Contents 2 313840G Contents Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Related Manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 DataTrak Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Installation . . . . . . . . . . . . . . . . ...
Page 3 - DataTrak Kits; Conversion Kits; Replacement Part Kits; Aluminum
DataTrak Kits 313840G 3 DataTrak Kits Conversion Kits Use to add data monitoring capabilities to an existing pump. * Kit includes replacement air valve compatible with solenoid. Replacement Part Kits Aluminum Polypropylene and Conductive Polypropylene Husky 1050 Husky 3300 Diaphragm Pump Material Da...
Page 4 - Installation; Prepare to Install; Install the Kit; WARNING
Installation 4 313840G Installation Prepare to Install 1. Relieve the pressure. Follow instructions in your Operation manual. 2. Disconnect the air line to the pump. Install the Kit 1. Mount the bracket to the wall. Use approximately 3/8 in. bolts or screws. 2. Install the DataTrak module (1) on the...
Page 5 - Check DataTrak Operation
Installation 313840G 5 6. Use the screw provided to attach the reed switch just behind the air inlet. Remove the muffler, if needed, for easier access. Rotate the air inlet fitting as needed so the wrench flat clears the reed switch. 7. Connect the DataTrak cable to the 5-pin connector on the reed s...
Page 6 - DataTrak Controls and Indicators
DataTrak Controls and Indicators 6 313840G DataTrak Controls and Indicators Key AA Runaway Limit, in cycles per minute (user settable; 00=OFF) AB Displacement (user settable) AC Flow Rate Units (user settable to gpm [US], gpm [Imperial], oz/min [US], oz/min [Imperial], l/min, or cc/min) AD LED (faul...
Page 7 - DataTrak Operation; Setup Mode; Runaway
DataTrak Operation 313840G 7 DataTrak Operation NOTE: The display (AE) will turn off after 1 minute to save battery life. Press any key to wake up the display. NOTE: DataTrak is factory set to 685 cc/cycle. This set-ting is accurate for pumping water at a medium speed on a Husky 1050 pump (approxima...
Page 8 - Display
DataTrak Operation 8 313840G NOTE: If the DataTrak does not reset, use a screwdriver to push the solenoid release button on the side of the air valve. 5. If the solenoid doesn’t actuate: a. Close the master air valve to stop the pump. The display will show the Service Component 1 screen. b. See Tabl...
Page 9 - Calibration Procedure
DataTrak Operation 313840G 9 Calibration Procedure 1. Press and hold for 5 seconds until Setup menu appears. 2. Press once. Change flow rate units to cycles/min. 3. Return to Run Screen. Press and hold for three seconds to reset batch totalizer. 4. Dispense fluid from pump into a graduated con-taine...
Page 10 - Table 1: Diagnostic Codes
DataTrak Operation 10 313840G Table 1: Diagnostic Codes Symbol Code Code Name Diagnosis Cause Runaway Pump running faster than set runaway limit. Increased air pressure. Increased fluid output. Exhausted fluid supply. E-3 Low Battery Battery voltage too low to stop runaway. Low battery. Replace batt...
Page 11 - Replace DataTrak Battery or Fuse; Replace Battery
DataTrak Operation 313840G 11 Replace DataTrak Battery or Fuse Replace Battery 1. Unscrew cable from the reed switch assembly. See Fig. 2. 2. Remove DataTrak module from bracket. See Fig. 3. Take module to a non-hazardous location. 3. Remove two screws on back of module to access battery. 4. Disconn...
Page 12 - Replace Fuse
DataTrak Operation 12 313840G Replace Fuse 1. Remove the screw, metal strap, and plastic holder. 2. Pull the fuse away from the board. 3. Replace with a new fuse. * Fig. 4 shows where to find the Series letter. Table 3. Approved Fuses DataTrak Part Number Series* Fuse Required 289822 A or B 24C580 C...
Page 14 - Parts; Conversion Kits, Cycle Count and Runaway Protection
Parts 14 313840G Parts Conversion Kits, Cycle Count and Runaway Protection Husky 1050 - 24B777 (Aluminum), 24B784 (Polypropylene), and 24B793 (Conductive Polypropylene) Husky 3300 - 24K861 (Aluminum) and 24K862 (Polypropylene) ti14052a Aluminum Plastic 1 2 3 4a 4b Aluminum Plastic 6a 6b 6c 6a 6b 6c ...
Page 16 - Conversion Kits, Cycle Count Only
Parts 16 313840G Conversion Kits, Cycle Count Only Husky 1050 and Husky 3300 - 24B794 (Aluminum) and 24B795 (Polypropylene and Conductive Polypropylene) ▲ Replacement Warning labels, signs, tags, and cards are available at no cost. 1 2 3 5a 5b ti14224a Ref. No. Part No. Description Qty 1 ----- DATAT...
Page 17 - Replacement Kits
Parts 313840G 17 Replacement Kits Solenoid/Reed Switch Reed Switch Husky 1050 Husky 3300 Air Valve Material Includes 24B771 24K863 Plastic Reed switch and solenoid (4a), bracket (4c), and fasteners (4b, 4d) 24B772 24K864 Aluminum Husky 1050 or Husky 3300 Air Valve Material Includes 24B796 Plastic Re...
Page 18 - Graco Standard Warranty
All written and visual data contained in this document reflects the latest product information available at the time of publication. Graco reserves the right to make changes at any time without notice. Original instructions.This manual contains English. MM 313840 Graco Headquarters: Minneapolis Inte...