Page 2 - Engineering Design Guide; Table of Contents
Engineering Design Guide HBH/V SERIES Heat Controller, Inc. Table of Contents Unit Features ........................................................................................................................................ 2Selection Procedure .....................................................
Page 3 - HB Series
Heat Controller, Inc. HBH/V SERIES Engineering Design Guide HB Series The HBH/V Series exceeds ASHRAE 90.1 efficiencies, and uses R-410A zero ozone depletion refrigerant, making it an extremely environmentally-friendly option. HBH/V is eligible for additional LEED™ (Leadership in Energy and Environm...
Page 4 - Air Flow Correction Table; Cooling Corrections; Reference Calculations; EPT = external pipe thread; Legend and Glossary of Abbreviations; Heating; Selection Procedure
Engineering Design Guide HBH/V SERIES Heat Controller, Inc. To convert Inch-Pound (English) to SI (Metric) Air Flow Correction Table 400 CFM per ton of cooling capacity is nominal rated airflow for all models (bold print) Use multipliers directly with unit data for correcting unit performance at oth...
Page 6 - HEAT CONTROLLER OEM PRICE LIST; Model Structure; Basic Unit Description:; H B H; R-410A refrigerant circuit with high & low; Cabinetry; – Compact design - galvanized steel construction -
Engineering Design Guide HBH/V SERIES Heat Controller, Inc. 7 May, 2009 Page 10 HEAT CONTROLLER OEM PRICE LIST HBH & HBV Model Structure HBH & HBV COMPACT Horizontal & Vertical HFC-410a Units The basic unit price includes sealed heat pump refrigerant circuit and air handler within cabine...
Page 7 - Performance Data; Model
Heat Controller, Inc. HBH/V SERIES Engineering Design Guide Performance Data ARI/ASHRAE/ISO 13256-1 ASHRAE/ARI/ISO 13256-1. English (IP) Units ASHRAE/ARI/ISO 13256-1. Metric (SI) Units Model Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump Cooling 30°C Heating 20°C Cooling 15°C Heat...
Page 21 - Antifreeze Correction Table
Heat Controller, Inc. HBH/V SERIES Engineering Design Guide Antifreeze Correction Table Antifreeze Type Antifreeze % Cooling Heating WPD Corr. Fct. EWT 30°F EWT 90°F EWT 30°F Total Cap Sens Cap Power Htg Cap Power Water 0 1.000 1.000 1.000 1.000 1.000 1.000 Propylene Glycol 5 0.995 0.995 1.003 0.989...
Page 22 - Blower Performance Data
Engineering Design Guide HBH/V SERIES Heat Controller, Inc. Blower Performance Data Standard Unit Airflow in CFM with wet coil and clean air filter Model Fan Speed Rated Airflow Min CFM Airflow (cfm) at External Static Pressure (in. wg) 0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.60 0.7...
Page 24 - Physical Data; Unit Maximum Water Working Pressure
Engineering Design Guide HBH/V SERIES Heat Controller, Inc. Physical Data HB Series 006 009 012 015 018 024 030 036 042 048 060 Compressor (1 Each) Rotary Scroll Factory Charge R410A (oz) 17 18.5 23 32 43 43 47 50 70 74 82 PSC Fan Motor & Blower Fan Motor Type/Speeds PSC/3 PSC/3 PSC-3 PSC/3 PSC/...
Page 25 - Dimensional Data
Heat Controller, Inc. HBH/V SERIES Engineering Design Guide HB - Horizontal Dimensional Data Horizontal Model Overall Cabinet A Width B Length C Height 006 - 012 in cm 19.1 48.5 34.1 86.6 11.1 28.2 015 - 018 in cm 20.1 51.1 43.1 109.5 17.0 43.2 024 - 030 in cm 20.1 51.1 43.1 109.5 18.3 46.5 036 - 04...
Page 26 - LEFT RETURN; Unit Hanger Detail; GC
Engineering Design Guide HBH/V SERIES Heat Controller, Inc. HB - Horizontal Dimensional Data F Right Return Straight Discharge Front L N O M Right Return Front Straight Discharge CSP Back Discharge Condensate 3 / 4" IPT 3.3" [83.8mm] 0.7" [17.8mm] Front-View E D K J 2 1 1.1 [27.9mm] A CA...
Page 29 - Corner Weights for HBH
Heat Controller, Inc. HBH/V SERIES Engineering Design Guide Corner Weights for HBH Series Units Model Total Left-Front* Right-Front* Left-Back* Right-Back* HBH006 Lbs 103 37 24 23 19 kg 46.72 16.78 10.89 10.43 8.62 HBH009 Lbs 105 38 24 23 20 kg 47.63 17.24 10.89 10.43 9.07 HBH012 Lbs 114 42 26 25 21...
Page 30 - Standard Unit; HACR circuit breaker in USA only
Engineering Design Guide HBH/V SERIES Heat Controller, Inc. Electrical Data - Standard Unit HB Model Voltage Code Rated Voltage Voltage Min/ Max Compressor Fan Motor FLA Total Unit FLA Min Circuit Amp Max Fuse/ HACR QTY RLA LRA 006 1 208-230/60/1 197/254 1 3.3 17.7 0.40 3.7 4.5 15 009 1 208-230/60/1...
Page 31 - Electrical Data
Heat Controller, Inc. HBH/V SERIES Engineering Design Guide Electrical Data High Static Blower HB Model Voltage Code Rated Voltage Voltage Min/ Max Compressor Fan Motor FLA Total Unit FLA Min Circuit Amp Max Fuse/ HACR QTY RLA LRA 015 1 208-230/60/1 197/254 1 6.0 29.0 1.00 7.0 8.5 15 8 265/60/1 239/...
Page 32 - Typical Wiring Diagram
Engineering Design Guide HBH/V SERIES Heat Controller, Inc. Typical Wiring Diagram Single Phase HB Units With CXM Controller 31