Page 2 - TABLE OF CONTENTS
SG UPS Features. . . . . . . 1 SG Series Online UPS Block Diagram. . . . . 1 Important Safety Instructions (READ FIRST) . . . . 2 Chapter 1. SG Series UPS Overview . . . . . 3 True Regenerative Online Design . . . . 3 Input Power Factor Correction . . . . 3 Microprocessor Control . . . . . 3 SNMP/HT...
Page 3 - True Double Conversion On-Line Design
SG SERIES UPS FEATURES SG SERIES ON-LINE UPS SYSTEM BLOCK DIAGRAM True Double Conversion On-Line Design Input Power Factor CorrectionWide Input Voltage WindowPure Sinewave Output Precision Output Voltage Regulation Superior Brownout, Surge and Transient ProtectionInternal System BypassEliminates Gen...
Page 4 - Refer all servicing to Falcon Electric, Inc.; plug this UPS into its own output as this may damage the UPS.; NEVER CONNECT; equipment that; DO NOT; the UPS and the equipment connected to the UPS.
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions which must be followed during the installation,operation and maintenance of this UPS and its batteries. Please read all instructions beforeoperating this equipment and save this manual for future refere...
Page 5 - SG Series UPS - Overview; UPS Plus
CHAPTER CHAPTER 1 1 SG Series UPS - Overview True Regenerative On-Line Design As new and innovative technologies have become the backbone of today's businesses, maximumsystem availability is critical and downtime is more expensive than ever. Increasingly, businessesneed a UPS that not only protects ...
Page 6 - SG RACKMOUNT INSTALLATION INSTRUCTIONS; All Falcon; Flat Head Pan Head
CHAPTER CHAPTER 2 2 SG RACKMOUNT INSTALLATION INSTRUCTIONS 1. Verify the following is included in the UPS shipping carton:* UPS* Software Diskette(s) & Manual *Power Cord* Owners Manual* UPS/Computer Cable* Box containing mounting brackets, handles & mounting hardware* SG2KRM-1TU, SG2KRM-2TU...
Page 7 - NO BATTERY BACKUP IS PROVIDED WHEN IN THIS MODE.; UPS OUT PUT VOLTAGE DIP SWITCH SETTINGS SWITCHES ON UPS REAR PANEL; GREEN MODE
c. Install a suitable shelf capable of supporting the weight of the UPS and batteries intothe equipment rack. Install the shelf so the UPS and battery bank (if required) will sit directly on the surface of the shelf. Lift the UPS onto its rack shelf, slide it into the rack until the UPS front panel ...
Page 8 - BATTERY MODULE INTERCONNECT WIRING
5. For all 1kVA & (-2) 2-3kVA models, connect the power cord to the UPS inlet located on the UPS rear panel. On (-1) 2 & 3Kva models the line cord is permanently attached to the UPS. 6. Connect the power cord(s) for the equipment to be protected to the UPS output receptacles. 7. For all 2 &a...
Page 9 - Plug the UPS power cord into the nearest grounded outlet.; THE UPS WILL RUN FOR ABOUT 30 SECONDS AND SHUTDOWN.
7 8. If unattended computer shutdown and monitoring are desired, connect the green UPS/Computer cable to the DB-9 connector located on the UPS rear panel. Then install the shutdown and monitoring software provided with the UPS. For your reference, UNIX shutdown and monitoring software is available f...
Page 10 - Slide Mounting Details
8 OPTIONAL SLIDE MOUNTING KIT (SGRMKIT) An slide mounting kit option is available from Falcon Electric. The part number for the kitis SGRMKIT and may be installed on any rackmount UPS and battery bank referenced inthis manual. As all 2-3kVA models consist of seperate UPS and battery bank modules, tw...
Page 11 - SG RACKMOUNT EXTENDED BATTERY BANK SELECTION GUIDE
BATTERY OPTION MODEL SG1KRM -1T SGBR2S7-1KU SGBR2S7 -1KU SGBR2S7 -1KU SGBR2S7 -1KU BATTERIES 7AH x 3 7AH x 6 (7AH x 6 ) x 2 (7AH x 6 ) x 3 (7AH x 6 ) x 4 BATTERIES IN UPS Batteries & UPS in same case 7AH x 3 7AH x 3 7AH x 3 7AH x 3 # OF BATTERY CASES UPS 1 2 3 4 RUN TIME @ 100W 54 Min. 220 min. ...
