Page 2 - OnLine Power; HEAD QUARTERS
OnLine Power (6002-1646) REV. X8 a FIRE ALARM BACK-UP UPS1481 UNI T, Congratulations on selecting one of the fine products from On-Line Power, the Leader in Power Protection Technology. Our wide product offering includes Uninterruptible Power Systems (UPS), Power Conditioners, Automatic Voltage Regu...
Page 3 - Proprietary Reproduction or Distribution forbidden; NOTICE: THIS DOCUMENT CONTAINS PROPRIETARY; the reason for its receipt has terminated.; SAFETY
OnLine Power (6002-1646) REV. X8 b On-Line Power, Inc. Proprietary Reproduction or Distribution forbidden NOTICE: THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION This document contains proprietary and confidential information of On-Line Power, Inc. (”On-Line Power”). In consideration of the receipt o...
Page 4 - THI S DANGER SYMBO L IDENTIFIES A CONDITION OR ACTION WHICH; CAUTION; This unit was designed for specific applications. It should; not; be modified and/or used for any application other; IMPORTANT SAFETY INSTRUCTIONS; SAVE THESE INSTRUCTION S
OnLine Power (6002-1646) REV. X8 c DANGER!! THI S DANGER SYMBO L IDENTIFIES A CONDITION OR ACTION WHICH WILL RESULT IN SEVERE INJURY OR DEATH TO AN INDIVIDUAL OR S EVERE DAMAGE TO E QUIPMENT OR O TH ER PROPERTY . CAUTION Th is Caution symbol identifies a cond ition or action which may result in mino...
Page 5 - TABLE OF C O NTENTS
OnLine Power (6002-1646) Rev. X8 i TABLE OF C O NTENTS SECTION PAGE SECTION 1 OPERATION 1 1-1 INTRODUCTION 1 1-2 BENEFITS 2 1-3 PRODUCT FEATURES 1, 5 1-4 CUSTOMERS CONNECTIONS 6-9 1-5 Fire Alarm Back-up UPS1481 SIZING 9 1-6 OUTPUT LOADS 9 1-7 OPTIONS 9 SECTION 2 PREINSTALLATION 11 2-1 SITE P LANNING...
Page 7 - SECTION 1
OnLine Power (6002-1646) Rev. X8 1 SECTION 1 — OPERATION 1-1 INTRODUCTION The Fire Alarm Back-up UPS1481 provides an exceptional level of load protection and monitoring capabilities. The critical load is provided with conditioned, regulated, computer grade power at all times. There is complete elect...
Page 8 - FEATURES; — The SCR solid state switch bypasses the complete UPS and provides; Control Board
OnLine Power (6002-1646) REV. X8 2 systems, from electrical interference. The Fire Alarm Back-up UPS1481 protects these systems from power problems associated with poor quality AC power including complete power Outages. Electrical disturbances can come from practically anywhere: from the incoming po...
Page 11 - tvss
OnLine Power (6002-1646) REV. X8 5 1-3 FUNCTIONAL BLOCK DIAGRAM (CONTINUED) INPUT C.B. K1 1 3 2 INPUT POW ER T.B. TB1 THE FUNTIONAL BLOCK DIAGRAM OF U.P.S (OPTION) C1 INPUT FILTER INPUT CONTACTOR T2 STEPDOW N T4 CONT- ACTOR COIL FULL BRIDGE RECTIFIER BR1 K L1 L2 FILTER DC CHOPPERUP/DOWN BATT. CHARGE...
Page 12 - CONNECTIONS
OnLine Power (6002-1646) REV. X8 6 1-4 CUSTOMERS CONNECTIONS 1-4-1 Input Power Connection by Customer (with no input C/B option) Connect input (Hot) at TB-1 Connect input Hot / Neutral at TB1-2 Connect input ground at TB1-3 Input wirings for various input voltages are same. When input cirucit breake...
Page 13 - SAME INPUT AND OUTPUT VOLTAGE UNIT @ WITHOUT OUTPUT XFMR.
OnLine Power (6002-1646) REV. X8 7 1-4-2 OUTPUT POWER CONNECTION BY CUSTOMER FOR SAME INPUT AND OUTPUT VOLTAGE UNIT @ WITHOUT OUTPUT XFMR. 1 3 4 TB2 7 6 5 2 N/C N/C OUTPUT CB GND N H TO CUSTOMER LOAD120V OUT (OPTION) UPS CABINET B A C PB2/1 1. 120V IN/OUTPUT UNIT 2. 240V IN/OUTPUT UNIT 1 3 4 7 6 5 2...
