Page 2 - WIRING DIAGRAM
48VFL & 96VFL v1.2 07/13 ■ WIRING DIAGRAM ■ Wiring Precautions: 1. Before wiring, verify the controller label for correct model number and options. 2. For thermocouple input, use the appropriate compensation wire. And note the polarity of input signal. 3. To avoid noise induction, keep input sig...
Page 3 - PROGRAMMING LEVEL PARAMETERS
48VFL & 96VFL v1.2 07/13 ■ PROGRAMMING LEVEL PARAMETERS ■ lst. Prog. Level 2nd. Prog. Level 3rd. Prog. Level 4 th Prog. Level 5 th . Prog. Level + 1. When 2nd Output (Cooling) is not selected, CPb 、 Cti 、 Ctd 、 HYS2 and db parameters are not available. 2. When Pb ≠ 0.0 , HYS1 will be skipped. 3....
Page 4 - PARAMETER DESCRIPTION
48VFL & 96VFL v1.2 07/13 ■ PARAMETER DESCRIPTION : LEVEL Selection Press keys for at least 5 seconds to access Soft Level. Use or key to select programming level. Then press key to enter this level. LEVEL Description SoFt Level PID Level Option Level USER LEVEL CODE DESCRIPTION RANGE Default Set...
Page 6 - tYPE; Time scale for timer alarm.; If A1FU=None, the alarm function is cancelled
48VFL & 96VFL v1.2 07/13 OPTION LEVEL CODE DESCRIPTION RANGE Default Input type selection. tYPE RANGE( ℃ ) RANGE( ℉ ) J -50 ~ 1000 -58 ~ 1832 K -50 ~ 1370 -58 ~ 2498 T -270 ~ 400 -454 ~ 752 E -50 ~ 750 -58 ~ 1382 B 0 ~ 1800 32 ~ 3272 R 0 ~ 1750 32 ~ 3182 S 0 ~ 1750 32 ~ 3182 N -50 ~ 1300 -58 ~ 2...
Page 7 - Code; ALARM TYPE
48VFL & 96VFL v1.2 07/13 If A2FU=None, it means alarm function is cancelled. dif.L, bd.Hi, bd.Lo t.on, t.oFF Alarm 2 mode. Refer to alarm mode section for details none, Stdy, Lath, St.La Controller address. For use with PC RS-485 interface 0 - 255 0 Baud rate. 2.4k=2400bps, 4.8k=4800 bps, 9.6k=9...
Page 9 - SP-HYST; SP; Output; ERROR MESSAGE AND TROUBLESHOOTING
48VFL & 96VFL v1.2 07/13 The controller can also be set to ON/OFF, PI, PD and P control mode. Set Pb = 0 for ON/OFF control mode. Set ti = 0 for PD control mode. Set td = 0 fro PI control mode and ti, td = 0 fro P control mode. The Hysteresis (dead band) for ON/OFF control operates as follows: O...
Page 11 - Controller Overview
48VFL & 96VFL v1.2 07/13 Controller Overview Controller Wiring The controller must be wired before use. The controller’s input, outputs, and AC power are connected via its rear terminals. Refer to the wiring diagram for details. Programming Menus The controller uses a menu-based programming form...
Page 12 - Specifications
48VFL & 96VFL v1.2 07/13 Specifications General Specifications Display Dual 7-segment 4-digit LED: Red digits for Process Variable (PV) and green digits for Setpoint Variable (SV) Display range -1999 to 9999 Indicating accuracy ± (0.2% full scale + 1 digit) Display update rate 4 readings per sec...
Page 14 - Copyright
48VFL & 96VFL v1.2 07/13 Warranty FLIR Systems, Inc. warrants this Extech Instruments brand device to be free of defects in parts and workmanship for one year from date of shipment (a six month limited warranty applies to sensors ...