Page 2 - TABLE OF CONTENTS; Please read and understand these; b. Firebox Liner Kit, Red Herringbone Liner; INTRODUCTION; Use Only These Approved Vent Components; WARNING; GENERAL INFORMATION; DO NOT ATTEMPT TO ALTER OR MODIFY
2 TABLE OF CONTENTS Packaging .........................................Page 2Introduction ......................................Page 2General Information ..........................Page 2Requirements for Commonwealth of Massachusetts ............................Page 4New York City, New York (MEA) ......
Page 3 - edition, or the Canadian Electrical Code, CSA; Table 1
3 Note: Installation and repair should be done by a qualified service person. The appliance should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bed- ding material, etcetera. It is imperati...
Page 4 - Flame appearance will diminish 4% per; Table 4; Flame Height; Flame Height; Figure 2; REQUIREMENTS FOR THE COMMON-
4 NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. Gas Pressure - All Models Tables 2 and 3 show the appliances' inlet and manifold gas pressure requirements: Inlet Gas Supply Pressure (all models) Fuel # Minimum Maximum Natural Gas 5.0" WC (1.24 kPa) 10.5" WC (2.61 kPa) Propane 11.0"...
Page 5 - TOP VENT INSTALLATIONS; Top View; Figure 3 - Typical Installation; Do not insulate the space between the ap-; When the unit is installed with one side flush
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 5 HORIZONTAL VENT (Top Vent Application) VERTICAL VENT (Top Vent Application) RECESSED INSTALLATION TOP VENT INSTALLATIONS HORIZONT AL VENT (T op V ent Application) VER TICAL VENT (T op V ent Application) RECESSED INST ALLA TION TOP VENT INSTALLAT...
Page 6 - VENT TERMINATION CLEARANCES; These instructions should be used as a; Vertical Vent Termination Clearances; Figure 4; Horizontal Vent Termination Clearances; Minimum; Figure 6; Horizontal Vent Termination Clearances; Side Elevation View
6 NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. Termination Heights For Vents Above Flat Or Sloped Roofs Ref. NFPA 54 / ANSI Z223.1 Roof Pitch * Feet * Meters Flat to 6/12 1.0 0.3 6/12 to 7/12 1.25 0.38 7/12 to 8/12 1.5 0.46 8/12 to 9/12 2.0 0.61 9/12 to 10/12 2.5 0.76 10/12 to 11/12 3.25 0.9...
Page 7 - EXTERIOR HORIZONTAL VENT TERMINATION CLEARANCE REQUIREMENTS; Figure 7
7 NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. EXTERIOR HORIZONTAL VENT TERMINATION CLEARANCE REQUIREMENTS Figure 7 V V V V V F C Fixed Closed Window Operable Window B B A B H M I = Area where Termination is not Permitted = Air Supply Inlet X = Vent Termination V D V 3 ft. 3 ft. A A A = 9” i...
Page 8 - The appliance is approved with zero clearance to com-; When the unit is installed; side walls surrounding the unit must not extend beyond; Mantel Clearances; Figure 9 - Mantel Clearances; Shelf Height; Figure 8; We recommend the use of high temperature
8 MINIMUM CLEARANCES TO COMBUSTIBLES Appliance And Vent Clearances The appliance is approved with zero clearance to com- bustible materials on all sides (as detailed in Table 5) , with the following exception: When the unit is installed with one side flush with a wall, the wall on the other side of ...
Page 9 - DETAILED INSTALLATION STEPS; on Page; Figures; TYPICAL INSTALLATION SEQUENCE; Page 9
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 9 DETAILED INSTALLATION STEPS The appliance is shipped with all gas controls and components installed and pre-wired. 1. Remove the shipping carton, exposing the front glass door. 2. Pull out the two spring loaded latches secur- ing the glass door ...
Page 10 - Framing should be; FIREPLACE AND FRAMING SPECIFICATIONS
10 NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. Co-axial DV Vent 4-1/2" (114) Inner 7-1/2" (191) Outer 36-23/32 (933) 21-1/16 (535) 1-7/8 (48) 6-1/16 (154) 8-7/32 (209) 1-1/2 (38) 15-1/32 (382) 15-15/32 (393) 7-11/16 (195) 34 (864) 40-1/32 (1017) 20-3/4 (527) 14-3/4 (375) 5-13/32 (13...
