Page 3 - HBH Series 60Hz Engineering Specifications; Table of Contents
Submittal Data HBH SerieS Heat Controller, Inc. 1 Engineering Design Guide HBH SERIES Heat Controller, Inc. 1 Selection Procedure ................................................................................................................................................................ 2 HBH Ser...
Page 4 - Heating; Air Flow Correction Table; Cooling Corrections; Reference Calculations; FPT = female pipe thread; Legend and Glossary of Abbreviations; Selection Procedure
Heat Controller, Inc. HBH SerieS Submittal Data 2 Heat Controller, Inc. HBH SERIES Engineering Design Guide 2 LWT = EWT - HE GPM x 500 LAT = EAT + HC CFM x1.08 LWT = EWT + HR GPM x 500 LAT (DB) = EAT (DB) - SC CFM x1.08 LC = TC - SC S/T = SCTC Heating Cooling To convert Inch-Pound (English) to SI (M...
Page 6 - Model Nomenclature; Heat Controller OEM Price List; HBH Large Compact Horizontal Units; Basic Unit Description:; • Blower Motor
Heat Controller, Inc. HBH SerieS Submittal Data Heat Controller, Inc. HBH SERIES Engineering Design Guide 4 Model Nomenclature Heat Controller OEM Price List HBH Large Compact Horizontal Units Entering Water Temperature Range: 20 - 120° F (-6. 7 - 48.9° C) Horizontal Sizes 072 - 120 HBH Large Model ...
Page 14 - SCFM
Heat Controller, Inc. HBH SerieS Submittal Data Heat Controller, Inc. HBH SERIES Engineering Design Guide 12 Blower Performance Data HBH072 - Standard Unit All Data is Wet Coil SCFM ESP 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1800 BHP 0.28 0.32 0.35 0.39 0.42 ...
Page 15 - Table Continued on Next Page
Submittal Data HBH SerieS Heat Controller, Inc. Engineering Design Guide HBH SERIES Heat Controller, Inc. 13 Blower Performance Data HBH096 - Standard Unit All Data is Wet Coil SCFM ESP 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 2400 BHP 0.45 0.50 0.54 0.59 0.63 ...
Page 16 - Table Continued from Previous Page
Heat Controller, Inc. HBH SerieS Submittal Data Heat Controller, Inc. HBH SERIES Engineering Design Guide 14 Blower Performance Data HBH096 - Standard Unit SCFM ESP 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 3300 BHP 1.01 1.08 1.14 1.21 1.28 1.33 1.39 1.45 1.51 1...
Page 19 - Unit Maximum Water Working Pressure
Submittal Data HBH SerieS Heat Controller, Inc. Engineering Design Guide HBH SERIES Heat Controller, Inc. 17 HBH Physical Data Model 072 096 120 Compressor Quantity Scroll Number of Circuits (Compressors) 2 Factory Charge R-410a (oz) [kg] per circuit 60 [1.70] 76 [2.15] 80 [2.27] Blower Motor Blower...
Page 20 - DIMENSIONAL DATA TABLE ON NEXT PAGE
Heat Controller, Inc. HBH SerieS Submittal Data Heat Controller, Inc. HBH SERIES Engineering Design Guide 18 HBH072-120 Dimensional Data DIMENSIONAL DATA TABLE ON NEXT PAGE LEFT RETURN STRAIGHT DISCHARGE CAP CAP FRONT BSP A EAP CBP B A O PQ R K M F G E D BSP RIGHT RETURN STRAIGHT DISCHARGE 1 EAP 2 C...
Page 22 - HACR circuit breaker in USA only
Heat Controller, Inc. HBH SerieS Submittal Data Heat Controller, Inc. HBH SERIES Engineering Design Guide 20 HBH Electrical DataStandard HB Model Voltage Code Rated Voltage Voltage Min Max Blower Option Compressor Fan Motor FLA Total Unit FLA Min Circuit Amp Max Fuse/ HACR QTY RLA LRA 072 H 208-3-60...
Page 24 - Heat Controller; HBH Series 60Hz
Heat Controller, Inc. HBH SerieS Submittal Data Heat Controller, Inc. HBH SERIES Engineering Design Guide 22 This product specification document is furnished as a means to copy and paste ClimateMaster product information into a project specification. It is not intended to be a complete list of produ...
Page 25 - certified; Note: If unit fails on any cross check, it shall not be allowed; introduction of glass fibers into the air stream.; Unit insulation must meet these stringent requirements or unit(s); installed mounting brackets.
Submittal Data HBH SerieS Heat Controller, Inc. Engineering Design Guide HBH SERIES Heat Controller, Inc. 23 HBH Series 60Hz Engineering Specifications Page 2 General: Furnish and install the HBH Series as indicated on the plans. Equipment shall be completely assembled, piped and internally wired. C...
Page 26 - Fan and Motor Assembly:; on a wet coil and a clean filter in place.; shall NOT be acceptable.; contractor supplied disconnect switch.
Heat Controller, Inc. HBH SerieS Submittal Data Heat Controller, Inc. HBH SERIES Engineering Design Guide 24 HBH Series 60Hz Engineering Specifications Page 3 Fan and Motor Assembly: All units shall have belt-driven single centrifugal fan. Fan motor shall be permanently lubricated with thermal overl...
Page 27 - g. Condensate overflow electronic protection.; protections will not be accepted.
Submittal Data HBH SerieS Heat Controller, Inc. Engineering Design Guide HBH SERIES Heat Controller, Inc. 25 HBH Series 60Hz Engineering Specifications Page 4 Option: The unit shall be supplied with stainless steel drain pan. Electrical: A control box shall be located within the unit compressor comp...
Page 28 - a. Supply and return hoses having ball valve with PT port.
Heat Controller, Inc. HBH SerieS Submittal Data Heat Controller, Inc. HBH SERIES Engineering Design Guide 26 Hose Kit Assemblies: The following assemblies ship with the valves already assembled to the hose described: a. Supply and return hoses having ball valve with PT port. b. Supply hose having ba...