Emerson Oxymitter 4000- Manuals
Emerson Oxymitter 4000– User Manual, Manual in PDF format online.
Manuals:
User Manual Emerson Oxymitter 4000
Manual Emerson Oxymitter 4000
Summary
Emerson Process ManagementRosemount Analytical Inc.Process Analytic Division 1201 N. Main St.Orrville, OH 44667-0901T (330) 682-9010F (330) 684-4434e-mail: [email protected]://www.processanalytic.com ESSENTIAL INSTRUCTIONS READ THIS PAGE BEFORE PROCEEDING! Rosemount Analytical designs, ...
HIGHLIGHTS OF CHANGES Effective April, 2004 Rev. 4.0 Page Summary Cover Updated revision number and date. Deleted certification data. P-3 through P-14 Added foreign language versions of “Safety Instructions for the Wiringand Installation of this Apparatus”. 1-1 Revised Warning. Revised para. 1-2a to...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management i Hazardous Area Oxymitter 4000 TABLE OF CONTENTS PREFACE............................................................................................................................1 ...
Instruction Manual IB-106-340C Rev. 4.1July 2004 ii Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 6-0 STARTUP AND OPERATION OF HAZARDOUS AREA OXYMITTER 4000WITH LOI........................................................................................
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management iii Hazardous Area Oxymitter 4000 LIST OF ILLUSTRATIONS Figure 1-1. Typical System Package ....................................................................................... 1-2F...
Instruction Manual IB-106-340C Rev. 4.1July 2004 iv Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 Figure 8-10. Fault 8, Low Heater Temp ................................................................................... 8-12Figure 8-11. Fault 9, Hig...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management P-1 Hazardous Area Oxymitter 4000 PREFACE The purpose of this manual is to provide information concerning the components, func-tions, installation and maintenance of the Oxymitter 400...
Instruction Manual IB-106-340C Rev. 4.1July 2004 P-2 Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 IMPORTANT SAFETY INSTRUCTIONS FOR THE WIRING AND INSTALLATION OF THIS APPARATUS The following safety instructions apply specifically to all EU member ...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management P-3 Hazardous Area Oxymitter 4000 BELANGRIJK Veiligheidsvoorschriften voor de aansluiting en installatie van dit toestel. De hierna volgende veiligheidsvoorschriften zijn vooral bedoe...
Instruction Manual IB-106-340C Rev. 4.1July 2004 P-4 Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 VIGTIGT Sikkerhedsinstruktion for tilslutning og installering af dette udstyr. Følgende sikkerhedsinstruktioner gælder specifikt i alle EU-medlemsland...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management P-5 Hazardous Area Oxymitter 4000 BELANGRIJK Veiligheidsinstructies voor de bedrading en installatie van dit apparaat. Voor alle EU lidstaten zijn de volgende veiligheidsinstructies v...
Instruction Manual IB-106-340C Rev. 4.1July 2004 P-6 Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 TÄRKEÄÄ Turvallisuusohje, jota on noudatettava tämän laitteen asentamisessa ja kaapeloinnissa. Seuraavat ohjeet pätevät erityisesti EU:n jäsenvaltiois...
Instruction Manual IB-106-340C Rev. 4.1July 2004 P-8 Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 Wichtig Sicherheitshinweise für den Anschluß und die Installation dieser Geräte. Die folgenden Sicherheitshinweise sind in allen Mitgliederstaaten der...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management P-9 Hazardous Area Oxymitter 4000 IMPORTANTE Norme di sicurezza per il cablaggio e l’installazione dello strumento. Le seguenti norme di sicurezza si applicano specificatamente agli s...
Instruction Manual IB-106-340C Rev. 4.1July 2004 P-10 Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 VIKTIG Sikkerhetsinstruks for tilkobling og installasjon av dette utstyret. Følgende sikkerhetsinstruksjoner gjelder spesifikt alle EU medlemsland og...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management P-13 Hazardous Area Oxymitter 4000 VIKTIGT Säkerhetsföreskrifter för kablage och installation av denna apparat. Följande säkerhetsföreskrifter är tillämpliga för samtliga EU-medlemslä...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management P-15 Hazardous Area Oxymitter 4000 CERAMIC FIBER PRODUCTS MATERIAL SAFETY DATA SHEET JULY 1, 1996 SECTION I. IDENTIFICATION PRODUCT NAME Ceramic Fiber Heaters, Molded Insulation Modul...
