Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to importantinformation: RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock symbol. CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your operator’s manual for additio...
Page 3 - Table of Contents; Introduction
EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 i Table of Contents 1 Introduction 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety Warnings 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....
Page 5 - Chapter 1; Up to six of Eaton’s Powerware; BladeUPS Bar 60; Figure 1. BladeUPS Bar 60 Installed in Rack
EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 1 Chapter 1 Introduction Up to six of Eaton’s Powerware ® BladeUPS ® uninterruptible power systems (UPSs) can be installed in an industry standard rack outfittedwith a BladeUPS Bar 60 for interconnecting the cabinets’ wiring. Fi...
Page 6 - Safety Warnings
INTRODUCTION EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 2 Safety Warnings IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that you should follow during installation andmaintenance of the BladeUPS Bar 60. Please read all i...
Page 7 - ВАЖНЫЕ УКАЗАНИЯ ПО МЕРАМ БЕЗОПАСНОСТИ
INTRODUCTION EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 3 WICHTIGE SICHERHEITSANWEISUNGEN AUFBEWAREN Dieses Handbuch enthält wichtige Hinweise, welche Sie bei der Installation und Wartungdes BladeUPS Bar 60 beachten sollten. Bitte lesen Sie alle Anweisungen des Handbuche...
Page 8 - INSTRUCCIONES DE SEGURIDAD IMPORTANTES
INTRODUCTION EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 4 INSTRUCCIONES DE SEGURIDAD IMPORTANTES GUARDE ESTAS INSTRUCCIONES Este manual contiene instrucciones importantes que debe seguir durante la instalación y elfuncionamiento del BladeUPS Bar 60. Por favor, lea todas ...
Page 9 - Chapter 2; Inspecting the Equipment; NOTE; Setup; Tools Required
EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 5 Chapter 2 Installation This section explains: S Equipment inspection S BladeUPS Bar 60 setup and installation Inspecting the Equipment If any equipment has been damaged during shipment, keep the shippingcartons and packing mat...
Page 10 - Checking the Package Contents
INSTALLATION EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 6 Checking the Package Contents Verify that the following items are included: S BladeUPS Bar 60 A six-socket bar with (1) attached terminal block assembly,(1) attached base bracket, and (3) attached mounting bracket...
Page 11 - Installation; To install the BladeUPS Bar 60:; C A U T I O N; Wireway Access Cover; Figure 2. Wireway Disassembly
INSTALLATION EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 7 Installation To install the BladeUPS Bar 60: 1. Remove the access cover and terminal block housing from thewireway housing (see Figure 2). Retain the wireway terminal blockhousing, wireway access cover, and screws...
Page 12 - Install six M6; Rear of Rack; Figure 3. Wireway Installation
INSTALLATION EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 8 4. Install an M6 hex nut onto each of the three wireway studs tosecure the wireway to the rear of the rack. Install the first stud inthe fourth hole location from the bottom. Do not tighten the nuts.Figure 4 shows...
Page 13 - Place the bar in the rack as shown in Figure 4.; Figure 4. Ferrite and Bar Placement
INSTALLATION EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 9 9. Place the ferrite assembly on the floor of the wireway and securewith the supplied tie wrap. Loop the tie wrap through bothattachment sites on the wireway floor and through the ferriteassembly. See Figure 4. 10...
Page 14 - of the rack. See Figure 5. Torque the bolts; front; Figure 5. Bar Base Installation
INSTALLATION EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 10 NOTE Verify that the bar is secure as shown in Figure 4. The sheetmetal at the base of the bar should be below the tab on the wireway floor. 12. Secure the bar to the wireway with three M6 × 12 hex bolts. Install...
Page 15 - Secure the base bracket to the rack with three M6; rear; Install two M6; Figure 6. Bar Bracket Installation
INSTALLATION EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 11 14. Secure the base bracket to the rack with three M6 × 12 hex bolts. Install the bolts from the rear of the rack. Use a large screwdriver or crowbar to lift the bar in place to alignthe holes in the base bracket...
Page 16 - Install two M4; Figure 7. Wireway Tab Attachment
INSTALLATION EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 12 16. Install two M4 × 8 pan-head screws into the tab on the wireway floor, securing the base of the bar to the wireway. See Figure 7.Torque the screws to 1.7 ± 0.2 Nm (15 ± 2 lb in). Rear of Rack Wireway Floor Tab...
Page 17 - Using two M6; Figure 8. Wireway Terminal Block Housing Installation
INSTALLATION EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 13 17. Using two M6 × 12 hex bolts, secure the left side of the wireway terminal block housing to the rack. See Figure 8. Torque the bolts to5.1 ± 0.8 Nm (45 ± 7 lb in). 18. Using nine M4 × 8 pan-head screws, secure...
Page 18 - Using five M4; Figure 9. Wireway Access Cover Installation
INSTALLATION EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 14 19. Using five M4 × 8 pan-head screws, install the wireway access cover. See Figure 9. Torque the screws to 1.7 ± 0.2 Nm (15 ± 2 lb in). M4 × 8 Pan-Head Screws (5 places) Wireway Access Cover Figure 9. Wireway Ac...
Page 19 - Using four M5; Front of Rack; Figure 11. Front Cover Mounting Panel Installation
INSTALLATION EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 15 21. Using four M5 × 16 hex bolts and four M5 cage nuts, secure the front cover mounting panel to the front of the rack. Verify that thebent edge of the panel is at the top. See Figure 11. Install the lower bolts ...
Page 20 - Snap the two front covers into place, as shown in Figure 12.; Figure 12. Front Cover Installation
INSTALLATION EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 16 22. Snap the two front covers into place, as shown in Figure 12. Front Covers(2 pieces) Figure 12. Front Cover Installation
Page 21 - Chapter 3; This section provides the following specifications:; Table 1. BladeUPS Bar 60; Depth of Wireway; Up to 6, using Anderson input/output connectors; Rack Placement; Bottom wireway fits into the bottom 6U of standard rack space
EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 17 Chapter 3 Specifications This section provides the following specifications: Table 1. BladeUPS Bar 60 Dimensions (WxDxH) 14.0 × 11.3 × 183.8 cm (5.5 ” × 4.4 ” × 72.4 ” ) Depth of Wireway 90.1 cm (35.5 ” ), excluding front cov...
Page 23 - Chapter 4; Local Distributor; Call your local service representative
EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 19 Chapter 4 Service and Support If you have any questions or problems with the BladeUPS Bar, call your Local Distributor or the Help Desk at one of the following telephone numbers and ask for a UPS technical representative. Uni...