Page 2 - Quick Installation Guide; WARNING; Explosions could result in death or serious injury:; is applied to the unit.; Process leaks may cause harm or result in death.; cause electrical shock.; IMPORTANT NOTICE
Quick Installation Guide 00825-0100-4593, Rev BA July 2009 Rosemount 1151 2 WARNING Explosions could result in death or serious injury: Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and pra...
Page 3 - TEP; Liquid Flow Applications; Flow
Quick Installation Guide 00825-0100-4593, Rev BAJuly 2009 Rosemount 1151 3 S TEP 1: M OUNT THE T RANSMITTER A. Applications Liquid Flow Applications 1. Place taps to the side of the line.2. Mount beside or below the taps. Gas Flow Applications 1. Place taps in the top or side of the line.2. Mount be...
Page 4 - B. Optional Mounting Brackets; Pipe Mount; Flat Mount
Quick Installation Guide 00825-0100-4593, Rev BA July 2009 Rosemount 1151 4 S TEP 1 CONTINUED ... B. Optional Mounting Brackets When installing the transmitter to one of the optional mounting brackets, torque the bracket bolts to 125 in.-lbs. (0,9 N-m). Pipe Mount Panel Mount (1) (1) Panel bolts are...
Page 5 - that is designed for its specific flange adapter, as shown below.
Quick Installation Guide 00825-0100-4593, Rev BAJuly 2009 Rosemount 1151 5 S TEP 1 CONTINUED ... C. O-rings with Flange Adapters WARNING Whenever the flanges or adapters are removed, visually inspect the o-rings. Replace them if there are any signs of damage, such as nicks or cuts. If you replace th...
Page 6 - To improve field access or to better view the optional LCD display:; NOTE; Housing Lock Nut
Quick Installation Guide 00825-0100-4593, Rev BA July 2009 Rosemount 1151 6 S TEP 2: C ONSIDER H OUSING R OTATION To improve field access or to better view the optional LCD display: 1. Loosen the housing lock nut. 2. Rotate the housing clockwise to the desired position – up to 90° from its original ...
Page 7 - Use the following steps to wire the transmitter:; Figure 1. Field Wiring Diagram; than the conduit connections and the transmitter housing.; Power
Quick Installation Guide 00825-0100-4593, Rev BAJuly 2009 Rosemount 1151 7 S TEP 3: C ONNECT THE W IRING AND P OWER U P Use the following steps to wire the transmitter: 1. Remove the housing cover on the side marked TERMINALS on the nameplate. 2. Connect the positive lead to the “+” terminal and the...
Page 8 - Power Supply; Figure 2. Load Limitation; Code; at Supply Voltage (V
Quick Installation Guide 00825-0100-4593, Rev BA July 2009 Rosemount 1151 8 S TEP 3 CONTINUED ... Power Supply The dc power supply should provide power with less than two percent ripple. The total resistance load is the sum of the resistance of the signal leads and the load resistance of the control...
Page 9 - Failure Mode Alarm Switch; Figure 3. Switch Locations
Quick Installation Guide 00825-0100-4593, Rev BAJuly 2009 Rosemount 1151 9 S TEP 4: C ONFIGURE THE T RANSMITTER Failure Mode Alarm Switch 1. Remove the housing cover.2. Locate the failure mode switch (see Figure 3).3. Move the switch to the desired alarm setting. To set the failure mode to high alar...
Page 10 - Function
Quick Installation Guide 00825-0100-4593, Rev BA July 2009 Rosemount 1151 10 S TEP 5: C ALIBRATE THE T RANSMITTER Verify Transmitter Configuration NOTE: A check ( ✓ ) indicates the basic configuration parameters. At minimum, these parameters should be verified as part of the configuration and startu...
Page 11 - Configure LCD Display; Note that the decimal point wraps around.; Options; Retaining Ring
Quick Installation Guide 00825-0100-4593, Rev BAJuly 2009 Rosemount 1151 11 S TEP 5 CONTINUED ... Configure LCD Display Figure 4. Sample 1151 LCD Display NOTE The LCD display time-out is approximately 16 seconds. If keys are not pressed within this period, the indicator reverts to reading the signal...
Page 12 - seconds. The LCD display is now configured.
Quick Installation Guide 00825-0100-4593, Rev BA July 2009 Rosemount 1151 12 S TEP 5 CONTINUED ... Set the Display Equivalent to a 4 mA Signal 1. Unscrew the retaining ring shown in Figure 4 and remove the LCD display cover.2. Press the left button for two seconds.3. To decrement the display numbers...
Page 13 - Full Trim; Zero Trim; Using the HART Communicator; HART Fast Keys; HART Fast Keys
Quick Installation Guide 00825-0100-4593, Rev BAJuly 2009 Rosemount 1151 13 S TEP 6: T RIM THE T RANSMITTER NOTE Transmitters are shipped fully calibrated per request or by the factory default of full scale (span = upper range limit). Full Trim A full trim is a two-point sensor calibration where two...
Page 15 - RODUCT; Approved Manufacturing Locations
Quick Installation Guide 00825-0100-4593, Rev BAJuly 2009 Rosemount 1151 15 P RODUCT C ERTIFICATIONS Approved Manufacturing Locations Rosemount Inc. — Chanhassen, Minnesota, USAFisher-Rosemount GmbH & Co. — Wessling, GermanyEmerson Process Management Asia Pacific Private Limited — Singapore Beij...
Page 16 - Canadian Certifications; Canadian Standards Association (CSA) Approvals; European Certifications; EEx d IIC T6 (–40 °C; EEx d IIC T4 (–40 °C; II 1 GD; Ex ia IIC T4 (–60 °C; Entity Parameters
Quick Installation Guide 00825-0100-4593, Rev BA July 2009 Rosemount 1151 16 Canadian Certifications Canadian Standards Association (CSA) Approvals E6 Explosion Proof for Class I, Division 1, Groups C and D; Class II, Division 1, Groups E, F, and G; Class III, Division 1 Hazardous Locations. Suitabl...
Page 17 - II 3 GD; current limiting barrier.; Table 3. Entity Parameters
Quick Installation Guide 00825-0100-4593, Rev BAJuly 2009 Rosemount 1151 17 N1 ATEX Type N and Dust CertificationCertificate Number: BAS99ATEX3293XATEX Marking: II 3 GD Ex nL IIC T5 (-40 °C T amb 40 °C) EX nL IIC T4 (-40 °C T amb 80 °C) Dust Rating: T90 °C (T amb = -20 °C to 40 °C) Ui = 45 V...
Page 18 - metallic housing shall be bonded to the system earth.; Combination Certifications
Quick Installation Guide 00825-0100-4593, Rev BA July 2009 Rosemount 1151 18 N7 Type NCertificate Number: Aus Ex 122XEx n IIC T5 (T a = 80 °C) / T6 IP66 Special Conditions for safe use (x): 1. It is a condition of safe use that a nominal voltage of 30 V for Ex n application shall not be exceeded. 2....