Instruction Manual IB-106-340C Rev. 4.1July 2004 P-16 Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 SECTION II. PHYSICAL DATA APPEARANCE AND ODOR Cream to white colored fiber shapes. With or without optional white to gray granular surface coating an...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management P-17 Hazardous Area Oxymitter 4000 SECTION V. HEALTH HAZARD DATA THRESHOLD LIMIT VALUE (See Section III) EFFECTS OF OVER EXPOSURE EYE Avoid contact with eyes. Slightly to moderately i...
Instruction Manual IB-106-340C Rev. 4.1July 2004 P-18 Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 TOXICOLOGY A number of studies on the health effects of inhalation exposure of rats and hamsters are available. Rats wereexposed to RCF in a series o...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management P-19 Hazardous Area Oxymitter 4000 SECTION VII. SPILL OR LEAK PROCEDURES STEPS TO BE TAKEN IF MATERIAL IS RELEASED OR SPILLED Where possible, use vacuum suction with HEPA filters to c...
Instruction Manual IB-106-340C Rev. 4.1July 2004 P-20 Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 SECTION IX. SPECIAL PRECAUTIONS PRECAUTIONS TO BE TAKEN IN HANDLING AND STORING General cleanliness should be followed. The Toxicology data indicate ...
Instruction Manual IB-106-340C Rev. 4.1July 2004 P-22 Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 GENERAL PRECAUTIONS FOR HANDLING AND STORING HIGH PRESSURE GAS CYLINDERS Edited from selected paragraphs of the CompressedGas Association’s “Handbook...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Description and Specifications 1-1 Hazardous Area Oxymitter 4000 SECTION 1 DESCRIPTION AND SPECIFICATIONS 1-1 COMPONENT CHECKLIST OF TYPICALSYSTEM (PACKAGE CONTENTS) A typical Rosemou...
Instruction Manual IB-106-340C Rev. 4.1July 2004 1-2 Description and Specifications Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 2 8 1 4 3 37270007 6 7 o HART Communicator FISHER-ROSEMOUNT TM MAN 4275A00 English October 1994 5 1. Instruction Bullet...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Description and Specifications 1-3 Hazardous Area Oxymitter 4000 When the cell is at operating temperature and there are unequal oxygen concentra-tions across the cell, oxygen ions wi...
Instruction Manual IB-106-340C Rev. 4.1July 2004 1-4 Description and Specifications Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 For systems with one or two Hazardous Area Oxymitter 4000 units per combustionprocess, an optional remote mounted SPS40...
Instruction Manual IB-106-340C Rev. 4.1July 2004 1-6 Description and Specifications Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 (d) Optional IMPS 4000. The Pro- grammable Logic Controller (PLC)in the IMPS 4000 provides faultindications using flash...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Description and Specifications 1-9 Hazardous Area Oxymitter 4000 A source of instrument air is optional at the Hazardous Area Oxymitter 4000 forreference air use. Since the unit can b...
Instruction Manual IB-106-340C Rev. 4.1July 2004 1-10 Description and Specifications Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 1-6 PROBE OPTIONS a. Flame Arrestor Ceramic Diffusion Assembly The flame arrestor ceramic diffusion as- sembly, Figure...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Description and Specifications 1-11 Hazardous Area Oxymitter 4000 VIEW A VIEW B A B A B 15 o 2 .187 1 ON INSIDE BREAK FOR SMOOTH ROUNDED EDGE ON BOTH ENDS OF CHAMFER .187 6.00 125 .45...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Description and Specifications 1-13 Hazardous Area Oxymitter 4000 Power Requirements: Probe Heater...................................... 175 W nominal Electronics........................
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Installation 2-1 Hazardous Area Oxymitter 4000 SECTION 2 INSTALLATION The Hazardous Area Oxymitter 4000and probe abrasive shield are heavy.Use proper lifting and carrying proce-dures ...
