.
6 Système d’évacuation de l’air vicié Le rendement du réseau d’évacuation de l’air vicié est basé sur la pression positive créée dans les canalisations de la fournaise. Pour que ce système soit efficace, il faut que la soufflante de l’appareil de traitement de l’air soit en marche. Raccord d’écoulem...
Page 21 - Raccordement d’appareils au VRC; • sécheuse à linge; Dégag
4 Choix de l’emplacement Le VRC doit être placé dans un endroit chauffé où il sera possible de l’entretenir facilement. Normalement, le VRC de vra it êtr e in sta llé d an s la c ha mb re d es a pp are ils mécaniques ou dans un endroit près du mur extérieur sur lequel on posera les capuchons anti-in...
Page 23 - Dimensionsdu
2 MODÈLE94-EXCHANGER-MD —Comprend unregistre motoriséà 24volts Fichetechnique -VRC Dimensionsdu VRC enpouces (mm) Dimensionsdu VRC enpouces (mm) ® GARANTIE: Garantieà viesur lenoyau d’échangede chaleuren aluminium.Garantie decinq anspour toutesles autres pièces. MODÈLE94-EXCHANGER —Pas deregistre. U...