Page 14 - -4-3 OUTPUT POWER CONNECTION BY CUSTOMER FOR DIFFERENT INPUT /
OnLine Power (6002-1646) REV. X8 8 1-4-3 OUTPUT POWER CONNECTION BY CUSTOMER FOR DIFFERENT INPUT / OUTPUT VOLTAGES USING OUTPUT XFMR. 1. 240V/120 OUTPUT UNIT 1 3 4 7 6 5 2 OUTPUT CB TO CUSTOMER LOAD (OPTION) FOR EACH OUTPUT VOLT B A C PB2/1 TB2 8 9 11 12 13 14 1 2 4 5 7 6 240V 120V 157V 120V 88V 0V ...
Page 15 - The Fire Alarm Back-up UPS1481 SIZING
OnLine Power (6002-1646) REV. X8 9 1-5 The Fire Alarm Back-up UPS1481 SIZING Each model of the Fire Alarm Back-up UPS1481 is designed to supply a maximum load which is given by its kVA (1000’s of volt-amperes) and KW rating. It is very important that the load is within the rating of the FIRE ALARM B...
Page 17 - SECTION 2; SITE PLANNING AND PREPARATION; STORAGE ENVIRONMENT.; • AMBIENT TEMPERATURE -30°C to 70°C
OnLine Power (6002-1646) REV. X8 11 SECTION 2 - INSTALLATION 2-1 SITE PLANNING AND PREPARATION The Fire Alarm Back-up UPS1481 is designed for installation indoors and meets NEMA specifications for operating temperature, humidity, and utility voltage. These cabinets are corrosion resistant and rugged...
Page 18 - SITE PLANNING SPECIFICATIONS FOR KVA UNIT
OnLine Power (6002-1646) REV. X8 12 TABLE 2-1 SITE PLANNING SPECIFICATIONS FOR KVA UNIT MODEL NUMBER IkW / kVA INPUT VOLTAGE INPUT AMP OUTPUT VOLTAGE OUTPUT AMP DC VOLT DC AMP QTY. BATT PER SET APPRO X. W/O BATT WEIGHT 1 WR3.0A58FPT1 3.0 120 40 120/240 25.00 @120 96V 43A 8 2 WR3.0B58FPT1 3.0 208 19 ...
Page 19 - UL1481 MICRO-CHIPS & OTHER COMPONENT’S LIST; KVA Rating; Single Phase; Output XFMN
OnLine Power (6002-1646) REV. X8 13 UL1481 MICRO-CHIPS & OTHER COMPONENT’S LIST MODEL NUMBER INPUT KW / KVA OUTPUT VOLTAGE MICRO-CHIP SOFTWARE BASIC UPS KIT LABEL KIT INPUT CONTACTOR BATT C.B. FANS 1 WR3.0A58FPT1 120 120/240V 9100-1319-018UL 9100-1312-11 9100-1295-02 1680-242 2025-769 1000-036 2...
Page 20 - the; CAUTIONS CAUTION
OnLine Power (6002-1646) REV. X8 14 2-2 Pre-Installation The Fire Alarm Back-up UPS1481 is designed for indoor installations. All customer connections are brought through knockouts located on the top or side of the Fire Alarm Back-up UPS1481. The Fire Alarm Back-up UPS1481 consists of one (1) integr...
Page 21 - Signaling; — This is a normally open contact; ON BYPASS”; — This is a normally open contact which closes when the; “SUMMARY ALARM”; — This is a normally open contact which closed when the Fire Alarm
OnLine Power (6002-1646) REV. X8 15 1. Verify that the main input circuit breaker, battery circuit breaker, and output circuit breaker(s), if provided are in the “OFF” position. See illustration 1-2 for the locations of the circuit breakers. See under Section 2-5, Storage for accessing the inside of...
Page 22 - Connection; J8 – connector / P8 IBM PC Serial Port
OnLine Power (6002-1646) REV. X8 16 3. Determine which signals will be used. Connect wires (customer-supplied) to the connector. 4. This concludes the remote signaling connection procedures. 5. This concludes the installation procedures. Please proceed to Section 3-Start-Up for these necessary to st...
Page 23 - and charging current.
OnLine Power (6002-1646) REV. X8 17 During long-term storage, the batteries are subject to aging and deterioration. If after visual inspection, the batteries need to be replaced contact your OnLine Power dealer or the OnLine Power factory directly to obtain new batteries. The UPS is stored in its or...
Page 24 - SECTION 3; CAUTION CAUTION
OnLine Power (6002-1646) REV. X8 18 SECTION 3 - OPERATION 3-1 Start-Up Procedures 1. Verify that the main input circuit breaker, battery breaker, and output circuit breaker(s), if provided, are in the “OFF” or “down” positions. Refer to illustration 1-2 for the locations of the circuit breakers. CAU...
Page 25 - Recheck that the output voltage is 120/240 VAC.