Page 11 - FACADE SPECIFICATIONS; Gated Facades
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 11 23-1/2” (597) 14-3/4” (375) 20-3/4” (527) Facade (Required) * (gated style shown) 1/2” (13) 37-7/8” (962) 18-3/4 (476) 1/2” (13mm) - 1-1/2” (38mm) ** A filigree inset kit is also required (sold separately). See Care and Operation Manual for ord...
Page 12 - Table 6; Proper Sizing of Gas Line; Inches; mm; Figure 15 - Route Gas Line; Step 2. ROUTING GAS LINE; * Measured from the top of platform that unit
12 NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. Schedule 40 Black Iron Pipe Inside Diameter (Inches) Schedule 40 Pipe Length (feet) Natural Gas Propane Gas 0-10 1/2 3/8 10-40 1/2 1/2 40-100 1/2 1/2 100-150 3/4 1/2 150-200 3/4 1/2 Table 6 Proper Sizing of Gas Line Properly size and route the ...
Page 13 - Approved Vent Components; on
13 Step 3. INSTALL THE VENT SYSTEM General Information These instructions should be used as a guideline and do not supersede local codes in any way. Install vent according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/...
Page 14 - Effective Vent Length; Model; Table 7; FlexTMpipe may also be used. A Vertical Vent; Figure 5; Tables on this page
14 NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. T R A H C H T G N E L N O I T C E S T N E V n o it c e S l a n i m o N ) s e h c n i ( h t g n e L 6 2 1 4 2 6 3 8 4 T O T A L Q T Y n o it c e S t e N ) s e h c n i ( h t g n e L 2 / 1 - 4 2 / 1 - 0 1 2 / 1 - 2 2 2 / 1 - 4 3 2 / 1 - 6 4 t n e ...
Page 17 - VERTICAL VENT FIGURES/TABLES; Maximum; Top Vent - THREE ELBOWS; rate Sections of Concentric Flexible
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 17 H V V1 Figure 24 - Top Vent - STRAIGHT VERTICAL VENT FIGURES/TABLES Notes: • Secure Vent™ (rigid vent pipe) is shown in the Figures; Secure Flex™ (flexible vent pipe) may also be used. • It is very important that the horizontal/in- clined run b...
Page 19 - Step B; Termination Guard
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 19 SV4.5 HT-2 Termination SV4.5 HT-2 Termination Horizontal terminations have been designed to perform in a wide range of weather condi- tions. Our terminations meet or exceed industry standards. When selecting the locations of your horizontal ter...
Page 20 - Under no circumstances, may separate sections of; HORIZONTAL VENT FIGURES/TABLES; Square termination; Termination Kit and 6 In. Vent; Table 8
20 NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. H V � Wall Firestop/Spacer (SV4.5HF) � When using Secure Flex, use Firestop/Spacer SF4.5VF. � Ceiling Firestop/Spacer (SV4.5VF) � When using Secure Flex, use Firestop/Spacer SF4.5HF. Figure 30 - Top Vent - ONE 90 DEGREE ELBOW - ELBOW CONNECTION...
Page 21 - to a maximum horizontal run of 20 feet.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 21 V H H 1 � Wall Firestop/Spacer (SV4.5HF) � Wall Firestop/Spacer (SV4.5HF) � When using Secure Flex, use Firestop/Spacer SF4.5HF. � Ceiling Firestop/Spacer (SV4.5VF) � Note - When using Secure Flex TM , use Firestop/Spacer SF4.5VF. Table E H + H...
Page 22 - SECuRE FLEXTM; PONENTS
22 NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. D. Install Firestop / Spacers at ceilings and walls - When Secure Flex penetrates a wall or ceiling, a firestop / spacer is required: use the SF4.5 VF firestop / spacer for ceilings and the SF4.5 HF firestop / spacer for walls. See the appropri...
Page 23 - Verify proper operation after servicing.; ELECTRONIC; See Figure 12 on Page; CAUTION
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 23 Step 4. FIELD WIRING Refer to Section A for millivolt appliances and Section B for electronic appliances. The gas valve is set in place and pre-wired at the factory on both models. A. Millivolt Wiring (See Figure 36) – 1. Appliance-mounted ON/O...
Page 24 - Figure 40 - Control Compartment; Gas
24 NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. BLOWER CONTROL CIRCUIT WIRING 120V, 60HZ, 1PH Factory Wired Ground Field Wired Junction Box Tab Intact Tab Broken Plug blower into this receptacle ne er G - dn uor G * Wall-mounted ON/ OFF Blower Switch or Variable Speed Control Switch. Blower ...
