Page 2 - TABLE OF CONTENTS
TABLE OF CONTENTS Engineering Features ............................................................................... 4 Introduction ............................................................................................. 5 Selection Procedure .....................................................
Page 3 - T G C; MODEL IDENTIFICATION
MODEL NOMENCLATURE - TGC SERIES T G C Package Gas Electric Rooftop 036 Cooling Capacity (BTUH Nominal) 036 = 36,000 042 = 42,000 048 = 48,000 060 = 60,000 C Vintage 1 Electrical Designation 1 = 208-230 V, 1 PH, 60 Hz 4 = 460 V, 3 PH, 60 Hz 3 = 208-230 V, 3 PH, 60 Hz K Drive Package K = Direct Drive ...
Page 4 - TGC Series Package Gas Electric Units; All models feature Copeland; ENGINEERING FEATURES
ENGINEERING FEATURES TGC Series Package Gas Electric Units 1. All models feature Copeland ® Scroll ® compressors offering maximum reliability, efficiency, and quiet operation. 2. Aluminized steel heat exchanger with in-shot burners helps eliminate corrosion. 3. Integrated blower/burner control board...
Page 5 - INTRODUCTION
These quality features are included in the Heat Controller Package Gas Electric Unit Evaporator Coil/Filter Access • Return air filters, normallyprovided, are removed inthis photo. Tubular Heat Exchanger • Aluminized steel(viewed from supplyair side panel.) • Stainless steel available Heating Compar...
Page 6 - SELECTION PROCEDURE EXAMPLE
1. Determine cooling and heating requirements at design conditions. Example: Total cooling capacity ........................43,600 BTUH Sensible cooling capacity ..................34,000 BTUH Heating capacity ................................96,000 BTUH Condenser entering air ......................95...
Page 7 - NOMINAL 3 TONS; GENERAL DATA
NOMINAL 3 TONS Model TGC036C-1K-120 TGC036C-3K-120 TGC036C-4K-120 Cooling Performance 1 Gross Cooling Capacity Btuh 37400 37400 37400 EER/SEER 2 11.7/13 11.7/13 11.7/13 Nominal CFM/ARI Rated CFM 1200/1200 1200/1200 1200/1200 ARI Net Cooling Capacity Btuh 36000 36000 36000 Net Sensible Capacity Btuh ...
Page 8 - ENERAL DATA
NOMINAL 3 .5 TONS Model TGC042C-1K-120 TGC042C-3K-120 TGC042C-4K-120 Cooling Performance 1 Gross Cooling Capacity Btuh 43000 43000 43000 EER/SEER 2 11.45/13 11.45/13 11.45/13 Nominal CFM/ARI Rated CFM 1400/1450 1400/1450 1400/1450 ARI Net Cooling Capacity Btuh 41000 41000 41000 Net Sensible Capacity...
Page 10 - NOMINAL 5 TONS
NOMINAL 5 TONS Model TGC060C-1K-135 TGC060C-3K-135 TGC060C-4K-135 Cooling Performance 1 Gross Cooling Capacity Btuh 60000 60000 60000 EER/SEER 2 11.6/13 11.6/13 11.6/13 Nominal CFM/ARI Rated CFM 2000/1900 2000/1900 2000/1900 ARI Net Cooling Capacity Btuh 58000 58000 58000 Net Sensible Capacity Btuh ...
Page 11 - SYSTEM PERFORMANCE
GROSS SYSTEM PERFORMANCE DATA— TGC036C ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C] CFM [L/s] 1500 [707.9] 1200 [566.3] 900 [424.8] 1500 [707.9] 1200 [566.3] 900 [424.8] 1500 [707.9] 1200 [566.3] 900 [424.8] DR ➀ .16 .12 .06 .16 .12 .06 .16 .12 .06 OU T DOO...
Page 13 - DIRECT
AIRFLOW PERFORMANC E — DIRECT DRIVE DIRECT -DRIVE 208 VOLT AIRFLO W PERFORMANCE External Static Pressure—Inches W .C. [kPa] CFM [L/s] Air Deliver y/RPM/W atts—208 V olts Blower Size/ Motor HP [w] # of Speeds Unit Model Motor Speed From Factor y Manufacturer Recommended Air -Flow Range (Min/Max) CFM ...
Page 14 - AIRFLOW PERFORMANCE—DIRECT DRIVE
AIRFLOW PERFORMANCE—DIRECT DRIVE External Static Pressure—Inches W .C. [kPa] CFM [L/s] Air Deliver y/RPM/W atts—230 V olts Blower Size/ Motor HP [w] # of Speeds Unit Model 120,000 [35.17] Motor Speed From Factor y Med Manufacturer Recommended Air -Flow Range (Min/Max) CFM Motor Speed High CFM 1870 [...
