Page 2 - TABLE OF CONTENTS
SG UPS Features. . . . . . . 1 SG Series Online UPS Block Diagram. . . . . 1 Important Safety Instructions (READ FIRST) . . . . 2 Chapter 1. SG Series UPS Overview . . . . . 3 True Regenerative Online Design . . . . 3 Input Power Factor Correction . . . . 3 Microprocessor Control . . . . . 3 SNMP/HT...
Page 3 - Hardwire Input and Output Conneciton
SG SERIES UPS FEATURES SG SERIES ON-LINE UPS SYSTEM BLOCK DIAGRAM Hardwire Input and Output Conneciton True Double Conversion On-Line DesignInput Power Factor CorrectionWide Input Voltage WindowPure Sinewave Output Precision Output Voltage Regulation Superior Brownout, Surge and Transient Protection...
Page 4 - Refer all servicing to Falcon Electric, Inc.; plug this UPS into its own output as this may damage the UPS.; NEVER CONNECT; equipment that; DO NOT; the UPS and the equipment connected to the UPS.; battery
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions which must be followed during the installation,operation and maintenance of this UPS and its batteries. Please read all instructions beforeoperating this equipment and save this manual for future refere...
Page 5 - SG Series UPS - Overview; General - Common for all models; The UPS is shipped; NO BATTERY BACKUP IS PROVIDED AFTER THE GREEN MODE HAS ACTIVATED.
CHAPTER CHAPTER 1 1 SG Series UPS - Overview General - Common for all models 1. Verify the following is included in the UPS shipping carton:(1) UPS, (1) Software Diskette(s) & Manual, (1) Owners Manual & (1) UPS/Computer Cable. 2. Verify the UPS unit is configured for the proper input/output...
Page 6 - Select a suitable location for the UPS.
5. Select a suitable location for the UPS. VERIFY THE FLOOR OR SURFACE SUPPORTING THE UPS WILL SUPPORT THE WEIGHT OF THE UPS AND ANY OPTIONAL EXTENDED BATTERY BANKS. SG2K-2T-HW & SG2K-2T-HW UPS MODELS = 68.4 lbs. (31 kg)SG3K-2T-HW & SG3K-2-HW UPS MODELS = 81.4 lbs. (37 kg) 6. If unattended c...
Page 7 - OUTPUT VOLTAGE 1; SWITCH SETTINGS FOR ALL MODELS
DIP SWITCHES SELECTION TABLE ON = 1 OFF = 0 SW2 SW1 OUTPUT VOLTAGE 1 (All models) OUTPUT VOLTAGE 2 (-TX & -TXC models only) Down Down 208 Vac 115 Vac Down Up 220 Vac (default) 120 Vac Up Down 230 Vac 125 Vac Up Up 240 Vac 130 Vac SW3 FUNCTION Down GREEN MODE ON Up GREEN MODE OFF SWITCH SETTINGS ...
Page 8 - SCREW TORQUE SPECIFICATIONS FOR; CAUTION; CHAPTER; Installation Instructions For Hardwire Models
1.0 UPS Input & Output Requirements. Note: All SG Series hardwire UPS models must be installed by a licensed electrician, in accordance with the National Electrical Code (NEC) ANSI/NFPA70 and all local regulations. It is further required that the input of SG Series hardwireUPS be wired to a buil...
Page 12 - TYPICAL EXTENDED BATTERY BANK & UPS INTERCONNECTION; INSTALLATION PROCEDURE FOR EXTENDED BATTERY BANKS; Reinstall the battery fuse.; Internal battery bank chargers do not charge the UPS batteries.
TYPICAL EXTENDED BATTERY BANK & UPS INTERCONNECTION (Mini-tower models shown; same applies for floor standing banks) INSTALLATION PROCEDURE FOR EXTENDED BATTERY BANKS 1. Remove the battery fuse located on the UPS rear panel. See illustration above. 2. Locate the battery interconnect cable(s). 3....
