Summary

Page 3 - For left to; Remove and set aside front panels.

made prior to installing these lines). For left to right applications. 1. Remove and set aside front panels. 2. Remove the coil support bracket (4-screws. 3. Remove horizontal drain pan retaining clip (1-screw). 4. Carefully remove coil assembly and bottom drain pan. 5. Move horizontal drain pan fro...

Page 4 - in; ALWAYS; disconnect

K. CONDENSATE DRAIN The air handler drain pan has ¾” FPT primary and secondary connections whether used in an upflow or horizontal configuration. Piping from each stub is to have a 1½” minimum trap and each run pitched so as to provide for adequate drainage and secondary fittings together into a com...

Page 5 - ELECTRIC HEATER KIT SPECIFICATIONS; MINIMUM CIRCUIT; heat 0

ELECTRIC HEATER KIT SPECIFICATIONS kW@ MINIMUM CIRCUIT AMPACITY MAX. FUSE OR BREAKER (HACR) MODEL USED WITH 240V 208V 240V 208V 240V 208V N/A Without heat 0 0 2.1 1.9 15 15 7800-305B 5.0 3.8 29 25 30 25 7800-306B 8.0 6.0 44 39 45 40 7800-308B HAH1324-00-1A 10 7.5 55 48 60 50 N/A Without heat 0 0 3.5...