Page 16 - AIRFLOW PERFORMANCE—BELT DRIVE
Air Flow CFM [L/s] Capacity 5 T on [17.6 kW]—13 SEER V oltage 460—3 Phase 2100 [991] 860 615 915 655 955 705 1005 760 1040 820 1090 870 1130 910 1170 950 1210 995 1250 1020 1290 1060 1335 1100 1370 1150 1400 1200 — — 2200 [1038] 895 680 945 735 995 780 1030 830 1060 880 1120 940 1155 980 1195 1020 1...
Page 17 - ELECTRICAL
ELECTRICAL DATA MODEL TGC036C-1K-120 TGC036C-3K-120 TGC036C-4K-120 TGC042C-1K-120 TGC042C-3K-120 TGC042C-4K-120 Unit Information Unit Operating Voltage Range 187-253 187-253 414-506 187-253 187-253 414-506 Minimum Circuit Ampacity 24/24 18/18 11 30/30 21/21 11 Max. Overcurrent Protection Device Size...
Page 18 - UNIT DIMENSIONS
UNIT DIMENSIONSPACKAGE GAS ELECTRIC UNITS TGR036C-TGR060C MODELS BOT TOM VIEW UNIT DIMENSIONS 18 Heat Controller, Inc. -18-
Page 20 - WEIGHTS
Accessory 3-5 Ton [10.6-17.6 kW] Economizer with Single Enthalapy 70 [32] Power Exhaust 19 [9] Fresh Air Damper (Manual) 11 [5] 9 [4] 16 [7] 60 [27] Fresh Air Damper (Motorized) 13 [6] Roof Curb 14" 92 [42] 88 [40] 11 [5] Roof Curb 24" 108 [49] 104 [47] Concentric Diffuser 18" Flush 37 [...
Page 21 - ACCESSORY EQUIPMEN; FIELD INSTALLED; ACCESSORIES
*Voltage 1 = 208/230 VAC-1PH-60HZ 4 = 460 VAC-3PH-60HZ 3 = 208/230 VAC-3PH-60HZ NOTES: ➀ If a particular unit is to be converted to operate on LP (propane) for elevations above 2000 ft. in Canada, the existing Natural Gas to LP Conversion Kits for the subject models already contain the necessary ori...
Page 22 - TYPICAL INSTALLATION; ROOFCURB FOR
ROOFCURBS (Full Perimeter) ■ This roofcurb design can be utilized on 3 through 5 ton models. ■ Two available heights (14" and24" for ALL models. ■ Quick assembly corners for simple and fast assembly. ■ Opening provided in bottom pan to match the “Thru the Curb” electrical connection opening ...
Page 23 - Honeywell; Horizontal or Downflow Applications; ECONOMIZERS; ingle Enthalpy
■ Features Honeywell Analog Controls ■ Field installed accessory ■ Gear Driven Direct Drive Actuator ■ Fully Modulating (0-100%) ■ Low Leakage Dampers ■ Horizontal or Downflow Applications ■ Slip-In Design for Easy Installations ■ Plug-In Polarized 9-pin Electrical Connections ■ Pre-configuring—No F...
Page 24 - POWER EXHAUST KIT
Illustration ST-A0903-01 FRESH AIR DAMPER RKNA 3-5 Ton [10.6-17.6 kW] Models RXRF-FBA1 (Manual)RXRF-FBB1 (Motorized) INTEGRAL POWER EXHAUST FOR ECONOMIZER RXRX-BFF04C— 208/230V-1phase ■ For Honeywell economizer. ■ Downflow or horizontal applications. ■ Requires separate 208-230 volt – 1 PH power sup...
Page 28 - THERMOSTATS GAS/ELECTRIC; RECOMMENDED THERMOSTATS WITH AND W/O ECONOMIZER
THERMOSTATS GAS/ELECTRIC RECOMMENDED THERMOSTATS WITH AND W/O ECONOMIZER Single Stage Cool w/o Economizer Two Stage Cool w/Economizer Maple Chase—Model #0970 Honeywell—Model #T7300-A1005 Honeywell—Model #T8602C Honeywell—Model #T874D-1959 Maple Chase—Model #0960White Rodgers—Model #1F91-59Rober tsha...
Page 35 - Jacks; THE; Design, material, performance data and components
1900 Wellworth Ave Jacks on, Michigan 49203 • Ph. 517-787-2100 • Fax 517-787-9341 THE QU ALIT Y LEADER IN CON D ITIONING AIR www.heatcontroller.com Design, material, performance data and components subject to change without notice. 0 4 / 04/07