Instruction Manual IB-106-340C Rev. 4.1July 2004 2-2 Installation Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 CO VER REMO V A L & A CCESS 305 305 (12) (12) ADD T O DI M “A ” FOR PR OBE W IT H CERAMI C DI FFUSER 95 ( 3 .8 ) WI T H SNUBBER DI FF...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Installation 2-3 Hazardous Area Oxymitter 4000 ( ) 56.0 2.21 ( ) 164.6 6.48 246.9 9.72 ( ) 84.6 3.33 ( ) 62.0 (2.44) DIA. 189.8 7.47 ( ) 140.2 5.52 ( ) 66.5 2.62 ( ) 93.5 ( ) 3.68 PIP...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Installation 2-5 Hazardous Area Oxymitter 4000 22.5 o B C 8 THREADED HOLES EQUALL Y S PACED ON D DIA B.C. ABRASIVE SHIELD FLANGE O.D. A A TABLE V. MOUNTING PLA TE DIMENSIONS FOR HAZAR...
Instruction Manual IB-106-340C Rev. 4.1July 2004 2-6 Installation Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 NOTE: ALL MASONRY STACK WORK AND JOINTS EXCEPT ADAPTOR PLATE NOT FURNISHED BY ROSEMOUNT. INSTALLATION FOR MASONRY WALL STACK CONSTRUCTION...
Instruction Manual IB-106-340C Rev. 4.1July 2004 2-8 Installation Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 P S U E I T P I C R H W E N T H G C K E N I - E E R W A V I S O L P - X O M T A G NI N - R I T L A I VE - E E H GAS CAL. DRIPLOOP LOGIC I...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Installation 2-9 Hazardous Area Oxymitter 4000 To meet the Safety Requirements ofIEC 1010 (EC requirement), and ensuresafe operation of this equipment, con-nection to the main electri...
Instruction Manual IB-106-340C Rev. 4.1July 2004 2-12 Installation Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 TYPE KTHERMOCOUPLESIGNAL HEATER POWER(BELOW COVER) OXYGEN SIGNAL + + - - TERMINALBLOCK GROUND LUGS 37270023 LINE VOLTAGE 4-20 mA SIGNAL ...
Instruction Manual IB-106-340C Rev. 4.1July 2004 2-14 Installation Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 If using an IMPS 4000 or an SPS 4000,install it in a non-hazardous, explosive-free environment. 2. Calibration Handshake/Logic I/O. The ...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Installation 2-15 Hazardous Area Oxymitter 4000 37270008 REF AIR SET 263C152G01 1 FLOWMETER 0.006-0.057 SCMH (0.2-2.0 SCFH) 771B635H02 2 PRESSURE GAGE 0-103 KPA GAGE (0-15 PSIG) 27543...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Configuration with Keypad 3-1 Hazardous Area Oxymitter 4000 SECTION 3 CONFIGURATION OF HAZARDOUS AREA OXYMITTER 4000 WITH MEMBRANE KEYPAD Install all protective equipment coversand sa...
Instruction Manual IB-106-340C Rev. 4.1July 2004 3-2 Configuration with Keypad Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 c. Verify Hazardous Area Oxymitter 4000 Configuration Located on the microprocessor board, the top board, are two switches t...
Instruction Manual IB-106-340C Rev. 4.1July 2004 3-4 Configuration with Keypad Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 The HART option is not protected byenergy limiting barriers. It must not beinterfaced from within the hazardousarea. The 4-2...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Configuration with Keypad 3-5 Hazardous Area Oxymitter 4000 3-3 RECOMMENDED CONFIGURATION a. 4-20 mA Signal Upon Critical Alarm Rosemount recommends that the factory default be utiliz...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Configuration with LOI 4-1 Hazardous Area Oxymitter 4000 SECTION 4 CONFIGURATION OF HAZARDOUS AREA OXYMITTER 4000 WITH LOI Install all protective equipment coversand safety ground lea...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Configuration with LOI 4-3 Hazardous Area Oxymitter 4000 f. Once the cell is up to operating tempera- ture, the O 2 percentage can be read: 1. To access TP5 and TP6 under the LOI modu...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Startup and Operation with Keypad 5-1 Hazardous Area Oxymitter 4000 SECTION 5 STARTUP AND OPERATION OF HAZARDOUS AREA OXYMITTER 4000 WITH MEMBRANE KEYPAD 5-1 POWER UP a. Startup Displ...