Page 25 - Never use an open flame to; TEST ALL CONNECTIONS FOR GAS LEAKS; TION; Lighting Instructions are also found on the; Millivolt Appliance Checkout
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 25 WARNING Never use an open flame to check for leaks. Turn on gas supply and test for gas leaks using a gas leak test solution (also referred to as bubble leak solution). Note: Using a soapy water solu- tion is an effective leak test solution but...
Page 26 - Glowing Embers; Bag of Glowing; Ember Burner Ports; Figure 43 - Log Set and Glowing Embers; Step 8. INSTALLING THE LOGS AND GLOWING EMBERS; Log setup is by design asymmetric. The fire is intentionally posi-; Remove the front glass enclosure panel
26 NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. Glowing Embers Bag of Glowing Embers (rockwool) Separate into Quarter Size (separate) Pieces Locating Pins - 5 Places Log Support Bracket Firebox Ember Burner Ports LOG SET Catalog Number H1237 * Item Description A Log, Rear B Log, Left Middle ...
Page 27 - that the main burner ports remain uncovered by the ember material; Figure 49 - Ember Placement; DO NOT place ember material directly
27 NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 1. Place the rear log (A) as shown in Figure 44 . Position the 2 holes on the bottom of the log over the corresponding locating pins (#1 & #2) and against the log support bracket. See Figures 43 and 44 for pin and rear bracket locations. 2....
Page 28 - Removing Glass Enclosure Panel; ) and raise it slightly to lift the top flange of; Installing Glass Enclosure Panels; Pull Latches; Note: When installing the glass door, ensure
28 NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. Step 9.INSTALLATION AND REMOVAL OF GLASS DOOR Figure 5 1 - Glass Door Removal Door Assembly These are direct-vent appliances. They are designed to operate only when the front glass enclosure panel is installed. Generally the front glass enclosu...
Page 29 - Step 10. BURNER ADJUSTMENTS; for proper burner flame; Figure 52 - Burner Air Shutter; Valve; the way down it is fully open. When the arm is; WARNINGS; Burner Air Shutter Adjustment Procedure
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 29 Step 10. BURNER ADJUSTMENTS Flame Appearance and sooting Proper flame appearance is a flame which is blue at the base and becomes yellowish-orange in the body of the flame. When the appliance is first lit, the entire flame may be blue and will ...
Page 30 - Figure 53 - Burner Flame Appearance; FINISHING REQUIREMENTS - Wall Details; standard hearth extension installation requirements.
30 NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. Figure 53 - Burner Flame Appearance * Vent to combustible on Side = 1" Min. Vent to combustible on Top = 3" Min. IMPORTANT NOTE: Place the header verti- cal as shown to main- tain proper clearance from the vent system to combustibles. F...
Page 31 - ) o en el termostato; ) and if used on the; Figure A
31 NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. Step 11. ATTACHING SAFETY IN OPERATION WARNINGSIt is the installer ' s responsibility to ensure these warnings are properly affixed during installation. These warning labels are a critical step in informing consumers of safe operation of this a...
Page 32 - INSTALLATION ACCESSORIES
32 (Fits 94L10 & H1968) (Fits H1968) (Fits 94L10 & H1968) INSTALLATION ACCESSORIES Listed Secure Vent™ Components Cat. No. Model Description H1968 SV4.5HT-2 Horizontal Square Ter- mination With Firestop / spacer (H2246) & Adaptor (74L61) H2152 SV4.5CGV-1 Vertical Termination Cap 77L70 SV...
Page 33 - Millivolt; this installation assumes responsibility for this conversion.; AVERTISSEMENT; assume les responsabilités liées à la conversion.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 33 Burner Assembly Burner Orifice Gas Train Assembly Gas Valve Figure 55 In Canada: THE CONVERSION SHALL BE CAR- RIED OUT IN ACCORDANCE WITH THE REQUIREMENTS OF THE PROVINCIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE RE- QUIREMEN...
Page 34 - VERIFY THE PROPER ORIFICE SIZE BE-; Millivolt & Electronic Gas Valves; Millivolt & Electronic Pilot Assemblies; Figure 58 - Burner Orifice; Table 9
34 NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 34 Step 6. Refer to Figure 57 and remove the pilot hood assembly to access the hexed pilot orifice. Remove and replace the orifice with the one provided with the kit. Step 7. (Refer to Figure 55 on Page 33 and Figure 58) VERIFY THE PROPER ORIFI...
Page 35 - NOTES