Page 2 - TABLE OF CONTENTS; INTRODUCTION; Manufactured Home Requirements; PACKAGING; WARNING; GENERAL INFORMATION; Millivolt; Please read and understand these
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 2 TABLE OF CONTENTS Packaging .........................................Page 2 Introduction ......................................Page 2 General Information ..........................Page 2 New York City Approval .....................Page 3 Require...
Page 3 - Series; Table 7; by closing their; Flame Height
3 NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. Electronic Models - Electronic models have a fixed rate gas valve. Input of electronic models is shown in Table 3. Electronic Models with Fixed Rate Gas Valve Natural and Propane Gas Model Series Input Rate (BTU / HR) LMDVT-3328 LMDVR-3328 17,50...
Page 4 - COLD CLIMATE INSULATION; Figure 4; Typical Locations; LOCATION
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 4 Massachusetts And New York City, NY Re- quirements These appliances are approved for installation in the following USA locations listed in the following: Massachusetts: These fireplaces are approved for installation in the US state of Massachuse...
Page 5 - VENT TERMINATION CLEARANCES; Figure 5; Horizontal Vent Termination Clearances; Figure 6; MANUFACTURED HOME; CAUTIONS; Termination Heights For Vents; Side Elevation View
5 NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 12 X Roof Pitch is X/12 2 FT MIN. 2 FT MIN. Lowest Discharge Opening H* *H = MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING OF VENT TERMINATION HEIGHTS FOR VENTS ABOVE FLAT OR SLOPED ROOFS Horizontal Overhang Vertical Wall Vent Termination...
Page 6 - EXTERIOR HORIZONTAL VENT TERMINATION CLEARANCE REQUIREMENTS; Figure 7; = Area where Terminal is not Permitted
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 6 EXTERIOR HORIZONTAL VENT TERMINATION CLEARANCE REQUIREMENTS Figure 7 V V V V V F C Fixed Closed Window Operable Window B B A B H M I = Area where Terminal is not Permitted = Air Supply Inlet X = Vent Terminal V D V 3 ft. 3 ft. A A A = 9” in U.S....
Page 7 - MINIMUM CLEARANCES TO COMBUSTIBLES; Table 8
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 7 Hearth Extension A hearth extension is not required with this appliance. If a hearth extension is used, do not block the lower control compartment door. Any hearth extension used is for appearance only and does not have to conform to standard he...
Page 8 - Pressure Relief Plates; TYPICAL INSTALLATION SEQUENCE; Figure; DETAILED INSTALLATION STEPS; Control Compartment Access / Louver Panel
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 8 Also see Figure 14. 6 1/2" (152 mm) 3" (76 mm) Figure 13 - ROUTE GAS LINE Right Side Front Corner of Fire- place Framing Continued on Page 10. REMOVE CARDBOARD BEFORE USING REMOVE CARDBOARD BEFORE USING Pressure Relief Plates Remove Card...
Page 9 - FIREPLACE SPECIFICATIONS; Vertical Venting Through the Ceiling:; Frame ceiling opening; of 2x4 or larger lumber; Framing; Top View
9 FIREPLACE SPECIFICATIONS Vertical Venting Through the Ceiling: Frame ceiling opening - Use a plumb line from the ceiling above the appliance to locate center of the vertical run. Cut and/or frame an opening, 10-1/2" x 10-1/2" (267 mm x 267 mm) inside dimensions, about this center mark (see...
Page 10 - FIREPLACE FRAMING SPECIFICATIONS; Table 9; Proper Sizing of Gas Line
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 10 C Back wall of chase/enclosure (including any finishing materials) a Inches (millimeters) LMDV and LMDVR units D E F A B LMDV and LMDVT units 7 1/4 (184) b Note- Venting requirments for rear vent applications in corner installations - • The hor...
Page 11 - Approved Vent Components; on
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 11 Figure 18 Figure 19 Select Venting System - Horizontal or Vertical With the appliance secured in framing, de- termine vent routing and identify the exterior termination location. The following sections describe vertical (roof) and horizontal (e...