Instruction Manual IB-106-340C Rev. 4.1July 2004 5-2 Startup and Operation with Keypad Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 d. Keypad The five membrane keys on the membrane keypad are only used during calibration toadjust the high and low g...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Startup and Operation with LOI 6-1 Hazardous Area Oxymitter 4000 SECTION 6 STARTUP AND OPERATION OF HAZARDOUS AREA OXYMITTER 4000 WITH LOI 6-1 POWER UP a. Startup Display When power i...
Instruction Manual IB-106-340C Rev. 4.1July 2004 6-2 Startup and Operation with LOI Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 LCD DISPLAY WINDOW SELECTION ARROWS SELECTION ARROW 37260054 SELECTION ARROW TOUCH CONFIRMATION LED Figure 6-3. LOI Fea...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Startup and Operation with LOI 6-3 Hazardous Area Oxymitter 4000 6-5 LOI MENU TREE This LOI menu for the Oxymitter 4000 is shownin Figure 6-4. This menu tree is specific to theOxymitt...
Instruction Manual IB-106-340C Rev. 4.1July 2004 6-4 Startup and Operation with LOI Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 SYSTEM O2 Gas 1 O2 Gas 2 O2-Reset Vals O2 O2 Cal Intervl O2- Gas Time Purge Time _____% _____% ____H ___Sec. Yes/No Yes...
Instruction Manual IB-106-340C Rev. 4.1July 2004 6-6 Startup and Operation with LOI Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 d. SYSTEM/Status 1. Alarms – Diagnostic alarms. See Section 8, TROUBLESHOOTING. 2. PID Parameter – Displays the line vo...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Startup and Operation with LOI 6-7 Hazardous Area Oxymitter 4000 6-8 OXYMITTER 4000 TEST POINTS Refer to Figure 6-6. System test points arelocated on the board below the LOI module.Te...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management HART/AMS 7-1 Hazardous Area Oxymitter 4000 SECTION 7 HART/AMS The HART option is not protected byenergy limiting barriers. It must not beinterfaced from within the hazardousarea. The ...
Instruction Manual IB-106-340C Rev. 4.1July 2004 7-2 HART/AMS Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 a. Method 1, For Load Resistance ≥ 250 Ohms Refer to Figure 7-1 and the following steps to connect the HART Communicator to asignal line 250 ...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management HART/AMS 7-3 Hazardous Area Oxymitter 4000 LOOP CONNECTORS USE INTERFACE00275 0013 ONLY SERIAL PORT & BATTERYCHARGER MUSTNOT BE USED INHAZARDOUS AREAS SERIAL PORT AC L1 AC N + + -...
Instruction Manual IB-106-340C Rev. 4.1July 2004 7-4 HART/AMS Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 7-5 LOGIC I/O CONFIGURATIONS The Hazardous Area Oxymitter 4000 logic I/Ooutput can be configured for ten different modesthrough HART/AMS. The...
Instruction Manual IB-106-340C Rev. 4.1July 2004 7-8 HART/AMS Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 7-7 HART COMMUNICATOR O 2 CAL METHOD Use the following procedure to perform acalibration using the HART Communicator. Ifnecessary, use the me...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Troubleshooting 8-1 Hazardous Area Oxymitter 4000 SECTION 8 TROUBLESHOOTING 8-1 OVERVIEW While the Hazardous Area Oxymitter 4000electronics provides a significant number ofdiagnostic ...
Instruction Manual IB-106-340C Rev. 4.1July 2004 8-2 Troubleshooting Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 d. When flowing calibration gasses, the raw cell millivolt value at test points 1 and 2should represent the levels on the chart inFigu...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Troubleshooting 8-3 Hazardous Area Oxymitter 4000 8-4 ALARM CONTACTS a. If autocalibration is not utilized, a common bi-directional logic contact is provided forany of the diagnostic ...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Troubleshooting 8-5 Hazardous Area Oxymitter 4000 Alarms O2 T/C Open LOI KEYPAD DIAGNOSTIC ALARMS TEST POINTS HEATER T/C HEATER O2 CELL CALIBRATION CALIBRATION RECOMMENDED O2 CELL mV ...
