Page 2 - Wall-Mounted Dewpoint Sensor; Product Information Sheet; E2 Actions Menu for Selected Input

Wall-Mounted Dewpoint Sensor Product Information Sheet 210-2002 E2 Actions Menu for Selected Input 2. Highlight the input-point the sensor is attached to and press  (SETUP) to set up the input, or press  to open the Actions Menu and select 5 (Setup). (If using an Einstein, select an input point an...

Page 3 - REFLECS; Analog Input Screen - Set Sensor Properties

Wall-Mounted Dewpoint Sensor Product Information Sheet 210-2002 • Set the Low End Point field to 0. • Set the HighEnd Point field to 5.0. • Set the Low Eng. Units field to 0. • Set the High Eng. Units field to 80. • Set the Low End Limit field to -0.5. • Set the HighEnd Limit field to 6.5. REFLECS 1...

Page 4 - Set Up Zero Calibration

Wall-Mounted Dewpoint Sensor Product Information Sheet 210-2002 7. Set Gain to 16, Offset to 0 (the default) and enter degrees fahrenheit units into the Eng. Unit field (for example, type DEGF). 8. To check the sensor input value, press 0 to go back to the Sensor Control screen and select 1 -Status....

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5

Summary

Page 2 - Wall-Mounted Dewpoint Sensor; Product Information Sheet; E2 Actions Menu for Selected Input

Wall-Mounted Dewpoint Sensor Product Information Sheet 210-2002 E2 Actions Menu for Selected Input 2. Highlight the input-point the sensor is attached to and press  (SETUP) to set up the input, or press  to open the Actions Menu and select 5 (Setup). (If using an Einstein, select an input point an...

Page 3 - REFLECS; Analog Input Screen - Set Sensor Properties

Wall-Mounted Dewpoint Sensor Product Information Sheet 210-2002 • Set the Low End Point field to 0. • Set the HighEnd Point field to 5.0. • Set the Low Eng. Units field to 0. • Set the High Eng. Units field to 80. • Set the Low End Limit field to -0.5. • Set the HighEnd Limit field to 6.5. REFLECS 1...

Page 4 - Set Up Zero Calibration

Wall-Mounted Dewpoint Sensor Product Information Sheet 210-2002 7. Set Gain to 16, Offset to 0 (the default) and enter degrees fahrenheit units into the Eng. Unit field (for example, type DEGF). 8. To check the sensor input value, press 0 to go back to the Sensor Control screen and select 1 -Status....