Page 12 - Model; See Figure 20 on Page 12 and Figures 28-
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 12 T R A H C H T G N E L N O I T C E S T N E V n o it c e S l a n i m o N ) s e h c n i ( h t g n e L 6 2 1 4 2 6 3 8 4 T O T A L Q T Y n o it c e S t e N ) s e h c n i ( h t g n e L 2 / 1 - 4 2 / 1 - 0 1 2 / 1 - 2 2 2 / 1 - 4 3 2 / 1 - 6 4 t n e ...
Page 14 - VERTICAL VENT FIGURES/TABLES; rate Sections of Concentric Flexible
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 14 If the vent system extends more than 5 feet (1.5 m) above the roof flashing, stabilizers may be necessary. Additional screws may be used at section joints for added stability. Guide wires may be attached to the joint for additional sup- port on...
Page 15 - Maximum; Ratio V to H ratio is 1:2; A Vent Restrictor, as shown in
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 15 V H H V V1 Figure 28 - Top Vent - STRAIGHT Notes: • It is very important that the horizontal/in- clined run be maintained in a straight (no dips) and recommended to be in a slightly elevated plane, in a direction away from the fireplace of 1/4&...
Page 16 - Top Vent - THREE ELBOWS
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 16 A. Plan the vent run - Analyze the vent routing and determine the types and quantities of sections required 4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" (876 mm) and 46-1/2" (1181 mm) net section lengths are ...
Page 18 - For thicknesses greater; IMPORTANT; Termination Guard
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 18 J. Assemble vent run to exterior wall - If not previously measured, locate the center of the vent at the exterior wall. Prepare an opening as described in Step B . Assemble the vent system to point where the terminus of the last section is loca...
Page 19 - When using Secure Flex,; Under no circumstances, may separate sections of; HORIZONTAL VENT FIGURES/TABLES; Square termination; Termination Kit and 6 In. Vent
19 NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. H H = 28 in. (711 mm) Maximum. 7 in. (178 mm) � When using Secure Flex, use Firestop/Spacer SF4.5HF � Wall Firestop/Spacer (SV4.5HF) H V � Wall Firestop/Spacer (SV4.5HF) � When using Secure Flex, use Firestop/Spacer SF4.5VF. � Ceiling Firestop/...
Page 20 - See Table 12 on Page 19 as an aid in venting component
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 20 H1 V H � Wall Firestop/Spacer (SV4.5HF) � Ceiling Firestop/Spacer (SV4.5VF) � When using Secure Flex, use Firestop/Spacer SF4.5HF. � When using Secure Flex, use Firestop/Spacer SF4.5VF. V H H1 � Wall Firestop/Spacer (SV4.5HF) � Wall Firestop/Sp...
Page 22 - SECuRE FLEX
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 22 D. Install Firestop / Spacers at ceilings and walls - When Secure Flex penetrates a wall or ceiling, a firestop / spacer is required: use the SF4.5 VF firestop / spacer for ceilings and the SF4.5 HF firestop / spacer for walls. See the appropri...
Page 23 - Step 4. FIELD WIRING; WIRING - OPTIONAL FORCED AIR; See; CAUTION; Millivolt Wiring Diagram; TP
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 23 Figure 46 See Figure 14 on Page 9 for Optional Electrical Inlet Knockout Location Step 4. FIELD WIRING 3. Connect the power supply wires (including the ground supply wire) as shown in Figure 47. (If the field-provided J-box/outlet box is being ...
Page 24 - Schematic Representation Only; Gas; Gas Flex Line Connector; GAS CONNECTION; Step 6. CONNECTING GAS LINE; Secure all joints tightly using appropriate; ground screw located on the outlet box. See
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 24 Electronic Wiring Diagram (Honeywell) Showing Blower Wiring for Optional FBK-100, FBK-200 & FBK-250 Kits Schematic Representation Only Relay Module C/W FBK-250 only. Plug blower into J-Box receptacle for FBK-100 or FBK-200 application. See ...
Page 25 - TEST ALL CONNECTIONS FOR GAS LEAKS; Never use an open flame to; CONTROL COMPARTMENT ACCESS /; can be found in the control compartment; SIT and Honeywell Millivolt Appliance
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 25 Figure 49 OPENING CONTROL COMPARTMENT DOOR Control Valve Lower Control Compartment Door Lift the Lower Control Compartment Door up and pull out to remove. Up Out Hook Catch Reinstalling Control Compartment Door: To reinstall, insert the hook ca...
