Page 2 - pertinent information.; WARNING; Educational Services; Emerson Process Management
Instruction Manual D103367X012 83000 Valve December 2014 2 WARNING Always wear protective gloves, clothing and eyewear when performing any installation operations to avoid personal injury.Personal injury or property damage caused by sudden release of pressure or bursting of pressure retaining parts ...
Page 3 - Instruction Manual; Maintenance; performing any maintenance operations:; Installation; guidelines shown below.
Instruction Manual D103367X012 83000 Valve December 2014 3 Maintenance WARNING Avoid personal injury and property damage from sudden release of process pressure or bursting of parts. Before performing any maintenance operations: D Do not remove the actuator from the valve while the valve is still pr...
Page 4 - Air Piping; to the 1/4 NPT in the lower diaphragm case. See figures 4 and 5.; Flow Direction; body bowl, Port A to port B. See figure 2 for port identification.; Use Flow to Open: Port B to A; In vacuum applications, vacuum on down stream.; Disassembly; relieve process pressure.
Instruction Manual D103367X012 83000 Valve December 2014 4 WARNING To avoid personal injury or property damage, do not attempt to do any work on a valve while the system is in operation, the valve must be isolated 100% from the active system and the isolated line voided of pressure and/or hazardous ...
Page 5 - Lapping Sealing Surfaces; the bonnet with a wrench until there is metal-to-metal contact.; Valve Body to Bonnet Assembly; CAUTION
Instruction Manual D103367X012 83000 Valve December 2014 5 3. Remove the O-ring (key 15) and diaphragm (key 5). Wipe with a clean soft cloth and examine for wear.4. Inspect the valve body sealing surfaces. Refer to the Lapping the Valve Seat procedure in this instruction manual. Lapping Sealing Surf...
Page 6 - Note; Parts Ordering; using the following parts tables.; Use only genuine Fisher
Instruction Manual D103367X012 83000 Valve December 2014 6 1. For an air-to-retract actuator (air-to-open/fail closed). Apply 6.9 bar (100 psi) air pressure (or N2) to the normal valve inlet A. Apply 0.2 bar (3.2 psi) air signal to the actuator. Add 0.07 bar (1 psi) signal to the actuator if the inl...
Page 7 - Figure 3. 83000 with Stem Adaptor for Baumann 32 Actuator
Instruction Manual D103367X012 83000 Valve December 2014 7 Figure 2. 83000 for Baumann 16 Actuator E1332 SEE DETAIL IN FIGURE 3 PORT B PORT A Figure 3. 83000 with Stem Adaptor for Baumann 32 Actuator E1333
Page 8 - Table 1. Common Parts
Instruction Manual D103367X012 83000 Valve December 2014 8 Table 1. Common Parts KEY NUMBER QUANTITY DESCRIPTION PART NUMBER Baumann 16 Actuator Baumann 32 Actuator 1 1 Valve Body Refer to table 2 2 1 Bonnet Yoke 81305 3 1 Piston Subassembly 81188 4* 1 Bearing Cartridge Subassembly 81180-2 5* 1 Clos...
Page 10 - Figure 8. Baumann 83000 - Rotated View to Show Locking Bolts; FIELDVUE DVC6000 Digital Valve Controller
Instruction Manual D103367X012 83000 Valve December 2014 10 Figure 8. Baumann 83000 - Rotated View to Show Locking Bolts E1334 NORMAL FLOW DIRECTION PREFERRED MOUNTING (for outlet drain) PORT B Figure 9. Valve Body Subassembly E1335 96 (3.79) mm (inch) Figure 10. 83000 with Baumann 16 Actuator and F...
Page 11 - Figure 12. Baumann 16 Actuator with FIELDVUE; Figure 13. Baumann 16 Actuator with FIELDVUE
Instruction Manual D103367X012 83000 Valve December 2014 11 Figure 11. Baumann 16 Actuator with Fisher 3660/3661 Positioner and 67CFR Airset E1331 3660/3661 POSITIONER 93 (3.7) 159 ( 4 6.25) 129 (5.1) 39 (1.6) 67CFR 146 (5.76) 125 (4.9) mm (inch) Figure 12. Baumann 16 Actuator with FIELDVUE DVC2000 ...
Page 12 - Table 4. Baumann Actuator Weights
Instruction Manual D103367X012 83000 Valve December 2014 12 Table 3. Baumann 83000 Valve Weight VALVE SIZE: 12.7 mm (NPS 1/2) kg lbs 1.82 4 Table 4. Baumann Actuator Weights BAUMANN 16 BAUMANN 32 kg lbs kg lbs 2.1 4.6 4.5 10 Emerson Process ManagementMarshalltown, Iowa 50158 USASorocaba, 18087 Brazi...