OnLine Power (6002-1646) REV. X8 19 6. At this point in time, the Fire Alarm Back-up UPS1481 should be providing AC line power. The Fire Alarm Back-up UPS1481 is not operating in the normal mode, turn off the input circuit breaker. Contact OnLine Power at (800) 797-7782 for technical assistance. 7. ...
Page 27 - Optional Output Isolation Transformer; (TI) — The transformer performs a number of; lnverter Test Switch; — This switch is a manually operated switch which tests the; Transformer; for various output voltages that are matched at its primary taps.
OnLine Power (6002-1646) REV. X8 21 9 . Optional Output Isolation Transformer (TI) — The transformer performs a number of critical functions. First, it provides excellent common mode and normal mode noise isolation of the load from the input or inverter power. Secondly, it provides voltage transform...
Page 28 - COMPONENT’S LOCATION & LIST
OnLine Power (6002-1646) REV. X8 22 3-4 COMPONENT’S LOCATION & LIST
Page 29 - COMPONENT’S TABLE
OnLine Power (6002-1646) REV. X8 23 COMPONENT’S TABLE
Page 32 - -5KW: Load only change using 5KW unit.; Battery Part Number Nomenclature.; Basic Model
OnLine Power (6002-1646) REV. X8 26 APPENDIX A: EXTENDED BATTERY RUN CHART Battery kitPart# 7050-354 7050-355 7050-356 7050-357 7050-358 7050-359 7050-360 7050-361 7050-362- 7050-363- 7050-364- 7050-365- LoadKVA 0.5 0.75 1.0 1.5 2.0 3.0 4.0 5.0 7.5 10.0 12.5 Minutes -015 -015 -015 -015 -015 -015 015...
Page 33 - APPENDIX B – Optional Main Input & Main Output Breakers; for various models (*All Values are typical as reference only); Output Voltages
OnLine Power (6002-1646) REV. X8 27 OTHERS ARE CALCULATED VALUES BASED ON THE BATTERY MANUFACTURER'S DATA FOR BACK UP TIME. APPENDIX B – Optional Main Input & Main Output Breakers for various models (*All Values are typical as reference only) TABLE B-1: External Output Breaker (Standard KAIC) Ou...
Page 34 - INPUT CIRCUIT BREAKER; Input Voltages
OnLine Power (6002-1646) REV. X8 28 INPUT CIRCUIT BREAKER TABLE B-3: Input Breaker Ampacity (Standard KAIC) Input Voltages KVA 120 Vac 240 V/ or 208V 3 50 Amps, 120 VAC, 1 Pole, 14 KAIC OLP P/N: 2025-784 30 Amps, 240 VAC, 2 Pole, 14 KAIC OLP P/N: 2025-790 5 70 Amps, 120 VAC, 1 Pole, 14 KAIC OLP P/N:...
Page 35 - The screen appears as below.; indicates the KW rating of the unit
OnLine Power (6002-1646) REV. X8 29 OnLine Power UPS Project UPS NORMAL @ 7 KW INPUT OK @ CHRG ON BATTERY OK @ DC OK ON INVERTER @ OUT OK APPENDIX C: LCD DISPLAY MENU & TROUBLSHOOTING GUIDE Two screens (A, B) are updated continuously for units without optional output transformer. Three screens (...
Page 36 - NA
OnLine Power (6002-1646) REV. X8 30 OUTPUT: ______V @ ______ W INPUT : ______V @ ______ A DC BUSS: ______V @ NA A BATT: ________V @ +______ A SCREEN B: The screen appears as below. 4. Indicates output voltage and power in watts, when output transformer is not used. It indicates primary voltage of th...
Page 38 - Electronic / Circuit Breaker
OnLine Power (6002-1646) REV. X8 32 APPENDIX D: SPECIFICATION POWER RATING (KW) 3.0 5.0 7.5 10 12.5 15 VOLTAGE (VAC) INPUT Single Phase, 120/208/240 Single Phase, 240/208VAC MAXIMUM CURRENT 40/19/16 58/30/28 41/36 58/50 69/60 83/72 TOLERANCE +10 % to -1 5 % FREQUENCY (Hz ) 6 0 +/- 3 % POWER FACTOR 0...
Page 39 - BATTERY
OnLine Power (6002-1646) REV. X8 33 POWER RATING (KVA/KW) 3.0 5.0 7.5 10 12.5 15 BATTERY BATTERY RUN TIME See Appendix C for various Run time BATTERY TYPE Sealed, Maintenance -Free, AGM, VRLA type NOMINAL DC VOLTAGE 96 VDC 120 VDC 120 VDC 192 VDC 192 VDC 240 VDC OVERCURRENT PROTECTION Circuit Breake...