Page 12 - OPERATION; UPS FRONT PANEL INDICATOR AND FUNCTION KEYS; LOAD LEVEL INDICATOR LEDS; This LED is lit when the unit is operating from battery.
10 CHAPTER CHAPTER 3 3 OPERATION 1 2 3 4 5 6 7 8 9 10 11 UPS FRONT PANEL INDICATOR AND FUNCTION KEYS 1. LOAD LEVEL INDICATOR LEDS *The first or bottom LED is lit when the output load is greater than 25% of the rated output of the UPS. *The second LED is lit when the output load is greater than 50% o...
Page 15 - FRONT & REAR PANEL DETAILS; Typical Rear Panel Overview
13 CHAPTER CHAPTER 4 4 FRONT & REAR PANEL DETAILS SG1KRM-1TU Typical Rear Panel Overview SG1KRM-2TU Typical Rear Panel Overview Power Cord Inlet (120Vac only) Input Fuse (15A) Cooling Fan Output Voltage Select Switch RS-232 Port Battery Fuse (30A) Output Receptacles (4) 5-15R Extended Battery Co...
Page 17 - COMMUNICATIONS INTERFACES; Supported Protocols; UPSILON 2000 & SEC Smart Mon; TX; RX; GEN; CAUTION; GND
CHAPTER CHAPTER 5 5 COMMUNICATIONS INTERFACES RS-232 INTERFACE 15 Pin # Function explanation I/O 9 RS 232 Rx INPUT 6 RS 232 Tx OUTPUT 7 Ground Location: The RS-232 interface is standard on all SG series UPS models. The port is located on the UPS rear panel, via a DB-9 female connector. Supported Pro...
Page 19 - OPTO Board Internal Circuitry
17 PIN ASSIGNMENT FOR THE FALCON UA88373 OPTO-COUPLER OPTION BOARD (no-bypass signal) PIN DESCRIPTION 1 Not Used 2 Utility Loss (N.O.) (Closes upon utility loss) 3 Utility Loss (N.C.) (Opens upon utility loss) 4 Common for pins 2, 3 & 5 5 Low Battery (N.O.) (Closes at low battery) 6 Remote Shutd...
Page 20 - Maintenance & Technical Support; WARNING
CHAPTER CHAPTER 6 6 Maintenance & Technical Support 1. Care & Maintenance Falcon ® SG Series UPSs are designed to be maintenance-free. They can be cleaned with a damp cloth or non-abrasive cleanser, providing the UPS is turned off and the input plug is disconnected from the utility source.On...
Page 21 - Storing the UPS and Batteries; receiver is connected.
The following precautions should be observed by a qualified technician when working with batteries. 1. Remove watches, rings, or other metal objects. 2. Use tools with insulated handles. 3. Wear rubber gloves and boots. 4. Do not lay tools or metal parts on top of batteries. 4. Storing the UPS and B...
Page 22 - Technical Support; Your FALCON; Requesting Technical Information or Support; Please send your technical or support questions by email to:; FALCON Web Support; Acrobat .PDF format on our corporate website.
6. Technical Support Your FALCON ® Electric SG Series UPS is backed by one of the finest customer service teams assembled. Write, call, fax or email should you require technical assistance or service. Falcon Electric Inc. 5106 Azusa Canyon RoadIrwindale, CA. 91706Service 800.842.6940Voice 626.962.77...
Page 23 - LIMITED NEW PRODUCT WARRANTY AGREEMENT
21 GENERAL PROVISIONS FALCON® ELECTRIC INC., hereby warrants product shipped under this agreement to be free from defective workmanship for a period of two yearsfollowing date of shipment. This Limited New Product Warranty Agreement only applies to covered repairs to the product occurring within the...
Page 24 - SG Series; TM; UPS PLUS
SG Series TM UPS PLUS ® 1kVA to 3kVA 22 Model Number SG1KRM -1TU SG1KRM -2TU SG2KRM -1TU SG2KRM -2TU SG3KRM -1TU SG3KRM -2TU Nominal VA 1000 2000 3000 Electrical Input Nominal AC Voltage 120V 230V 120V 230V 120V 230V AC Voltage Range 87-140V 170-275V 87-140V 170-275V 87-140V 170-275V Current -Amps 6...