Wall-Mounted Dewpoint Sensor Product Information Sheet 210-2002 E2 Actions Menu for Selected Input 2. Highlight the input-point the sensor is attached to and press (SETUP) to set up the input, or press to open the Actions Menu and select 5 (Setup). (If using an Einstein, select an input point an...
Wall-Mounted Dewpoint Sensor Product Information Sheet 210-2002 • Set the Low End Point field to 0. • Set the HighEnd Point field to 5.0. • Set the Low Eng. Units field to 0. • Set the High Eng. Units field to 80. • Set the Low End Limit field to -0.5. • Set the HighEnd Limit field to 6.5. REFLECS 1...
Wall-Mounted Dewpoint Sensor Product Information Sheet 210-2002 7. Set Gain to 16, Offset to 0 (the default) and enter degrees fahrenheit units into the Eng. Unit field (for example, type DEGF). 8. To check the sensor input value, press 0 to go back to the Sensor Control screen and select 1 -Status....
Manual Emerson 210-2002
Summary
Wall-Mounted Dewpoint Sensor Product Information Sheet 210-2002 E2 Actions Menu for Selected Input 2. Highlight the input-point the sensor is attached to and press (SETUP) to set up the input, or press to open the Actions Menu and select 5 (Setup). (If using an Einstein, select an input point an...
Wall-Mounted Dewpoint Sensor Product Information Sheet 210-2002 • Set the Low End Point field to 0. • Set the HighEnd Point field to 5.0. • Set the Low Eng. Units field to 0. • Set the High Eng. Units field to 80. • Set the Low End Limit field to -0.5. • Set the HighEnd Limit field to 6.5. REFLECS 1...
Wall-Mounted Dewpoint Sensor Product Information Sheet 210-2002 7. Set Gain to 16, Offset to 0 (the default) and enter degrees fahrenheit units into the Eng. Unit field (for example, type DEGF). 8. To check the sensor input value, press 0 to go back to the Sensor Control screen and select 1 -Status....