Instruction Manual IB-106-340C Rev. 4.1July 2004 8-8 Troubleshooting Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 DIAGNOSTIC ALARMS TEST POINTS HEATER T/C HEATER O2 CELL CALIBRATION CALIBRATION RECOMMENDED O2 CELL mV + O2 CELL m - HEATER T/C + HEAT...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Troubleshooting 8-13 Hazardous Area Oxymitter 4000 Alarms O2 Temp Hi LOI KEYPAD DIAGNOSTIC ALARMS TEST POINTS HEATER T/C HEATER O2 CELL CALIBRATION CALIBRATION RECOMMENDED O2 CELL mV ...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Troubleshooting 8-15 Hazardous Area Oxymitter 4000 Alarms O2 Cell Bad LOI KEYPAD DIAGNOSTIC ALARMS TEST POINTS HEATER T/C HEATER O2 CELL CALIBRATION CALIBRATION RECOMMENDED O2 CELL mV...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Troubleshooting 8-17 Hazardous Area Oxymitter 4000 DIAGNOSTIC ALARMS TEST POINTS HEATER T/C HEATER O2 CELL CALIBRATION CALIBRATION RECOMMENDED O2 CELL mV + O2 CELL mv - HEATER T/C + H...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Troubleshooting 8-19 Hazardous Area Oxymitter 4000 DIAGNOSTIC ALARMS TEST POINTS HEATER T/C HEATER O2 CELL CALIBRATION CALIBRATION RECOMMENDED O2 CELL mV + O2 CELL mv - HEATER T/C + H...
Instruction Manual IB-106-340C Rev. 4.1July 2004 8-20 Troubleshooting Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 8-6 HAZARDOUS AREA OXYMITTER 4000PASSES CALIBRATION, BUT STILLREADS INCORRECTLY There are a few fault conditions where no alarmindica...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Troubleshooting 8-21 Hazardous Area Oxymitter 4000 3. Always note the time it takes for the cell to recover to the normal processvalue after the cal gas is removed. Asthe diffuser plu...
Instruction Manual IB-106-340C Rev. 4.1July 2004 9-0 Maintenance and Service Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 Calibration Record For Rosemount Analytical In Situ O 2 Probe Probe Serial Number: Probe Tag Number: Probe Location: Date Plac...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Maintenance and Service 9-1 Hazardous Area Oxymitter 4000 SECTION 9 MAINTENANCE AND SERVICE 9-1 OVERVIEW This section identifies the calibration methodsavailable and provides the proc...
Instruction Manual IB-106-340C Rev. 4.1July 2004 9-4 Maintenance and Service Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 SW2 DIP SWITCH HART LOCAL 0-10% 0-25% 4mA 20mA NOT USED NOT USED LED HEATER O2 CELL CALIBRATION HEATER T/C STATUS OPEN SHORTED...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Maintenance and Service 9-5 Hazardous Area Oxymitter 4000 calibration). If the slope or theconstant is out of specifica-tion, a diagnostic alarm LEDwill be flashing. The diagnos-tic a...
Instruction Manual IB-106-340C Rev. 4.1July 2004 9-6 Maintenance and Service Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 4. Touch the Enter arrow to start the Gas 2 flow. The timer is activated and theLOI displays: Flow Gas 2 xxxxsRead Gas 2xxxxsD...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Maintenance and Service 9-7 Hazardous Area Oxymitter 4000 9-4 HAZARDOUS AREA OXYMITTER 4000REPAIR Each of the following procedures details how toremove and replace a specific componen...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Maintenance and Service 9-9 Hazardous Area Oxymitter 4000 37270005 17A 11 15 17 2 Note: The Electronic Assembly, item 2, consists of items 3 through 10. 1 23 1A 4A REMOTE ELECTRONICS ...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Maintenance and Service 9-11 Hazardous Area Oxymitter 4000 J8 POWER SUPPLY BOARD 37270022 Figure 9-6. J8 Connector 3. Loosen the three captive screws (9, Figure 9-3 or Figure 9-4). Sl...
Instruction Manual IB-106-340C Rev. 4.1July 2004 9-12 Maintenance and Service Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 Opening the electronic housing willcause the loss of ALL hazardous per-mits. Opening the electronics housingin a hazardous ar...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Maintenance and Service 9-13 Hazardous Area Oxymitter 4000 15. Replace right housing cover (1, Figure 9-3); make sure it is tight. Secure thecover using captive washer (20), coverlock...
