Page 2 - Required Tools for Installation; Procedure for Selecting the Location; • Since drain flows out of the outdoor unit,; Clearances of Indoor and Outdoor Units
INSTALLATION PAGE 2 ENGLISH Step 1 - Preparation Required Tools for Installation Procedure for Selecting the Location • Drill • Wire Snipper • Hole Saw 2 3/4” • Vacuum pump • Soap-and-water solution or gas leakage detector • Torque wrench • 17mm, 22mm, 26mm • Tubing cutter • Flaring tool • Razor kni...
Page 3 - Screw the mounting plate to the wall.; Piping Exit Options; Step 2 - Installation of the Indoor Unit
INSTALLATION PAGE 3 ENGLISH 2.1 Step 2.1 Using a stud sensor, locate and mark the stud positions in the wall where the indoor unit is to be mounted. 2.2 Step 2.2 Place the mounting plate on the wall in the desired location taking into account the minimum clearances necessary for proper operation. Us...
Page 4 - Illustration 2; Extension piping to attach to this fitting is field supplied.; Mounting the Indoor Unit Onto the Wall Plate
INSTALLATION PAGE 4 ENGLISH Illustration 2 Illustration 3 2.9 Step 2.9 With the top of the indoor unit closer to the wall, hang the indoor unit on the upper hooks of the mounting plate. Slide the unit slightly side to side to verify proper placement of the indoor unit on the mounting plate. Rotate t...
Page 5 - Step 4 - Interconnecting the Indoor and Outdoor Units
INSTALLATION PAGE 5 ENGLISH Step 4.2 Step 4.1 Step 4.3 Table 1 Step 3.3 Step 3.4 Half union Flare nut Torque wrench Spanner Forced fastening without careful centering maydamage the threads and cause a leakage of gas. Pipe Diameter( ǿ ) Fastening torque Liquid side6.35mm(1/4") 18N.m/13.3Ft.lbs Li...
Page 6 - Hazard of Explosion! Never use an open flame to detect gas; Leak Test; Attach a manifold gauge, micron gauge, and vacuum pump
INSTALLATION PAGE 6 ENGLISH Hazard of Explosion! Never use an open flame to detect gas leaks. Explosive conditions may occur. Use a leak test solution or other approved methods for leak testing. Failure to follow recommended safe leak test procedures could result In death or serious injury or equipm...
Page 7 - This product contains fluorinated greenhouse gases covered; Refrigerant Charge Label; oz; Contains fluorinated greenhouse gases; Are the connecting wirings of indoor and outdoor firmly
INSTALLATION PAGE 7 ENGLISH Illustration 6 It becomes high midway. The gap with the ground is too small There is the bad smell from a sewer It waves. The end is imm- ersed in water. Less than 5cm piping hole. Use a sealant to seal the piping hole opening to prevent weather elements from entering the...
Page 10 - Issued Date: Aug 2016 Update