Page 26 - Bag of Glowing; CANIC STONE, GLOWING EMBERS AND; Removing Glass Enclosure Panels; Electronic Appliance Checkout
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 26 WARNING The size and position of the log set was engineered to give the appliance a safe, reliable and attractive flame pattern. Any attempt to use a different log set in the fireplace will void the warranty and will result in incomplete combus...
Page 27 - Log Placement Instructions; LOG SET; Description; DO NOT PLACE EMBERS OVER BuRNER SLOTS; shown here (1 through 6) and per the instructions on
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 27 Figure 55 MODEL LMDV-3328 & LMDV-3530 Log Placement Instructions LOG SET Catalog Number H3366 * Item Description A Log, Rear B Log, Left C Log, Left Center D Log, Right Center E Log, Right * Item "letters" above correspond to photos...
Page 29 - Step 9. INSTALLING THE GLASS DOOR; Ensure front glass panel are in; Reinstalling Control
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. Step 9. INSTALLING THE GLASS DOOR WARNING Air shutter adjustment should only be performed by a qualified profes- sional service technician. WARNING Ensure front glass panel are in place and sealed during adjust- ment. Air Shutter Adjustment Guidel...
Page 30 - The air shutter door and nearby appliance surfaces are; Step 11. HOOD INSTALLATION; See Page 4 for Cold Climate Insulation; Burner Air Shutter Adjustment Procedure; Combustible Wall Framing
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 30 Main Burner Factory Air Shutter Opening Setting - Inches (millimeter) Model Nat.Gas Propane Gas LMDVT-3328 1/16 (1.58) 1/4" (6.35) LMDVR-3328 1/16 (1.58) 1/4" (6.35) LMDV-3530 1/16(1.58) 5/16" (7.94) LMDV-4035 1/8 (3.18) 3/8" (9...
Page 31 - INSTALLATION ACCESSORIES; The following flashings come packaged with a storm collar:; Through Wall Shield Kit; Termination Shroud (Guard) for Horizontal Square Termination
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 31 Item Cat. No. Model Description 1 H1968 SV4.5HT-2 Horizontal Square Termination With Firestop / spacer (H2246) & Adapter (74L61) 2a H2152 SV4.5CGV-1 Vertical Termination Cap 2b H4687 SV4.5CTS Chase Top Termination Square 2b H4716 SV4.5CTS-B...
Page 32 - Open Top, Chase Top Shroud; All compressed flex vents can be; Arch Top, Chase Top Shroud
32 NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. Item Cat. No. Model Description 18 H1969 SF4.5HT-2 Horizontal Square Termination (without flex) 18 77L87 SFKIT12S Flex Square Term. (with 12 inch [305 mm] * compressed flex) 18 77L88 SFKIT18S Flex Square Term. (with 18 inch [457 mm] * compresse...
Page 33 - Horizontal Small Square Termination without flex vent
33 NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. Listed Secure Flex™ Components LMDV-3328 & LMDV-3530 Models Only Cat. No. Model Description 94L04 SFKIT12SS Flex - Small Square Termination with 12 in. (305 mm) of *compressed flex vent 94L05 SFKIT18SS Flex - Small Square Termination with 1...
Page 34 - GAS CONVERSION KITS
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 34 IMPORTANT/CANADA The conversion shall be carried out in accordance with the requirements of the provincial authorities having jurisdiction and in accordance with the requirements of the CAN1-B149.1 And B149.2 Installation code. WARNING This con...
Page 35 - La conversion devra être effectuée; Note - use extra care not to engage the; NA
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 35 IMPORTANT LE CANADA SEULEMENT La conversion devra être effectuée conformément aux recommanda- tions des autorités provinciales ayant juridiction et conformément aux exigences du code d'installation CAN1-B149.1 ET.2. Note - use extra care not to...
Page 36 - drill
36 NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. Printed in U.S.A. © 2005 by LENNOX HEARTH PRODUCTS P/N 850,029M REV. G 05/2008 Lennox reserves the right to make changes at any time, without notice, in design, materials, specifications, pri...