Instruction Manual IB-106-340C Rev. 4.1July 2004 9-14 Maintenance and Service Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 27540007 WIRE LOOP CERAMIC SUPPORT ROD CELL FLANGE HEATER CERAMIC DIFFUSER ASSEMBLY V-DEFLECTOR Figure 9-8. Heater Strut Asse...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Maintenance and Service 9-15 Hazardous Area Oxymitter 4000 When working on this equipment onthe laboratory bench, be aware thatthe Hazardous Area Oxymitter 4000,probe tube, and flame ...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Maintenance and Service 9-17 Hazardous Area Oxymitter 4000 12. If previously removed, install the entire electronics per paragraph 9-4b, steps4 and 5. 13. Follow the instructions in p...
Instruction Manual IB-106-340C Rev. 4.1July 2004 9-18 Maintenance and Service Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 diffusion element into seat. Do notget any cement on upper part ofceramic diffusion element. Ensurecomplete penetration of ce...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Return of Material 10-1 Hazardous Area Oxymitter 4000 SECTION 10 RETURN OF MATERIAL 10-1 If factory repair of defective equipment isrequired, proceed as follows: a. Secure a return au...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Replacement Parts 11-1 Hazardous Area Oxymitter 4000 SECTION 11 REPLACEMENT PARTS Table 11-1. Replacement Parts for Probe Figure andIndex No. Part Number Description (Dust Seal) (No D...
Instruction Manual IB-106-340C Rev. 4.1July 2004 11-2 Replacement Parts Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 Table 11-1. Replacement Parts for Probe (Continued) Figure andIndex No. Part Number Description 4849B94G07 JIS High Sulfur/HCl Resi...
Instruction Manual IB-106-340C Rev. 4.1July 2004 11-4 Replacement Parts Rosemount Analytical Inc. A Division of Emerson Process Management Hazardous Area Oxymitter 4000 Table 11-2. Replacement Parts for Electronics Figure andIndex No. Part Number Description 9-3, 1, 17 5R10145G01 Cover, Blind 9-3, 1...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Optional Accessories 12-1 Hazardous Area Oxymitter 4000 SECTION 12 OPTIONAL ACCESSORIES HART HANDHELD 375 COMMUNICATOR The HART Handheld 375 Communicator is an interface devicethat pr...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Optional Accessories 12-3 Hazardous Area Oxymitter 4000 O 2 CALIBRATION GAS Rosemount Analytical’s O 2 Calibration Gas and Service Kits have been carefully designed to provide a more ...
Instruction Manual IB-106-340C Rev. 4.1 July 2004 Rosemount Analytical Inc. A Division of Emerson Process Management Optional Accessories 13-1 Hazardous Area Oxymitter 4000 SECTION 13 INDEX This index is an alphabetized listing of parts, terms, and procedures having to do with theHazardous Area Oxym...
3727 3732/07-04 WARRANTY Rosemount warrants that the equipment manufactured and sold by it will, upon shipment, be freeof defects in workmanship or material. Should any failure to conform to this warranty becomeapparent during a period of one year after the date of shipment, Rosemount shall, upon pr...
Instruction Manual IB-106-340C Rev. 4.1July 2004 © Rosemount Analytical Inc. 2003 Hazardous Area Oxymitter 4000 Emerson Process ManagementRosemount Analytical Inc.Process Analytic Division 1201 N. Main St.Orrville, OH 44667-0901T (330) 682-9010F (330) 684-4434E [email protected] ASIA - PACI...
Emerson Manuals
-
Emerson LD195EM8
User Manual
-
Emerson EWR20V4
User Manual
-
Emerson EWR20V4
Manual
-
Emerson SLC195EM8
User Manual
-
Emerson SLC195EM8
Manual
-
Emerson CR202EM9
User Manual
-
Emerson HD14070
User Manual
-
Emerson RLC320EM9
User Manual
-
Emerson LC320EM9
User Manual
-
Emerson LC320EM9
Manual
-
Emerson PD6922
User Manual
-
Emerson PD6922
Manual
-
Emerson EPT427D
User Manual
-
Emerson EPT427D
Manual
-
Emerson 400 VMC
User Manual
-
Emerson 400 VMC
Manual
-
Emerson CF960CK
User Manual
-
Emerson MICRO MOTION 2700
Installation Manual
-
Emerson CF787AP00
User Manual
-
Emerson CF787AP00
Manual