Page 13 - SG 2-3kVA TOWER EXTENDED BATTERY BANK SELECTION GUIDE
SG 2-3kVA TOWER EXTENDED BATTERY BANK SELECTION GUIDE BATTERY OPTION MODELS W/O Charger SGB2S7-2K3 SGB2S7-2K3 SGB5S7-2K6 SGB2S7-2K3 SGB5S7-2K6 SGB5S7-2K6 BATTERIES 12 Pieces of 12V, 7AH 24 Pieces of 12V, 7AH 30 Pieces of 12V, 7AH 36 Pieces of 12V, 7AH 60 Pieces of 12V, 7AH 90 Pieces of 12V, 7AH BATT...
Page 14 - OPERATION; UPS FRONT PANEL INDICATOR AND FUNCTION KEYS; LOAD LEVEL INDICATOR LEDS; This LED is lit when the unit is operating from battery.
12 CHAPTER CHAPTER 3 3 OPERATION 1 2 3 4 5 6 7 8 9 10 11 UPS FRONT PANEL INDICATOR AND FUNCTION KEYS 1. LOAD LEVEL INDICATOR LEDS *The first or bottom LED is lit when the output load is greater than 25% of the rated output of the UPS. *The second LED is lit when the output load is greater than 50% o...
Page 18 - COMMUNICATIONS INTERFACES; Supported Protocols; UPSILON 2000 & SEC Smart Mon; TX; RX; GEN; GND
CHAPTER CHAPTER 5 5 COMMUNICATIONS INTERFACES RS-232 INTERFACE 16 Pin # Function explanation I/O 9 RS 232 Rx INPUT 6 RS 232 Tx OUTPUT 7 Ground Location: The RS-232 interface is standard on all SG series UPS models. The port is located on the UPS rear panel, via a DB-9 female connector. Supported Pro...
Page 20 - OPTO Board Internal Circuitry
18 PIN ASSIGNMENT FOR THE FALCON UA88373 OPTO-COUPLER OPTION BOARD (no-bypass signal) PIN DESCRIPTION 1 Not Used 2 Utility Loss (N.O.) (Closes upon utility loss) 3 Utility Loss (N.C.) (Opens upon utility loss) 4 Common for pins 2, 3 & 5 5 Low Battery (N.O.) (Closes at low battery) 6 Remote Shutd...
Page 22 - Maintenance & Technical Support; WARNING
CHAPTER CHAPTER 6 6 Maintenance & Technical Support 1. Care & Maintenance Falcon ® SG Series UPSs are designed to be maintenance-free. They can be cleaned with a damp cloth or non-abrasive cleanser, providing the UPS is turned off and the input plug is disconnected from the utility source.On...
Page 23 - Storing the UPS and Batteries; which the receiver is connected.
The following precautions should be observed by a qualified technician when working with batteries. 1. Remove watches, rings, or other metal objects. 2. Use tools with insulated handles. 3. Wear rubber gloves and boots. 4. Do not lay tools or metal parts on top of batteries. 4. Storing the UPS and B...
Page 25 - LIMITED NEW PRODUCT WARRANTY AGREEMENT
GENERAL PROVISIONS FALCON® ELECTRIC INC., hereby warrants product shipped under this agreement to be free from defective workmanship for a period of two yearsfollowing date of shipment. This Limited New Product Warranty Agreement only applies to covered repairs to the product occurring within the Un...
Page 26 - SG Series; TM; UPS PLUS
SG Series TM UPS PLUS ® 2kVA & 3kVA 24 Electrical Input Nominal AC Voltage 120V 230V 120V 230V 230V AC Voltage Range 87 – 140V 170 – 275V 87 – 140V 170 – 275V 170 – 275V Current – Amps 14.2 7.4 21.4 11.2 7.5 11.3 Frequency 50/60 Hz ± 5% (Auto – Tracking) Power Factor Correction > 0.95 Efficie...